Programmer Key Functions; Programmer Keypad - Fire-Lite 411UDAC Installation, Programming, Troubleshooting And Operating Instruction Manual

Fire alarm communicator
Table of Contents

Advertisement

Normal Mode
The 411UDAC meets NFPA 72 requirements for Remote Station Protective Signaling Service and Central Station
Signaling Service reporting requirements for: (a) the type of signal, (b) condition and (c) location of the reporting
premises. See "Central Station Communications" on page 55, for additional information.
The 411UDAC can be switched from Normal Mode to any other Mode, provided no channel programmed for fire
alarm or fire supervisory is active, that is, in alarm (shorted). The PRO-411 DACT Programmer, for use with the
Fire•Watch 411 Series, must be connected to the 411UDAC in order to change from mode to mode.

3.1.1 Programmer Key Functions

Programmer Keypad

FIGURE 3-1:
Address entry keys are 0 to 9
Data entry keys are 0 to 9 and A to F
MODE KEY
Pressing the MODE key followed by a valid 4-digit numerical code and the [ENTER/STORE] key selects one of
the five modes of operation. To enter Normal Mode from any other mode, press the MODE key followed by
6676 and then [ENTER/STORE].
6676 spells NORM on a Touch-Tone
If an incorrect key is entered, reenter the proper 4-digit code before pressing the [ENTER/STORE] key. Note that as
information is entered into the 411UDAC, the digits will scroll across the Programmer display from right to left.
___6
__66
_667
6676
A pause of up to 10 seconds between each number is allowed while entering the code.
32
®
phone.
411UDAC
Document #51073
Rev. D 12/09/2008
Select operating mode
Increment memory address
Decrement memory address
One press = first memory address
Two presses = type any address
Save data, go to next address
P/N 51073:D