Engineering Data - Delta Electronics DRP024V060W1BA Manual

Switch mode power supply 60w 1phase cliq ll din rail
Table of Contents

Advertisement

Engineering Data

 Derating Curve (Both of Horizontal and Vertical)
Model: DRP024V060W1BA
o
Note:
1. Do not use the device in areas outside
of the shaded portion shown in the
above
graph.
gradually
deteriorate
damaged.
2. Based on the above graph, if the
ambient temperature is greater than
50°C, the output capacity has to be
reduced
by
temperature increase. If not, the device
will
go
protection by switching off i.e. device
will go into bouncing mode. It will
6/13
1/10/2011
Switch Mode Power Supply
110%
100%
90%
80%
70%
60%
50%
40%
30%
20%
10%
0%
-20
-10
0
Internal
parts
and
become
2.5%
per
Celsius
into
over-temperature
10
20
30
40
50
Ambient Temperature (C)
recover
drops to 50°C or output capacity is
may
reduced as recommended in the graph.
3. If the device has to be mounted in any
other direction, please contact your
service provider for more details.
4. In order for the device to function in
the manner intended, it is also
necessary to observe a lateral spacing
of 2cm from other equipments.
5. Depending on the ambient temperature
and output capacity of the device, the
device housing can be very hot!
60
70
80
when
ambient
DRP024V060W1BA
temperature
Rev: 00,

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents