Safety stop function
Hide thumbs Also See for FR-D700:

Advertisement

Wiring
The safety related terminals are described in Table.2 and Table.3
Terminal
Symbol
For input of safety stop channel1.
S1-SC is
S1
Open: In safety stop mode.
Short: Non safety stop mode.
For input of safety stop channel2.
S2-SC is
S2
Open: In safety stop mode.
Short: Non safety stop mode.
As output for safety stop condition.
SO terminal type is 'Open collector output'.
SO-SC is
SO
OFF(Open) :Drive enabled
ON(Close) :Drive shutoff, no fault
Important: SO terminal should be used for monitoring safety stop
condition only. SO terminal cannot be used for safety function.
Common terminal for S1,S2,SOsignals.
SC
*SC is connected terminal SD internally.
As output for failure detection and alarm. RUN terminal type is 'Open
collector output'.
RUN-SE is
OFF(Open): Detect failure or Alarm.
ON(Close): No failure detected.
RUN
Attention: To use RUN terminal for monitor output of failure
Note: This terminal can be used for alarm or to prevent restart only,
SE
Common terminal for safety RUN signal.
As output for failure detection. A,C terminal type is 'Relay output'.
A-C is
OFF(Open): Detect failure or Alarm.
ON(Close): No failure detected.
A,C
Attention: To use A,C terminal for monitor output of failure
Note: This terminal can be used for alarm or to prevent restart only,
SD
Signal ground
Input power
S1-SC
OFF
-
Short
ON
Open
Short
Open
Table.2 The safety related terminals
Description
detection, The parameter No.190 should be set 199
(Alarm output).
no other safety function.
detection, The parameter No.192 should be set 199
(Alarm output).
no other safety function.
Table.3 Truth table of Safety related signals
S2-SC
Failure
-
-
OFF(Open)
No failure
OFF(Open)
Short
Detected
OFF(Open)
No failure
Open
Detected
OFF(Open)
Open
Detected
OFF(Open)
Short
Detected
OFF(Open)
SO-SC
RUN-SE or A-C
OFF(Open)
ON(Close)
OFF(Open)
ON(Close)
ON(Close)
OFF(Open)
OFF(Open)
OFF(Open)
3
Rating
Input resistance:4.7kOhm
Current : 4 to 6 mA
(In case of shorted to SC)
Voltage : 21 to 26 V
(In case of open from SC)
Load: 24VDC/0.1A max.
Voltage drop: 3.4V max.
(In case of 'ON' state)
Load: 24VDC/0.1A max.
Voltage drop: 3.4V max.
(In case of 'ON' state)
Load: 30VDC/0.3A max.
Drive state
Drive shutoff (Safe state)
Drive enable
Drive shutoff (Safe state)
Drive shutoff (Safe state)
Drive shutoff (Safe state)
Drive shutoff (Safe state)
Drive shutoff (Safe state)