Safety stop function
Hide thumbs Also See for FR-D700:

Advertisement

Example 2
START
EM
+24V
X0
X1
COM0
Safety
DC24V
Logic
Circuit
24G
MITSUBISHI MELSEC Safety relay unit
QS90SR2SN-Q
Fig.5 Safety system example 2 – STOP synchronous with EM and fault detection through RUN output.
For safety stop, configure the wiring as shown in Fig.4 above.
Note: the above wiring is configured to prevent restart in case of a fault.
XS0 should be connected to RUN terminal and XS1 should be connected to SE, because polarity of XS0 is
positive, XS1 is negative.
The parameter No.190 must be set to '199'. This setting makes the RUN output to turn off in case of
failure.
After the power-up, to reset the safety stop mode, press the START switch, and also press the STF switch,
then start the motor rotation.
In the above Fig.4, wired example2, in the event of reset of 'safe-condition' the motor rotation will not occur
until STF is pressed.
(for normal 'non-safety' STF/STOP function, please refer to your drive's User Manual)
To prevent restart in case of recovering from input power loss of drive, 3-wired connection for STF/STOP
control is recommended.
In case of 2-wire connection and using latching type switch to short between STF and SD/PC for starting,
ensure the compliance with safety requirement for the restarting when the drive recover from input power
loss.
STF
STOP
XS0
XS1
Z00
Z10
Z20
COM1
K1
K2
Z01
Z11
Z21
RUN
SE
STF
STOP
SINK
CPU
S1
S2
SC
SD
ATTENTION
7
R S T
IGBTs
Gate
Gate
Driver
Driver
U V W
FR-D700
IM