Switch Mode Power Supply DRP024V060W1BA Technical Data 60W1Ph Input Data (1) Nominal input voltage and frequency 100-240VAC / 50-60Hz 85-264VAC (120 – 375 VDC) Voltage range Frequency Range 47-63Hz Nominal current 1.5A max @115VAC, 1.0A max @230VAC Inrush current limitation. I2t (+25°C) typ. <...
Page 3
Switch Mode Power Supply DRP024V060W1BA General Data Isolation voltage: Input / output type test/routine test 4 KVAC / 3 KVAC Input / PE type test/routine test 1.5 KVAC / 1.5 KVAC output / PE type test/routine test 1.5 KVAC / 500 VAC Degree of protection IP20 Class of protection...
Page 4
Switch Mode Power Supply DRP024V060W1BA Numbering for DIN Rail Power Supply DRP024V060W1BA For example: XX X XXXX XXXX X XX XX X XXXX XXXX X XX XXXX……………Watt XX………………….Product Type 060W 60 Watt DinRail 120W 120 Watt 240W 240 Watt XX X XXXX XXXX X XX 480W 480 Watt X………………….Model...
Page 5
Switch Mode Power Supply DRP024V060W1BA Block Diagrams/Connections: Block Diagram of Power Supply, DRP024V060W1BA 5/13 Rev: 00, 1/10/2011...
Switch Mode Power Supply DRP024V060W1BA Engineering Data Derating Curve (Both of Horizontal and Vertical) Model: DRP024V060W1BA 110% 100% Ambient Temperature (C) Note: 1. Do not use the device in areas outside recover when ambient temperature of the shaded portion shown in the drops to 50°C or output capacity is above graph.
Switch Mode Power Supply DRP024V060W1BA Overload Protection The Power Supply is provided with an overload protection (OLP) function which protects the power supply from possible damage caused by excess current. The Power Supply also has an over temperature protection (OTP) in case overload condition persists for an extended duration and is below the overload trigger point but >...
Switch Mode Power Supply DRP024V060W1BA Overvoltage protection The Power Supply has an overvoltage protection (OVP) and is activated when the power supply feedback circuit fails. The output voltage will not be > 35V under any Line/Load and operating ambient temperature. The Power Supply does not shut down but goes into Hiccup mode (Auto-Recovery).
Page 10
Switch Mode Power Supply DRP024V060W1BA Hold-up Time, Hold time is the time when the AC input collapses and o/p voltage retains regulation for a certain period of time is called as hold up time. See in the picture below a typical hold up time characteristic of a power supply.
Page 11
Switch Mode Power Supply DRP024V060W1BA Surge Load See below typical surge load capability of the power supply, the PSU is capable of delivering 3 secs of Surge load about 150% of I max the o/p voltage can be out of regulation limits of + 5%. Dynamic Load ...
Page 12
Switch Mode Power Supply DRP024V060W1BA Redundancy & Parallel Operation with ORing Diode See picture below for a typical Redundant/Parallel operation using CliQ II Series Power Supplies. Power Supply Unit 1 (PSU1) and Power Supply Unit 2 (PSU2) are connected through a twin diode where Anode 1 (A1) is connected to the +Ve of PSU1 and A2 is connected to the +Ve of PSU2 and both output ground are shorted together.
Page 13
Switch Mode Power Supply DRP024V060W1BA Parallel Operation: When 2 Power Supplies are connected in parallel, they can share the load if the following steps are taken. Step 1: Measure the output voltages at no load from A1 to Ground i.e. VA1 to Ground of PSU1 and VA2 to Ground of PSU2.