Troubleshooting - Majestic fireplaces UVS33RN Operating Instructions Manual

Vent-free gas room heaters
Table of Contents

Advertisement

Honeywell
20002211

Troubleshooting

START
• Gas Supply On
YES
Pilot Lights with
Piezo Ignitor
YES
Pilot Stays Lit
YES
Pilot Lights Main
Burner
YES
System OK
FP396A
UVHB-standing pilot troubleshooting
7/2/98
CHECK
• Supply line hooked up
NO
• Shutoff valve open
• Lockout has engaged. Wait
60 seconds and try again
• For spark at electrode while
NO
depressing Piezo
1/8" gap to pilot hood needed
• All wiring connections
• Replace Piezo ignitor
• For air in lines
• Thermopile needs a minimum
325mV. Adjust pilot flame height
• All wiring connections
• Replace Thermopile
NO
• Thermocouple needs a minimum
of 14mV.
• Defective valve. turn to pilot,
meter should read greater than
100mV. If not, replace
• Valve is turned on
• Wall switch is not turned on.
Watch for grounded wires!
NO
• Thermopile needs a minimum
325mV.
• Plugged burner orifice
UVS33/36 Vent-Free Heaters