ITI 60-770 - Security SuperBus 2000 4-Zone Output Module Installation Instructions Manual page 5

4-relay output module
Table of Contents

Advertisement

Connecting Devices to Outputs
Note
All terminals are Class 2 power limited.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
*
OUTPUT
DEVICE
(N.O. INPUT)
* DO NOT EXCEED RELAY CONTACT
VOLTAGE AND CURRENT RATINGS
**
DO NOT EXCEED PANEL +12V POWER CONSUMPTION
LIMITS (SEE PANEL INSTALLATION INSTRUCTIONS)
Figure 8. Module Typical Output Wiring
Connecting Devices to the Zone Input
Follow the maximum zone input wire length (run) guide-
lines in Table 5 based on the type of wire used.
Important!
For Advent UL-864 Listed Installations, all inputs must
be dedicated to either fire or burglary applications. Do
not mix fire and burglary on any module in any
partition for these installations.
Table 5. Zone Input Wire Runs
Gauge
18
22
*Wire run based on 10 ohms maximum wire and
device resistance including 2.0K ohm EOL resistor.
Figure 9 shows an example of how to connect normally
closed (N/C) or normally open (N/O) intrusion circuits to
the module zone input.
SuperBus® 2000 4-Relay Output Module
**
2K OHM
1/2 W
(TYPICAL)
LED
Max. Wire Run*
750 Feet
300 Feet
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
NORMALLY
< OR >
CLOSED
(N/C)
CONTACTS
IN SERIES
Figure 9. Module Zone Input Wiring
Installing a Cover Tamper Switch
If you are mounting the module in its own plastic or mount-
ing it inside a metal cabinet, you must add module tamper
detection for UL Listed systems.
To do this, install a UL listed ¼-inch press-fit reed switch
on the module back-plate and wire the switch to the module
zone input terminals or unused panel hardwire input termi-
nals. Once programmed, if someone opens the module
cover, the tamper switch opens and causes an alarm.
The tamper switch holder is located at the lower-right side
of the back-plate as shown in Figure 10. The plastic cover
holds the magnet.
MODULE
BACK-PLATE
REED
TO ANY ZONE
SWITCH
INPUT
2.0K OHM EOL
RESISTOR (49-467)
Figure 10. Installing the Reed Switch
Installing a Cover Tamper Switch
NORMALLY
OPEN
(N/O)
CONTACTS
IN PARALLEL
2.0K Ohm EOL RESISTOR 46-467
(INSTALL AT LAST DEVICE)
9710G04A.DSF
MODULE
COVER
MAGNET
MAGNET
CLIP
9712G12A.DSF
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Superbus 2000 60-770

Table of Contents