Figure 4-4 (Continued)
40, 50 & 55 Ton Supply Fan Performance with Inlet Guide Vanes
8.0
7.5
7.0
1200 RPM
6.5
6.0
1100 RPM
5.5
5.0
1000 RPM
4.5
4.0
900 RPM
3.5
3.0
800 RPM
2.5
700 RPM
2.0
600 RPM
1.5
500 RPM
1.0
0.5
0.0
0
2000
4000
6000
60, 70 & 75 Ton Supply Fan Performance with Inlet Guide Vanes
8.0
1200 RPM
7.5
1100 RPM
7.0
6.5
1000 RPM
6.0
5.5
5.0
900 RPM
4.5
4.0
800 RPM
3.5
3.0
700 RPM
2.5
600 RPM
2.0
1.5
500 RPM
1.0
0.5
0.0
0
3000
6000
30 HP
25 HP
20 HP
15 HP
10 HP
7.5 HP
5 HP
8000
10000 12000 14000 16000 18000 20000 22000 24000 26000 28000 30000
CFM
25 HP
20 HP
15 HP
10 HP
7.5 HP
9000
12000
15000
18000
CFM
40 HP
50%
50 HP
40 HP
30 HP
21000
24000
27000
74
S_HFC40, C50, C55
Dual 20 X 20 Fans
Entrance Losses
- with Inlet Guide Vanes
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust
60%
Fan Curve Limits
70%
- Minimum Motor HP = 7.5
- Maximum Motor HP
C40, C50 & C55 = 30 HP
- Maximum RPM
20 - 30 HP = 1170
80%
- Maximum CFM
- Maximum Static Pressure
Leaving the Unit = 4.0" w.c.
90%
S_HFC60, C70, C75
Dual 22 X 22 Fans
Entrance Losses
- with Inlet Guide Vanes
- without Evap Coil
- without Filters
- without Return Air Dampers
50%
- without Exhaust
Fan Curve Limits
- Minimum Motor HP = 10
- Maximum Motor HP = 40
60%
- Maximum RPM = 1130
- Maximum CFM
- Maximum Static Pressure
70%
Leaving the Unit = 4.0" w.c.
80%
90% wocfm
30000
33000
36000
7.5 - 15 HP = 1141
C40 = 18,000
C50 = 22,500
C55 = 24,000
C60 = 27,000
C70 & C75 = 30,000

Hide quick links: