Installation - Bosch ISN-SM-50 Installation Manual

Seismic detector
Hide thumbs Also See for ISN-SM-50:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Indirect installation with mounting plate GMX−P0
Seismic detector ISN−SM−50
fig. 8 to 11

Installation

In the case of uneven or hardened steel plates, weld on
mounting plate GMX−P0.
1. Remove residual paint from the welding area (fig. 8).
Application
2. Weld mounting plate in four fixing points. Ensure cor-
The ISN−SM−50 is a seismic detector with new detec-
rect positioning (fig. 10).
tion and parameterization features.
ü The welding symbol must be visible on the front of
The detection is improved by the patented distur-
the mounting plate (fig. 9).
bance filter and new clock filter.
3. Weld along surfaces indicated. Tap off slag and re-
The detector may be used together with ultrasonic de-
move weld spatter from the plate surface (fig. 11).
tectors.
4. Mount detector.
The seismic detector ISN−SM−50 provides reliable pro-
Do not use silicon grease between sensor and
tection for
mounting plate!
− safes
− strongroom walls
Installation on concrete using mounting plate
− strongroom doors
GMX−P0 fig. 12
− automatic cash dispensers
Never install the detector directly on a bare or plastered
− vending machines
concrete surface, since bending forces may cause
damage to the seismic sensor. Plaster of less than
− ticket machines
10mm need not be removed.
against attack with explosives and break-in attempts
1. Drill center hole
with any of the known tools, such as diamond-head
drills, hydraulic pressure tools, oxygen lances and at-
deep using a sintered carbide bit (fig. 12).
tack using explosives.
2. Insert metal plug into drilled hole flush with the con-
crete surface. Use metal plugs only!
Coverage area fig. 1 + 2
3. Ensure that the mounting plate is correctly posi-
The coverage area is highly dependent on the material
tioned. Press the mounting plate onto surface, knock
of the object to be monitored:
in screw with plug and tighten well. The plate should
− Operating radius on steel: «r» = 6ft. 8" (2m)
no longer be capable of rotation.
− Operating radius on reinforced concrete: «r» = 13ft.
4. Mount detector.
(4m)
Do not use silicon grease between sensor and
The coverage area of the detector on strongroom
mounting plate!
walls may also extend to part of the ceiling, floor, or
over corners if an homogeneous connection exists. In
Recessed mounting with wall recess plate
such cases the operating radius is reduced to ¾ of the
GMX−W0 fig. 13 to 15
range setting (fig. 2).
1. Drill
Joints between two materials always damp the struc-
2. Fasten the wall recess set by inserting threaded bolt
ture-borne noise transmission. One detector on the
and tightening wing nut (fig. 13).
door and one on the body must always be installed.
3. Push the installation conduit through the polystyrene
This also applies to entrance doors of strongrooms.
block.
4. After removing mould, unscrew threaded bolt.
Surveillance of metal cases fig. 3
Scrape out polystyrene and cut off conduit flush (fig.
The coverage area is designated as the surface of a me-
14).
chanical obstacle which is monitored by a detector. The
5. Mount detector.
coverage area is highly dependent on the material of the
6. Mount cover plate (fig. 15).
object to be monitored. Practical experience has shown
that the operating radius for steel is 6ft. 8" (2m)
Cable feed in wall box and floor box fig. 16
Note: Joints between two materials always damp the
Insert cable with reserve loop into the box. Ensure ap-
structure-borne noise transmission, therefor not recom-
propriate cable length when drawing the cable in.
mended on standard multilayer safes.
Installation in floor box GMX−B0 fig. 17 to 19
To install the floor box GMX−B0, a recess with a base
Installation
area of at least 12" x 12" (300 x 300mm) and a depth of
Opening the detector fig. 4
3¼" (80mm) is required (fig. 17). Use a polystyrene
Unscrew the captive screws and lift off the metal cover
block to keep this recess open when pouring in the wet
carefully.
concrete.
− The seismic sensor is now exposed.
Two threaded bolts M6x4" (M6x100mm) screwed into
metal plugs provide the acoustic connection between
Fastening the detector fig. 4
the detector and the concrete floor.
Use only the two pre-assembled M4 cross-head screws
1. Level floor box using the nuts on the two threaded
provided in order to fix the detector.
bolts. Fix position finally by tightening the lock nuts
(fig. 18).
