Dell PowerEdge M620 Getting Started Manual page 9

Document
Hide thumbs Also See for PowerEdge M620:
Table of Contents

Advertisement

Power — Blades
Coin-cell battery
Power — Enclosure
AC/DC power supply (per power supply
module)
Wattage
Connector
Heat dissipation
Maximum inrush current
System Voltage Requirements
NOTE: This system is also designed to be
connected to IT power systems with a
phase to phase voltage not exceeding
230 V.
NOTE: Heat dissipation is calculated by
using the power supply wattage rating.
Physical — Blades
PowerEdge M915
Height
Width
Depth
Weight (maximum)
PowerEdge M910
Height
Width
Depth
Weight (maximum)
PowerEdge M710 and M610x
3 V CR2032 Lithium coin cell
2360 W and 2700 W
IEC C20
1205 BTU/hr (maximum)
Under typical line conditions and over
the entire system ambient operating
range, the inrush current may reach 55 A
per power supply for 10 ms or less.
43 A, 200 V AC to 240 V AC, 50 Hz/60 Hz
(2360 W power supply)
16 A, 100 V AC to 240 V AC, 50 Hz/60 Hz
(2700 W power supply)
38.5 cm (15.2 inch)
5 cm (2 inch)
48.6 cm (19.2 inch)
12.7 kg (28 lb)
38.5 cm (15.2 inch)
5 cm (2 inch)
48.6 cm (19.2 inch)
13.1 kg (29 lb)