Haier AD18LS1ERA Service Manual page 84

Multi upgrade series commercial air conditioner
Hide thumbs Also See for AD18LS1ERA:
Table of Contents

Advertisement

3.8 Frequency control when there is CT over current protection
1.0 I
0.95I
0.93I
0.90I
0.88I
0.85I
3.9 High pressure protection
When the input signal of pressure switch is high level:1, that shows there is no protection.
When the input signal of pressure switch is low level: 0 for 1 minute, that shows high pressure protection
works. At this time, compressor stops, outdoor will send the alarm signal. The alarm can be resumable. If
in 60 minutes, the failure occurs 3 times, the failure can be confirmed and send failure code to indoor.
Meanwhile, by controling the max. condensate temp. Tc (cooling) or TmAVE (heating), please confirm as
follow:
In nominal cooling/dry/heating mode, high pressure can be controlled by limiting the max. frequency.
69
68℃
66℃
64℃
62℃
60℃
3.10 Low pressure protection
(1) When compressor is running, if output signal of low pressure switch is low level: 0 for 1 minute
continously, compressor will stop,outdoor alarms. The alarm can be resumable. If in 60 minutes, the
failure occurs 3 times, the failure can be confirmed and send failure code to indoor.
(2) When compressor no running, if output signal of low pressure switch is low level: 0 for 30 seconds
continously, alarm will occur.
Stop immediately, if abnormal stop 3 times in 1 hour, the
unit will stop and alarm.
Reduce FQY rapidly 2HZ/S
Reduce FQY rapidly 1HZ/S
Reduce FQY slowly 1HZ/10S
Remain FQY
Increase FQY slowly 1HZ/10S
Keep for 5 seconds, stop to alarm, after 3-minute standby, the
unit can restartup. In 60 minutes it occurs 3 times continously,
unit will stop to alarm and the failure can be resumed after being
electrified again.
Reduce FQY rapidly 2HZ/S
Reduce FQY rapidly 1HZ/S
Reduce FQY slowly 1HZ/10S
Remain FQY
Increase FQY slowly 1HZ/10S
-83-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents