Main Burner
Flames:
The main burner flames
should
be
blue, with a more intense blue cone in the center core. Yellow
flames could
be a sign of wrong size gas orifices
or dirty
burners, or a blockage
on the heat exchangers
fins. If some
burners have yellow flames while others have good flames,
it is likely that dust, lint or spider webs have partially clogged
the burner
venturis.
To clean the burners,
contact
a gas
service person.
Mineral Scale Build-up:
AquaStars,
when operated at lower
temperature
settings, do not accumulate
mineral buildup.
If
however,
the heater is used
at the higher
temperature
settings
and the water has a high mineral content,
periodic
descaling
may
be necessary.
The heating coils should
be
flushed
with a descaling
solution.
Consult your dealer or service person.
TROUBLE
SHOOTING
(see maintenance
table)
Introduction
The AquaStar
125FX pilot and burners are ignited by a water
flow valve. Numerous
water related problems
can cause
this water valve to malfunction
such as: Insufficient
water
flow volume
to activate
the burners
at its minimum
flow
requirement;
Dirt
in the water
flow
valve causing
it to
malfunction;
Sediment build-up in faucet aerators, or shower
heads; Uneven pressures
between
cold and hot with single
lever faucets; Plumbing
cross overs. These water flow related
problems
can cause the heater to deriver less than its furl
output, or to fail to ignite or to shut down completely.
Problems are stated in upper case, bold face. Most common
causes
for the problems
follow
in order of likelihood.
The
suggested
solutions
require that the cover be taken off. To
do this, pull off the temperature
knob and unscrew
and
remove the temperature
knob collar. Pull main cover out
toward you and lift up and out.
NO SPARK AT TH E PI LOT
1. On/Off switch is not "On" (Position "•
").
The On/Off switch is located behind the flipdown cover
plate on the front panel strip. See fig. 10.
2. Bad electrical connections.
Be certain
that all electrical
connections
are clean, tight,
and free of any moisture.
3. Water flow is not sufficient
to activate heater.
Water flow rate at faucet is below minimum flow needed to
activate heater. When temperature
adjustment
knob is turned
all the way clockwise,
the AquaStar
model 125FX requires
1/2 gallon
per minute flow
to activate
the heater. As a
reference,
this is a flow which
would fill a quart jar in 30
seconds.
If the temperature
adjustment
knob is turned fully
counterclockwise,
afiow rate of 1.1 gallons/minute
is required
to activate
the heater.
4. Bad fuse
Check the viability of the fuse (see Fig 9 (#9) for location
of fuse). Replace if necessary.
5. Water inlet filter is clogged
Water flow is restricted, preventing flow needed to activate
heater. Clean water inlet filter screen.
6. Cross
over in water lines
To confirm
there is no cross-over
in the plumbing,
shut off
the cold water
supply
to the AquaStar
water
heater and
open a hot water faucet.
There should
not be any water
flowing at that faucet. Water running is a sign of a plumbing
cross-over.
Consult your plumber.
7. Microswitch
needs to be adjusted
or replaced.
If you do not hear a click
when
a tap is opened,
the
microswitch
needs to be adjusted.
See Fig. 15 (#11) for
location
and see Fig. 14 for adjustment.
The microswitch
may need to be replaced.
Adjusting screw
L_
Fig. 14 - microswitch adjustment
Pilot
does not spark
with
water flow
Close water tap
Remove
screw
cap
and
unscrew
till sparking
starts
Screw
in turning
one and a
half turns
Pilot
always
sparks
without
water
flow
1 Close water tap
2 Screw
in adjusting
screw
until it stops sparking
3 Continue
to
screw
in
turning
one
and
a
half
turns
more
8. Cold incoming
water connection
made to wrong side
of heater
Make sure cold water inlet connection
is on the right side
when you are facing the AquaStar.
9. Water valve parts may be dirty or components
damaged
First check that venturi is free of dirt particles.
Water valve
and component
parts must be totally free of dirt.
Mineral deposits
can eventually
(3-5 years in hard water
areas) corrode
the water valve parts to a point where they
will need replacing. Any sign of moisture
at the bleed hole
is a sign that
the
water
valve
needs
to be replaced
immediately.
10. Poor circuit connections atthe ECO (overheat sensor)
or the flue gas safety device
Ignition sparker will not operate if the electrical circuit is
interrupted. Check that the connections to the ECO are
secure and tighten if necessary.
11. Reset electrical
power to heater
If resetting the electrical
power corrected
the symptom then
likely the unit's Safety Spill switch (Flue gas safety device -
#33
on page 20) had tripped
from a flue blockage
during
the previous usage. Inadequate
combustion
air to the room
area can also cause the unit to improperly
vent. Improper
venting
or insufficient
combustion
air must be corrected.
Consult a licensed
professional
to inspect
the installation.