Haier AD18LS1ERA Service Manual page 92

Multi upgrade series commercial air conditioner
Hide thumbs Also See for AD18LS1ERA:
Table of Contents

Advertisement

6.4 In AUTO mode, when the indoor unit occurs abnormal operation, the indoor unit will keep OFF state,
and the buzzer will not sound until the outdoor mode and the requested mode of indoor unit are the same.
6.5 COOL (included AUTO COOL), DRY, FAN are not abnormal mode.
6.6 HEAT and FAN are not abnormal mode.
7. Control for discontinuous operation
After the unit starts up in cooling/heating mode, in 5 minutes, the compressor run/stop will not be
controlled by the room temp., but after changing the set temp., if compressor stop condition can be met,
the system will stop compressor immediately.
8. Anti-cold air control
In heating mode, after compressor startup, the system will control indoor fan motor according to indoor
coil temperature. Detailed operation is as below:
Tc2(℃)
30(32)
26(30)
22(26)
20(20)
Note:
1) The data in the parentheses is the control point when Tao>10℃;
2) Indoor unit will send "pre-heat" signal to wired controller in anti-cold air period.
9. Fan motor control in defrosting
9.1 On receiving outdoor defrosting signal, indoor unit will stop after blowing remaining heat at slow
speed for 20 seconds.
9.2 In defrosting period, indoor fan motor stops running.
9.3 Defrosting is over, and indoor motor will run as anti-cold air state.
10. Blowing remaining heat operation
When the unit shuts off in heating mode or the thermostat is OFF, indoor motor will stop running after
running at low speed for 30 seconds.
11. Swing motor control
Indoor unit will control the swing motor according to the swing signal from the wired controller.
Full OFF 54º
set speed
low speed
off
54°
-91-
Swing range
Standard
position
HEAT, COOL mode
in

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents