ICP NAC048AKA1 Installation Instructions Manual
ICP NAC048AKA1 Installation Instructions Manual

ICP NAC048AKA1 Installation Instructions Manual

Split system premium line ac & hp condensers

Advertisement

INSTALLATION
INSTRUCTIONS
Split System
Premium Line
AC & HP Condensers
These instructions must be read and understood completely before attempting installation.
Installation / Startup Information & Warranty
Installation
or
repairs
made
by
unqualified
persons can result in hazards to you and others.
Installation
MUST conform with local building
codes or, in the absence of local codes, with the
the
National
Electrical
Code
NFPA
70/ANSI
C1-1999
or
current
edition
and
Canadian
Electrical Code Part 1 CSA C.22.1.
The information
contained
in this manual
is
intended for use by a qualified service technician
familiar with safety procedures
and equipped
with the proper tools and test instruments.
Failure to carefully read and follow all instruc-
tions in this manual
can result in equipment
malfunction,
property damage,
personal injury
and/or death.
After uncrating unit, inspect thoroughly for hidden damage.
If damage is found, notify the transportation company im-
mediately and file a concealed damage claim.
Locating The Outdoor Unit:
CAUTION
Improper installation, adjustment,
alteration,
service or
maintenance can void the warranty.
The weight of the condensing
unit requires caution and
proper handling procedures when lifting or moving to avoid
personal injury. Use care to avoid contact with sharp or
pointed edges.
Safety Precautions
1. Always wear safety eye wear and work gloves when
installing equipment.
2. Never assume electrical power is disconnected. Check
with meter and disconnect.
3. Keep hands out of fan areas when power is connected
to equipment.
4. R-22 causes frost-bite burns.
5. R-22 is toxic when burned.
NOTE TO INSTALLING DEALER: The Owners Instruc-
tions and Warranty are to be given to the owner or promi-
nently displayed near the indoor Furnace/Air Handler Unit.
Check local codes covering zoning, noise, platforms.
If practical, avoid locating next to fresh air intakes, vent or
bedroom windows. Noise may carry into the openings and
disturb people inside.
Placement of the unit should be in a well drained area or
unit must be supported high enough so runoffwill not enter
the unit.
Do not locate where heat, lint or exhaust fumes will be dis-
charged on unit (as from dryer vents).
Roof top installations are acceptable providing the roof will
support the unit and provisions are made for water drain-
age and the noise or vibration through the structure.
Do not install the unit in a recessed or confined area where
recirculation of discharge air may occur.
Heat Pumps Only: The top surface of platform must be
above average winter snow levels to prevent coil blockage.
Clearances:
Nominal operating clearances,
where practical, are 48
inches (120 cm) above unit for discharge air and 18 inches
(40cm) around coil for intake air on three sides. Clearance
on one side (normally between unit and structure) may be
reduced to 6 inches (15cm). Nominal clearances are based
from a solid parallel object, wall, roof overhang, etc.
Do Not install under roof overhangs without guttering. A
minimum vertical clearance of 48" is required to overhang.
The clearance may be reduced from a single object with a
small surface area, such as the end of a wall, outside cor-
ner of a wall, fence section or a post, etc. As a general rule
the width ofthe object should equal the minimum clearance
from the unit. For example, a 4 inch (lOcm) fence post
could be 4 inches (lOcm) from the unit.
421 01 3202 02
Dec. 2004

Advertisement

Table of Contents
loading

Summary of Contents for ICP NAC048AKA1

  • Page 1 INSTALLATION INSTRUCTIONS Split System Premium Line AC & HP Condensers These instructions must be read and understood completely before attempting installation. Installation / Startup Information & Warranty CAUTION Improper installation, adjustment, alteration, service or Installation repairs made unqualified maintenance can void the warranty. persons can result in hazards to you and others.
  • Page 2: Unit Support

