Facility Characteristics; Floor Loading - HP L1000 - 9000 - 0 MB RAM Manual

Site preparation guide - rp5400
Hide thumbs Also See for L1000 - 9000 - 0 MB RAM:
Table of Contents

Advertisement

Facility Characteristics

This section contains information about facility characteristics that must be considered for the installation or
operation of an hp server. Facility characteristics are:

Floor loading

Windows
Altitude effects
Floor Loading
The computer room floor must be able to support the total weight of the installed hp server as well as the
weight of the individual cabinets as they are moved into position.
Floor loading is usually not an issue in nonraised floor installations. The information presented in this section
is directed toward raised floor installations.
NOTE
An appropriate floor system consultant should verify any floor system under consideration for
an hp server installation.
Raised Floor Loading
Raised floor loading is a function of the manufacturer's load specification and the positioning of the
equipment relative to the raised floor grid. While Hewlett-Packard cannot assume responsibility for
determining the suitability of a particular raised floor system, it does provide information and illustrations
for the customer or local agencies to determine installation requirements.
The following guidelines are recommended:
Because many raised floor systems do not have grid stringers between floor stands, the lateral support for
the floor stands depends on adjacent panels being in place. To avoid compromising this type of floor
system while gaining under floor access, remove only one floor panel at a time.
Larger floor grids (bigger panels) are generally rated for lighter loads.
Do not position or install any equipment cabinets on the raised floor system until you have
CAUTION
carefully examined it to verify that it is adequate to support the appropriate installation.
Floor Loading Terms
Table 1-2
Floor Loading Term Definitions
Term
Dead load
Live load
Chapter 1
The weight of the raised panel floor system, including the
understructure. Expressed in lb/ft2 (kg/m2).
The load that the floor system can safely support. Expressed
in lb/ft2 (kg/m2).
Definition
General Site Preparation Guidelines
Facility Characteristics
13