Bosch AquaStar 125FX LP Installation And Operating Instructions Manual page 8

Automatic instantaneous type water heater for use with natural and liquefied petroleum gas

Advertisement

Installing
Flue collar
Remove 4 screws
from the top of the heater leaving the
plate in place. The supplied
exhaust collar must be fitted to
this heater before
connecting
the vent, align the exhaust
collar and tighten with the 4 screws.
4"single wall venting only. Use
stainless steel (AL29-4C)
or
galvanized
pipe of 26 minimum
gauge
must be used.
Each
connection
must be properly
sealed.
HORIZONTAL
SIDE WALL
* Maximum
15 feet with 2 elbows.
Deduct 5 feet for each additional
elbow.
/y
Approved Vent Terminal
(FXHOOD
or other approved
terminal)
The FXHOOD
is design
approved
with
the
Aquastar
125FX and has a built in back draft
flapper to prevent negative air from freezing the
Aquastar
- see Fig. 5 for restrictions
in location
of vent terminal.
4"single wall venting only. Use
stainless
steel (AL29-4C)
or
galvanized
pipe of 26 minimum
gauge
must be used.
Each
connection
must be properly
sealed.
Approved Vent Terminal
(FXHOOD
or other approved
terminal)
The FXHOOD
is design
approved
with
the
Aquastar
125FX and has a built in back draft
flapper to prevent negative air from freezing the
Aquastar - see Fig. 5 for restrictions
in location
of vent terminal.
5
-,.,',,.
Fig 4: Some Venting
Guide Suggestions
An approved
side wall vent terminal
must be used when the water heater is vented through a side
wall. Locate in accordance
with ANSI Z223.1 and local applicable
codes.
See Fig 5 for restrictions
in location of vent terminal in relation to opening
doors and windows,
grade, and forced air inlets.
Be certain that snow and ice will not interfere with the vent.
8