Direct mounting on steel fig. 5 to 7
2. Feed installation conduits through sealing sleeves.
The detector can be installed directly on steel plates
Fill recess with wet cement.
with a smooth surface. Ensure that any residual paint
3. Pull cable through and thoroughly seal the entry
between the steel surface and the seismic sensor is
openings for protection against moisture (fig. 19).
completely removed and the mounting surface is level
4. Mount the detector.
1
to within
/
" (0.1mm). If this is not possible, use
128
5. Fit cover plate. Cut out wood or carpet floor covering
mounting plate GMX−P0.
and stick to cover plate.
1. Remove residual paint from sensor installation site
(fig. 5).
2. Stick on drilling template and centerpunch drill holes
(fig. 6).
1
3. Drill only the two marked holes of
/
" (3.2mm) dia.
8
1
and tap M4 thread at least
/
" (6mm) deep (fig. 7).
4
Deburr threaded holes.
4. Mount detector.
Do not use silicon grease between sensor and object!
008738_b_−−_−− page 2
Papiergrösse = 360 x 270mm
Installation accessories
GMX−D7 Anti-drilling foil fig. 4
A special anti-drilling foil is available for fitting into the
detector cover as an additional protection against tam-
pering, if required. For installation refer to the separate
mounting sheet delivered with the GMX−D7.
Programming
After the detector housing has been opened, use the
switches to select the respective settings.
SW1, SW2
Application settings, SW1 and SW2
Select the sensitivity setting to suit the application, the
material and the object with the associated interference.
Important: During commissioning, be sure to check for
3
/
" (10mm) dia. at least 2" (50mm)
function-related noise (see "Commissioning" ).
8
Settings on the detector
Steel 6ft. 8" (2.0m)
Steel 4ft. 9" (1.5m)
Concrete 13ft. ( 4.0m)
User Mode, with SMS−W7 SensTool
3
/
" (9mm) dia. hole in wooden concrete mould.
8
Remote controlled sensitivity reduction fig. 21
An additional feature of this detector is a sensitivity re-
duction input at terminal 7 "Remote" which can be re-
motely activated if required.
Using a LOW signal (0V), the detector is reduced to
about 1/8 of the sensitivity setting for as long as there is
heavy functional noise by means of a touch-sensitive
switch on the opening device during operation of day-
night deposit.
ü Open control input is HIGH (internal pull-up resistor).
Test input fig. 21
The test input terminal 4 is used for the functional testing
of the seismic detector together with the GMX−S1.
With TEST ON the functional test is run once and a pos-
itive test result is output to the alarm relay.
ü Open control input is HIGH (internal pull-up resistor).
LED
During commissioning or when changing operating
mode the red LED flashes until the detector is ready for
operation.
Lights on alarm condition for approx. 2.5s.
Commissioning
If the GMX−S1 test transmitter is to be used, it must be
connected before power is switched on.
Procedure:
1. Switch on voltage − wait 1 minute − the detector is
ready for operation.
2. Functional check: Simulate an attack signal in the su-
pervised area, for example scratch lightly with a
screwdriver or test signal GMX−S1 − the detector
should trigger an alarm.
3. Interference checks: Connect an universal measur-
ing instrument (impedance ≥20kΩ) between terminal
1 (0V) and "TEST POINT" for integrator signal:
ON
− quiescent level
0V
. . . . . . . . . . . . . . . . . . . . .
OFF
− integration start
1.0V
. . . . . . . . . . . . . . . . . . . .
1 2
− alarm threshold (without load)
3.0V
. . . .
4. Carefully close the cover, tightening the housing
screw.
SensTool SMS−W7
The SensTool software allows operating parameters to
be set individually. In addition, current information such
as integrator signals can be viewed and stored.
The following additional settings are possible, depend-
ON
ing on the application, material and object, with corre-
OFF
sponding interferences:
1 2
ON
3ft. 4" (1.0m)
OFF
Steel
4ft. 9" (1.5m)
1 2
Detector sensitivity
y
6ft. 8" (2.0m)
ON
8ft. 2" (2.5m)
OFF
Concrete
Concrete
1 2
13ft. (4.0m)
ON
low
OFF
1 2
Shock sensitivity
y
mid
high
Recommended sensitivity settings
The following approximate values can be used as refer-
ence values for the setting of the seismic detector:
Application
Sensitivity
Ticket machine
Steel
with heavy functional related noises,
3ft. 4" (1.0m)
exposed location
Autom. cash dispenser, Day/night
Steel
deposit, Safe door
4ft. 9" (1.5m)
with heavy functional related noises
Steel
Armored safe, Strongroom door
with functional related noises
6ft. 8" (2.0m)
Strongroom, Modular vault
Concrete
with light interferences
8ft. 2" (2.5m)
Strongroom, Modular vault
Concrete
with minimum interferences
13ft. (4.0m)
Maintenance
Test detectors regularly (at least once a year) for opera-
tion and firm mounting.
