Fire-Lite LCD-80FC Manual page 20

Remote fire indicator
Table of Contents

Advertisement

Mounting
Mounting in Three Electrical Boxes Ganged Together
Remove the plug-in terminal blocks from the LCD-80FC circuit board.
Connect the EIA-485 and power wiring into the terminal block positions
illustrated in Figure 1-2 on page 9, Figure 4-1 on page 22 and Figure 4-
2 on page 23. Plug the terminal blocks back into the P2 and P1 connec-
tors on the back of the indicator. Set DIP switch SW1 for the desired
options. Refer to Figure 1-4 on page 13.
Carefully insert the LCD-80FC into the three electrical boxes ganged
together and attach it using the four mounting holes on the LCD-80FC
flange and the four screws provided for this purpose. Replace the trim
ring and secure with the two screws which were previously loosened.
Adjust the plastic trim ring to the surface of the wall before tightening
the screws. Do not overtighten.
Figure 3-4: Mounting in 3 Ganged Electrical Boxes
mounting holes (4)
The LCD-80FC can be surface mounted
in three gangable electrical switch boxes
connected together.
Important! When installing conduit in three
ganged electrical boxes, use knockouts on
the top or bottom. Installing conduit on the
sides or back of some boxes may interfere
with mounting of the LCD-80FC in the box.
flange
20
LCD-80FC
Document 53244 Rev. A 03/14/08 P/N 53244:A
Semi-flush Mount Backbox
LCD-80FC flange
Three ganged electrical boxes
Three electrical boxes ganged together
EIA-485 and
power wiring