ITI 60-770 - Security SuperBus 2000 4-Zone Output Module Installation Instructions Manual

4-relay output module

Advertisement

Quick Links

®
SuperBus
4-Relay Output Module
Document Number: 466-1608 Rev. B
November 2000

Product Summary

Each SuperBus 2000 4-Relay Output module adds four pro-
grammable relay outputs to a compatible panel.
Examples of module uses include:
Turning on a CCTV camera during a burglary alarm.
Turning on exit lights during a fire alarm.
Activating backup cellular phones or long-range radios
if primary communications are inoperable.
Each module comes complete with mounting hardware.
Power for the module is provided by the panel.
®
Advent
panels can be expanded to a total of 124 (24 pre-
programmed) output points.
®
UltraGard
and Concord
panels can be expanded to a total
of 32 output points.
For additional security, the plastic case accommodates a
magnetic reed switch to provide tamper protection. Simply
connect a UL listed reed switch to the module built-in zone
input or to one of the fire/security panel hardwire input
zones.
SuperBus 2000 vs. SuperBus
SuperBus 2000 panels have the ability to auto-address mod-
ule unit numbers. When the panel is initially powered up,
the panel automatically reads the unique SuperBus 2000
device ID number and assigns a unit number to the module.
This eliminates manually setting DIP switches and the
chance of identical unit number conflicts.
SuperBus 2000 Panels
Advent
Concord (software versions 2.0 and later)
SuperBus panels communicate with SuperBus 2000 mod-
ules but require the module unit number to first be set man-
ually with DIP switches.
SuperBus Panels
UltraGard
Concord (software versions 1.0–1.6)
SuperBus® 2000 4-Relay Output Module
2000

Installation Instructions

Module Components

Figure 1 shows the main module components and Table 1
describes them.
Figure 1. Module Circuit Board Components
Table 1: Module Component Descriptions
Component
Unit Number DIP
Used for manually setting module unit
Switches
number (SuperBus panels).
BUS LED (Red)
Flashes to indicate normal
communication with the panel.
POWER LED
Indicates module power status.
(Green)
Output Relays
Form C (dry contact) output relays rated
4A @ 24VDC, 4A @ 24VAC, 1A @
70VAC maximum.
SuperBus 2000
Identifies the unique device ID
Device ID Number
(SuperBus 2000).
Label
Software Version
Identifies the installed software version.
Label
Wiring Terminals
Used for power, bus, and output wiring
connections. All terminals are Class 2
power limited.
ITI Part No. 60-770
8557109A.DS4
UNIT NUMBER
DIP SWITCHES
BUS STATUS LED
(RED)
POWER LED
(GREEN)
OUTPUT RELAYS (4)
SOFTWARE
VERSION LABEL
SUPERBUS 2000
DEVICE ID
NUMBER LABEL
WIRING
TERMINALS
9710G01A.DSF
Function
1

Advertisement

Table of Contents
loading

Summary of Contents for ITI 60-770 - Security SuperBus 2000 4-Zone Output Module

  • Page 1: Installation Instructions

    ITI Part No. 60-770 ® SuperBus 2000 4-Relay Output Module 8557109A.DS4 Document Number: 466-1608 Rev. B November 2000 Installation Instructions Product Summary Module Components Each SuperBus 2000 4-Relay Output module adds four pro- Figure 1 shows the main module components and Table 1 grammable relay outputs to a compatible panel.
  • Page 2: Mounting The Module

    Installation Guidelines Installation Guidelines Installation For the maximum number of bus devices and The relay output module can be mounted: touchpads per panel see Table 2. On a wall. Table 2: Maximum Bus Devices Per Panel Inside an Advent cabinet. Inside a Concord cabinet.
  • Page 3 Installation Mounting the Module in a Concord Cabinet MOUNTING HOLES Remove AC panel power and disconnect the backup battery. Remove and discard the module cover (Figure 2). Insert a support standoff as shown in Figure 5 (sup- plied with panel) into the panel circuit board. SUPPORT STANDOFF PANEL MODULE...
  • Page 4 Installation Wiring Note A) Class 2, Class 3, and power-limited fire alarm cir- ID: XXXXXXXX cuits must be installed using FPL, FPLR, FPLP, or substitute cable permitted by the National Electrical Code ANSI/NFPA 70. Wire that extends beyond the cable jacket must be separated from all other conduc- tors by a minimum of 1/4-inch or by a nonconductive barrier.
  • Page 5 Installing a Cover Tamper Switch Connecting Devices to Outputs Note All terminals are Class 2 power limited. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 NORMALLY <...
  • Page 6 Setting the Module Unit Numbers To install the tamper reed switch: UNIT NUMBER 1 UNIT NUMBER 2 UNIT NUMBER 0 Slide the reed switch into the holder located on the module back-plate. 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 Insert the reed switch magnet into the nibs on the...
  • Page 7: Troubleshooting

    Programming and Testing Troubleshooting Connect the panel battery(s) and restore panel AC power. Alphanumeric touchpad displays should come on. Both the green and red LEDs turn on for one sec- ond, then the green POWER LED will remain on. Use the following table to determine possible solutions to module problems.
  • Page 8: Specifications

    Specifications Specifications Notices Compatibility: Advent, Concord, and UltraGard FCC Part 15 Information to the User Power Requirements: 12V nominal, 12 mA typical (idle), 180 Changes or modifications not expressly approved by Interactive Technologies, Inc. can void the user’s authority to operate the equipment. mA maximum (all relays energized) FCC Part 15 Class A Inputs:...

This manual is also suitable for:

Superbus 2000 60-770