Trial Operation - Haier AD18LS1ERA Service Manual

Multi upgrade series commercial air conditioner
Hide thumbs Also See for AD18LS1ERA:
Table of Contents

Advertisement

Pipe expansion dimensions as follows:
Pipe diameter
6.35 mm (1/4 " )
9.52 mm (3/8 " )
12.7 mm (1/2 " )
The connection of indoor unit pipes must use double spanners.
The installing torque shall be as given in the following table.
Installing torque
Connecting pipe
O.D.(mm)
11.8 (1.2kgf-m)
? 6.35
24.5 (2.5kgf-m)
? 9.52
49.0 (5.0 kgf-m)
? 12.70

4.Trial operation

The person who has completed this installation shall be requested to conduct a test operation for
check:
Is the temperature adjuster working normally?
Does the location for installation conform to requirements?
Winding up with Protective Plastic Tape.The connection pipes,drain pipe, and the connection
wires shall be wound up with PVC tape.
The connection pipes shall also be wound up with insulating material to preserve
the temperature. The airing direction shall be from bottom to top.
Wiring methods:
1 Wiring method of ring terminal
For connecting line which end is a ring,its wiring method as shown in the right figure: remove
wiring screw and pass it through the end ring of connecting line,then connect it to the terminal
block and tighten screw.
Correct
Size A (mm)
?
0.8 ~ 1.5
1.0 ~ 1.8
1.2 ~ 2.0
Increased installing
(N-m)
torque (N-m)
13.7 (1.4 kgf-m)
29.4 (3.0 kgf-m)
53.9 (5.5 kgf-m)
NOTE!
Incorrect
Slope Damage Bur Partial Overlong
A
Pipe expander
Double-spanner
operation
-70-