Installation
Wiring
Note
A) Class 2, Class 3, and power-limited fire alarm cir-
cuits must be installed using FPL, FPLR, FPLP, or
substitute cable permitted by the National Electrical
Code ANSI/NFPA 70. Wire that extends beyond the
cable jacket must be separated from all other conduc-
tors by a minimum of 1/4-inch or by a nonconductive
barrier.
OR
(B) Class 2, Class 3, and power-limited fire alarm cir-
cuit conductors must be installed as Class 1 or higher
circuits.
Wiring the Module to a Panel
Important!
On Advent panels, the BUS 1 and BUS 2 headers
must be used only for fire or burglary applications. Do
not mix fire and burglary bus devices on either header.
Auxiliary power supplies must be power limited.
1.
Turn off (or disconnect) the panel power and discon-
nect the panel backup battery(s).
2.
Wire the module to the panel as shown in Figure 7 and
Table 4.
Note
For specific wiring details, see the panel Installation
Instructions .
3.
Wire multiple modules in "daisy-chain" fashion (in
parallel) to the panel terminals or connector.
4
ID: XXXXXXXX
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
*
ALSO OUTPUT AND AUX. SUPPLY
**
ALSO OUTPUT AND AUX. SUPPLY GND (COMMON)
Figure 7. General Module Wiring
Table 4: Module SuperBus/Panel Wiring
Module
Advent*
Terminals
13 (+12VDC)
Red
14 (BUS A)
Green
15 (BUS B)
White
16 (GND)
Black
* Panel SuperBus device connector wiring harness.
(Connect to either panel connector.)
4.
Wire the module outputs as shown in Figures 7 and 8.
For specific wiring details, see the device Installation
Instructions.