Fire-Lite LCD-80FC Manual page 9

Remote fire indicator
Table of Contents

Advertisement

LCD-80FC Indicator
Figure 1-2: Wiring to Terminals
Terminal Block
P2
replacement
P/N 02109
Earth Ground Option
-24 VDC OUT
-24 VDC IN
+24 VDC OUT
+24 VDC IN
no connection
in from FACP
EIA-485 Terminals
Note: These connections must be power-limited and the +24 VDC nom-
inal power input must be filtered and nonresettable.
Refer to illustrations on the following page for LCD-80FC connections
to the MS-9200UDLSC and MS-9600LSC.
MS-9200UDLSC
(TB8)
Terminal 2 IN (+)
Terminal 4 IN (-)
Terminal 1 OUT (+)
Terminal 3 OUT (-)
Operating Voltage Range: 18 VDC to 28 VDC
Current Consumption @ 24 VDC nominal (filtered and nonresettable):
Normal/Standby (no activity): 64.3 mA
Trouble Condition: 64.3 mA
Alarm: 64.3 mA
AC Fail (not backlit): 25 mA
Document 53244 Rev. A 03/14/08 P/N 53244:A
1 2 3 4 5 6 7 8
7 6 5 4 3 2 1
-
EIA-485 IN
+
EIA-485 IN
MS-9600LSC
(TB7)
Terminal 5 IN (+)
Terminal 6 IN (-)
Terminal 7 OUT (+)
Terminal 8 OUT (-)
Components & Wiring
Side view
P1
Terminal Block
4 3 2 1
replacement
P/N 02108
Terminals Out to next
LCD-80FC
to FACP if this is last
or only device on the
line.
-
EIA-485 OUT
+
EIA-485 OUT
LCD-80FC
(P1 Connector)
Terminal 1 OUT (+)
Terminal 3 OUT (-)
Terminal 2 IN (+)
Terminal 4 IN (-)
or back
9