Approvals
CE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UL
applied for
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Any national approval requirements relating to the ap-
plication of the product must be complied with.
Technical data
Detector
Supply voltage (nom. 12V
)
8.0...16.0V
DC
. . . . . . . . . . . . . . . .
Current consumption (at 12
, quiescent)
typ. 3mA
DC
. . . . . . . . .
− alarm condition
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm output, terminals 14+15:
Semiconductor relay
. . . . .
opens on alarm and/or low voltage
− contact load
. . . . . . . . . . . . . . . . . . .
30V
/100mA, ohmic load
DC
≤45Ω
− series resistance
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm holding time
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sabotage surveillance:
Tamper, terminals 10+11:
− microswitches for cover + body
opens on tamper
. . . . . . . . .
− contact load
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30V
/100mA
DC
<7V...8V ⇒ alarm
Supply voltage
. . . . . . . . . . . . . . . . . . . . . . . . . . .
tamper ⇒ alarm
Anti-drilling foil in cover
. . . . . . . . . . . . . . . . . . . .
Sensitivity reduction input, terminal 7:
LOW ≤1.5V / HIGH ≥3.5V
− for reduction
. . . . . . . . . . . . . . . . . . .
− reduction to
1/8 of the actual setting
. . . . . . . . . . . . . . . . . . . . . .
Sensitivity, adjustable in
. . . . . . . . . . . . . . . . . . . . .
3 fixed levels +
SW programmable with SensTool
Functional test input, terminal 4:
LOW ≤1.5V / HIGH ≥3.5V
− for test
. . . . . . . . . . . . . . . . . . . . . . . .
− with GMX−S1, test duration
. . . . . . . . . . . . . . . . . . . . . . . . . .
Measuring output, TEST POINT analogue integration signal
.
− quiescent level
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
− integration start
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
− alarm treshold (without load)
. . . . . . . . . . . . . . . . . . . . . . . .
Operating radius on steel
. . . . . . . . . . . . . . . . .
r = 6ft. 8" (2.0m)
Coverage area on steel
43sq.ft. (13m
. . . . . . . . . . . . . . . . . . . . .
Ambient conditions:
− operating temperature −40°F to +158°F (−40°C to +70°C)
− storage temperature
−58°F to +158°F (−50°C to +70°C)
. .
− humidity, DIN class F
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
<95%
− housing protection category (EN60529, EN50102)
IP435
. .
− VdS environmental class
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
− insensitive to RD interferences
0.01...2GHz (IEC 801-3)
30V/m
. . . . . . . . . . . . . . . . . . . . . . . . . .
Accessories
GMX−W0 Wall recess set with cover
− housing protection category IEC
. . . . . . . . . . . . . . . . . . . .
− max. carrying capacity of cover
. . . . . . . . . . . . . . . . . . . . .
GMX−B0 Floor box
Shock
− housing protection category IEC
. . . . . . . . . . . . . . . . . . . .
− max. carrying capacity of cover plate
. . . . . . . . . . . . .
1000kg
low
GMXW−G0 Watertight housing
− housing protection category IEC
. . . . . . . . . . . . . . . . . . . .
− max. carrying capacity of cover
. . . . . . . . . . . . . . . . . .
1000kg
mid
Details for ordering
mid
Elements supplied with detector
high
1 Seismic detector
1 Mounting instructions
high
1 Mounting template
3 Cable straps
Seismic detector
ISN−SM−50
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting plate
ISN−GMX−P0
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wall recess set w/cover
ISN−GMX−W0
. . . . . . . . . . . . . . . . . . . . .
Floor box
ISN−GMX−B0
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Watertight housing
ISN−GMXW−G0
. . . . . . . . . . . . . . . . . . . . . . . .
Swivel plate
ISN−GMX−P3S
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
conforms
Test transmitter
ISN−GMX−S1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SensTool, interface and software
ISN−SMS−W7
. . . . . . . . . . . .
Anti-drilling foil (10 pcs)
. . . . . . . . . . . . . . . . . .
ISN−GMX−D7
Fixing plate
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
ISN−GMA−S6
Spacer, 2mm
. . . . . . . . . . . . . . . . . . . . . . . . .
ISN−GMX−P3S2
Spacer, 4mm
. . . . . . . . . . . . . . . . . . . . . . . . .
ISN−GMX−P3S4
Swivel plate
ISN−GMX−PZ
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DC
5mA
2.5s
≤3s
0V
1,0V
3,0V
2
)
III
IP51
25kg
IP51
IP65