Table 2-6 HP Integrity rx8640 and HP 9000 rp8440 AC Power Requirements (continued)
Requirements
Power factor correction
Ground leakage current (mA)
Table 2-7 HP Integrity rx8640 System Power Requirements
Power Required (50–60 Hz)
Maximum Theoretical Power
Marked Electrical Power
User Expected Maximum Power
Note 1: Maximum Theoretical Power: or "Maximum Configuration" (Input power at the ac input
expressed in Watts and Volt-Amps to take into account Power factor correction.)The calculated
sum of the maximum worst case power consumption for every subsystem in the server. This
number will never be exceeded by a functioning server for any combination of hardware and
software under any conditions.
Note 2: Marked Electrical Power: (Input power at the ac input expressed in Volt-Amps.)The
Marked Electrical Power is the rating given on the chassis label and represents the input power
required for facility ac power planning and wiring requirements. This number represents the
expected maximum power consumption for the server based on the power rating of the bulk
power supplies. This number can safely be used to size ac circuits and breakers for the system
under all conditions.
Note 3: Typical Maximum Power: or User Expected Maximum Power, (Input power at the ac
input expressed in Watts and Volt-Amps.)The measured maximum worst case power
consumption. This number represents the larges power consumption that HP engineers were
able to produce for the server with any combination of hardware under laboratory conditions
using aggressive software applications designed specifically to work the system at maximum
load. This number can safely be used to compute thermal loads and power consumption for the
system under all conditions.
Table 2-8 HP 9000 rp8440 System Power Requirements
Power Required (50–60 Hz)
Maximum Theoretical Power
Marked Electrical Power
User Expected Maximum Power
Note 1: Maximum Theoretical Power: or "Maximum Configuration" (Input power at the ac input
expressed in Watts and Volt-Amps to take into account Power factor correction.)
The calculated sum of the maximum worst case power consumption for every subsystem in the
server. This number will never be exceeded by a functioning server for any combination of
hardware and software under any conditions.
Note 2: Marked Electrical Power: (Input power at the ac input expressed in Volt-Amps.)
The Marked Electrical Power is the rating given on the chassis label and represents the input
power required for facility ac power planning and wiring requirements. This number represents
the expected maximum power consumption for the server based on the power rating of the bulk
power supplies. This number can safely be used to size ac circuits and breakers for the system
under all conditions.
36
System Specifications
Value
>0.98
>0.95
<3.0 (ma)
Watts
VA
5862
5982
– – –
5400
3883
3962
Watts
VA
5720
5837
– – –
5400
3789
3866
Comments
At all loads of 50%–100% of supply
rating.
At all loads 0f 25%–50% of supply rating
Per line cord
Comments
See Note 1
30A @ 180 VAC, See Note 2
See Note 3
Comments
See Note 1
30A @ 180 VAC, See Note 2
See Note 3