16
Configuring Drive Parameters
"B" Group: Fine Tuning Functions
For the following functions, L100-M Series inverters have new ranges or descriptions.
Func.
Name /
Code
SRW Display
B_12 Level of electronic
thermal setting
E-THM LVL 03.00A
B_13 Electronic thermal
characteristic
E-THM CHAR
NOTE: The set value links with the detection current of output current monitor, electric
thermal protection, and overload limit.
The three available electronic thermal characteristic curves are shown in the graph
below.
WARNING: When parameter B_12, level of electronic thermal setting, is set to device
FLA rating (Full Load Ampere nameplate rating), the device provides solid state motor
overload protection at 115% of device FLA or equivalent. Parameter B_12, level of
electronic thermal setting, is a variable parameter.
"B" Function
Description
Set a level between 5% and
120% for the rated inverter
current.
Select from three curves,
option codes:
00...Reduced torque
CRT
01...Constant torque
02...Reduced torque 2
Torque
B_13 = 01
100%
80%
60%
0
5
20
Run
Mode
–MFU2
Edit
Rated current for
each inverter model
01
Constant torque
B_13 = 02
Reduced torque 2
B_13 = 00 Reduced torque
60
Output frequency
Defaults
-MFR2
Units
%
00
Hz
120