Fire-Lite 411UDAC Installation, Programming, Troubleshooting And Operating Instruction Manual page 37

Fire alarm communicator
Table of Contents

Advertisement

Program Mode
• D = three second pause
• E = five second pause
• F = end of phone number (Note: F must remain in all unused phone number addresses)
If the first digit of the Primary Central Station Phone Number remains 'F' and the digital communicator is enabled for
transmission to a Central Station, a primary phone number fault will be generated. The phone number must begin
with a digit other than 'F.'
New FCC regulations allow extra digits to the CIC (Carrier ID Code), to identify the long distance carrier. The
expanded phone number field of 20 digits facilitates this function. Simply enter the digits required by the telephone
company if desired.
Primary Central Station Number Communication Format (20)
One location is needed to select the Communication Format to the primary phone number. Address 20 is used for
this purpose. The factory default setting for this address is 'E', which is Contact ID Format. You may enter '0'
through 'D' in place of the default, then press [ENTER/STORE]. Choose from the list of formats below:
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Contact ID, DTMF, 1400/2300 ACK
F: Future use
Consult the Central Station for proper Format selection. For any Format chosen, all event codes are automati-
cally programmed by the 411UDAC. Refer to Table 3-2, "4+2 Standard and 4+2 Express Formats - Primary," on
page 40, Table 3-3, "All 3+1, 4+1 and 4+2 Expanded Formats - Primary," on page 41 and Table 3-1, "Ademco
Contact ID Format - Primary," on page 39.
Event Codes - Setting Entries
The Format selected in address 20 will cause the 411UDAC to automatically program addresses 145 - 228 with the
factory default settings. Any of the Event Code settings may be altered. Consult your Central Station prior to alter-
ing the event code settings. An entry of all zeros for any event code will cause the communicator to NOT transmit the
report. Transmission of reports to either or both Central Station phone numbers may be disabled.
411UDAC
Document #51073
Rev. D 12/09/2008
P/N 51073:D