The approved
vent terminal must be installed so that flue gases will not jeopardize
people, overheat combustible
structures
or enter into buildings,
and so that proper clearances
are maintained
(See Fig 5).
a)
The vent terminal
shall not be less than 7 feet above a public walkway.
b)
The vent terminal shall terminate
at least 3 feet above any (mechanical)
air inlet within
10 feet.
c)
The vent terminal shall not be within a 6-foot radius from a gas meter or regulator.
d)
The vent terminal
shall be a minimum
of 6 feet from any combustion
air inlet.
e)
The vent terminal
shall terminate
from an opening
window,
at least 4 feet below or 4 feet horizontally
from the
opening.
f)
The vent terminal
shall terminate
from a door, at least 1 foot above and 4 feet horizontally
from the door.
g)
The vent terminal
shall not be less than 3 feet from an adjacent
building.
h)
The vent terminal
shall not be less than 1 foot above grade.
VENT
HOO_
MUST
BE MOUNTED
ONE FOOT MINIMUM
ABOVE DOORS AND WINDOWS
J
VENTHOOD
VENT
HOOD
MUST
BE
MOUNTED
FOUR
FEET
AWAY
FROM
DOORS
AND
WINDOWS
VENT
HOOD
MUST
BE MOUNTED
FOUR
FEET
MINIMUM
BELOW
WINDOWS
Fig 5: Side wall exit locations for mechanical draft vent terminals