    _ Installation Instructions Split System Condensers Inside corner locations on single story structures require A service clearance of 24 inches (60cm) is desirable from evaluation. Large overhanging soffits may cause air recir- control box end or side. Control box and corner panel be- low it can be loosened and moved out to the side to facili- culation in a corner area even though recommended clear- ances are maintained.
  • Page 3 I Split System Condensers Installation Instructions Figure 2 Clearances Minimum Clearances Recommended Clearances Minimum Clearances 24" 24" 24" 24'_ 18" 24" Minimum Clearances Minimum Clearances 24" 24" 24" 24" 24" 18" Pipe Installing Refrigerant Lines Component Matches Changing the Restrictor Orifice Check to see that you have the proper system compo- The restrictor orifice is located in a fitting in the liquid line.
  • Page 4 I Installation Instructions Split System Condensers Line Valves Refrigeration Line Sets If it is necessary to add tubing in the field, use dehydrated or The outdoor condensing unit is supplied with straight sweat dry sealed deoxidized copper refrigeration tube. DO NOT brass service valves with copper stubs.
  • Page 5 I Split System Condensers Installation Instructions For valves with retaining rings: Replace service valve Evacuating, And Charging Instructions cap and torque to; 8-11 ft. Ibs. on 1/4" and 3/8" valves, NOTE 12-16 ft. Ibs. on 5/8" and 3/4", 15-21 ft. Ibs on 7/8" valves. If Intentional release of CFC or HCFC Refrigerant to the torque wrench is not available, tighten cap finger tight and Atmosphere violates Federal Law, It may also violate...
  • Page 6: Electrical Wiring

    Split System Condensers Installation Instructions Electrical Wiring Wiring Connections Make all outdoor electrical supply (Line Voltage) connec- Electrical Shock Hazard. tions with rain-tight conduit and fittings. Most codes re- quire a disconnect switch outdoors within sight of the unit. Shut off electric power at fuse box or service pan- Route Line Voltage wiring through entrance and through el before making any electrical connections.
  • Page 7 I Split System Condensers Installation Instructions A/C Condenser Typical Low Figure Sensor Probe Mounting Figure !i Voltage Connections (1) Pull ambient sensor probe through 3/8" diameter hole located on the external electrical connection panel. Indoor Outdoor Thermostat Unit ontactor) (Compressor 318"...
  • Page 8: Start-Up Procedure

    _ Installation Instructions Split System Condensers Start-Up Procedure 2. Measure and record the suction line refrigeration pres- Start-up Procedure sure. (Measure at the suction line service valve gauge 1. Close electrical disconnects to energize system. port.) Using Temperature / Pressure Chart convert this pressuretothe saturation refrigerant temperature.
  • Page 9 I Split System Condensers Installation Instructions If the actual superheat readings are lower than shown, the With the unit operating, close all doors, windows, storm windows, and openings to the house. Set the system is most likely over-charged, and charge should be thermostat to the desired setting.
  • Page 10 Split System Condensers Installation Instructions Adjustable TVX Figure 17 Figuie ! 5 Non-AdjustableTVX Adjustable Do Not Remove Mark CAUTION: Do not remove the cap on a Non-Adjustable TXV. Note: It is recommended that a reference mark be made on the TXV body and the adjustment stem before adjustments are made.
  • Page 11: Defrost Control

    I Split System Condensers Installation Instructions Table A-1 shows the subcooling range at 47 degrees F Adjusting Defrost Time - outdoor ambient and 70 degrees F dry bulb indoor ambient Figure 18 [ Time Temperature Type temperature conditions. Table A-1 Heat Pump Model Subcooling Range at...
  • Page 12: Maintenance

    _ Installation Instructions Split System Condensers Maintenance Free air flow is essential. Keep the outdoor coil clean and free of restrictions. Keep fences, shrubs, snow drifts and any other obstructions at least two feet from Electrical Shock Hazard. all coil air inlets. Shut off electric power at fuse box or service pan- Keep the coil free of grass clippings, weeds and other debris.

Table of Contents