Data Point
DC-To-DC Converter On
Load On Inverter
Bypass Active
Load On Battery
Permanently On Bypass
Bypass SCR Open Circuit
Low Battery - Shutdown
Imminent
Output Overload
Inverter Unsynchronized
Input Power Supply Fail
Bypass Input
Voltage/Frequency Fault
Data Point
Number Of Input Lines
Number Of Bypass Lines
Number Of Output Lines
Number Of SubModules
Number Of Battery Cells
Load Circuit Present
Load (Apparent Power)
Load (Real Power)
Input Frequency
Output Frequency
Battery Voltage
Battery Current
(Charge/Discharge)
Battery Charge Percentage
Ambient Temperature
Input Voltage L1
Input Current L1
Output Voltage L1
Output Current L1
Input Voltage L2
Liebert HiNet
Supported Modbus Points
Status
Coil
10042
10073
10074
10128
10133
10149
10152
10154
10160
10186
10202
Input
Holding
Register
Register# of Reg. Scale
30004
40004
30004
40004
30004
40004
30009
40009
30012
40012
30013
40013
30102
30104
30107
30108
30113
30114
30116
30119
30153
30154
30163
30164
30203
22
Liebert Monitoring Group –Development
Notes / Units
# of Reg. Scale
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Notes / Units
Bits 12 - 15
1
1
Bits 4 - 7
1
1
Bits 8 - 11
1
1
1
1
1
1
There are 16 possible Load
Circuits. So each bit
represents 1 load circuit.
Load Circuit 1 is bit 0, Load
Circuit 2 is bit 1 and so on.
If the bit is 1 then the Load
1
Circuit is supported.
VA
2
1
W
2
1
10 Hz
1
10 Hz
1
V
1
1
A
1
1
%
1
1
deg C
1
1
V
1
1
A
1
1
V
1
1
A
1
1
V
1
1
7/6/2007
REV. 5