Item
Function
Capacity
Sensible heat ratio
Dehumidifying capacity
Power Supply
Type × Number
Speed(H-M-L)
Fan
Fan motor output power
Air-flow(H-M-L)
Type / Diameter
Heat exchanger
Total Area
Temp. scope
External (L×W×H)
Dimension
Package (L×W×H)
Drainage pipe (material , I.D./O.D.)
Control type
(Remote /wired)
Fresh air hole dimension
Electricity Heater
Noise level ---sound presure
Noise level ---sound power
Weight
(Net / Shipping)
Refrigerant
Type
Liquid
Pipe
Gas
Connecting Method
Norminal condition: indoor temperature (cooling): 27℃DB/19℃WB, indoor temperature (heating): 20℃
DB
Outdoor temperature(cooling): 35℃DB/24℃WB, outdoor temperature(heating): 7℃DB/6℃WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser
calibrated sound intensity meter. It is a sound pressure noise level.
Model
kW
10‐³×m³/h
r/min
kW
m³/h
mm
mm×mm×mm
mm×mm×mm
mm
mm
kW
(H-M-L)
dB(A)
(H-M-L)
dB(A)
kg / kg
mm
mm
-13-
AC12CS1ERA
cooling
heating
3.5(0.9--4.5)
3.9(1.0--4.8)
0.71
1.6
1PH,220-230V 50-60HZ
CENTRIFUGALX2
1100/1025/825
0.09
650/550/450
inner grooved pipe/φ7
0.20
2-7
990*655*199
1150*750*300
PVC 18/20
Remote,.YR-HD
NONE
NONE
41/37/33
52/48/44
26.3/32.3
R410A
φ6.35(1/4)
φ9.52(3/8)
flared
/