Advertisement

Quick Links

MODELS DESCRIBED IN THIS MANUAL
AT650, GS650 (650VA)
AT800, GS800 (800VA)
AT1200, GS1200 (1200VA)
AT1600, GS1600 (1600VA)
AT2300, GS2300 (2300VA)
OWNER'S MANUAL

Advertisement

Table of Contents
loading

Summary of Contents for Minuteman AT1200

  • Page 1 MODELS DESCRIBED IN THIS MANUAL AT650, GS650 (650VA) AT800, GS800 (800VA) AT1200, GS1200 (1200VA) AT1600, GS1600 (1600VA) AT2300, GS2300 (2300VA) OWNER'S MANUAL...
  • Page 2: Table Of Contents

    TABLE OF CONTENTS PAGE Introduction ………………………………………………………………. 1 Receiving Inspection …………………………………………………… 1 Warranty Registration ………………………………………………….. 1 Important Safety Instructions ………………………………………….. 1 Selection of UPS Location ……………………………………………… 2 Electrical Specifications ………………………………………………… 3 Other Electrical Specifications ………………………………….4 Physical Specifications ………………………………………………….. 4 Unit Description ………………………………………………………….. 5 GS Models ………………………………………………………..
  • Page 3: Introduction

    INTRODUCTION Congratulations on your purchase of a MINUTEMAN "AT" Series Synchronized Sinewave Uninterruptible Power Supply (UPS). Each unit is designed to provide superior, total power protection for personal computers, telephone systems and any other sensitive or critical electronic equipment against all commercial power anomalies. These models provide light and audible alarm indications, so the user will know the status of both commercial power and the MINUTEMAN "AT"...
  • Page 4: Selection Of Ups Location

    the plug is removed to simulate a power failure (not recommended), do not touch the plug conductors or the chassis while the lug is removed. CAUTION -- Do not allow water or any foreign object to enter the UPS. In case this occurs, immediately turn the unit power switch off and unplug the MINUTEMAN from the commercial receptacle.
  • Page 5: Electrical Specifications

    Route unit power-cords so it cannot be walked on or damage. ELECTRICAL SPECIFICATIONS Electrical Specifications Battery Time Max Heat Output System (Min) Dissipation Rated Output Freq. Input Back Up Model Watts VAC/A VAC/A Full Load Half Load BTU/HR AT650 120/6.0 120/5.4 GS650 220/3.3...
  • Page 6: Other Electrical Specifications

    OTHER ELECTRICAL SPECIFICATIONS Electrical Specifications Input Voltage (AC Mode Function) 120VAC ± 15 VAC; 225 VAC ± 35VAC Input Frequency Deviation for Synchronization ± 5% Inrush Current 1.5xRated Surge Protection 3 way, meets IEEE STD 587 RFI/EMI Filtering Both Common & Normal Modes Transfer 120VAC Units 220VAC Units...
  • Page 7: Unit Description

    All Models: Operating Temperature 0ºC to 40ºC (32ºF to 104ºF) Storage Temperature -15ºC to 40ºC (5ºF to 104ºF) Relative Humidity 95% maximum at 25ºC Non-Condensing Audible Noise 40 dB ANSI Scale A, at 3' UNIT DESCRIPTION AT SYCHRONIZED SINEWAVE MODELS 1.
  • Page 8: Gs Models

    5. AC Fault LED (Yellow/Red): Yellow when commercial input voltage is lost or too low or input frequency shifts drastically and unit switches to inverter mode. Red when commercial input voltage is too high and unit switches to inverter mode Both stay on until fault is cleared.
  • Page 9: Load Testing

    AC fuse blows (AT650, AT800 or AT2300) or input breaker trips (AT1200 or AT 1600), the MINUTEMAN UPS will switch to the normal inverter mode - "AC Normal" LED will extinguish, audible alarm will sound after a five (5) second delay and the LED(s) indicating the problem will illuminate.
  • Page 10: System Batteries

    frequency shift will cause the "AC Fault" light to turn yellow and a blown fuse or tripped circuit breaker will cause the fuse/breaker light to illuminate (RED). The audible alarm can be silenced in both the "Normal Inverter" and the "Low Battery Warning" modes by depressing the "Test/Alarm Silencer Switch"...
  • Page 11: Battery/System Checkout

    BATTERY /SYSTEM CHECKOUT To verify proper system function and battery condition, the user is encouraged to engage the test switch periodically. Normal indications as specified should be observed. If the system goes immediately to the low battery-warning mode the batteries should be replaced. UPS MONITORING CONFIGURATIONS All of these models provide an UPS monitoring capability which will allow direct interface with many different computer hardware/software configurations.
  • Page 12: Ups Db9 Pin Out

    UPS DB9 PIN OUT PIN 2 -- SIMULATED CLOSURE to pin 8 at Utility Failure PIN 3 -- SIMULATED CLOSURE to Pin 8 at Low Battery Warning PIN 4 -- UPS INVERTER SHUTDOWN: When a high (+5VDC minimum) is provided for 10 msec. PIN 5 -- SIGNAL GROUND PIN 8 -- COMMON RETURN FOR PINS 2 AND 3 SERVICE...
  • Page 13: Policy And Instructions For Return Of Product To Para Systems, Inc

    to identify a bad slow blow fuse visually. If the fuse is blown, replace it with a fuse of the same type and ratings. Reset breaker if tripped. Unit drops or reboots computer but continues to run in Inverter Mode. Unit is slightly overloaded.
  • Page 14: Warranty Statement

    PARA SYSTEMS, INC. Tel: (972) 446-7363 1455 LeMay, Carrollton, TX 75006 Fax: (972) 446-9011 LIMITED PRODUCT WARRANTY PARA SYSTEMS, INC. (PARA SYSTEMS) warrants that this product will be free from defective material and workmanship for a period of two years from the date of the original retail purchase by the end user provided that the warranty registrations card is completed and returned PARA SYSTEMS within ten (10) days of purchase.

This manual is also suitable for:

Gs1200At1600Gs1600At2300Gs2300At650 ... Show all

Table of Contents