Tables; Table 1: Control Data - Field Controls 4291UV-AIR Test Instructions

Duct mounted uv-aire air purifier efficiency of bacterial disinfection
Table of Contents

Advertisement

Table 1: Control Data (testing with lamp off)
Sample
Air Sampling
Number
Duration (min)
1
1
2
1
3
1
4
0.5
5
0.5
Total min. = 4
1
2
2
2
3
2
4
1
5
1
Total min. = 8
Table 2: UV-18 Test data and results (testing with lamp on)
Air
Airflow
Sample
Sampling
Velocity
Number
Duration
(min)
1
1
2
1
3
3
4
6
Total min = 11
1
1
2
1
3
3
4
6
Total min = 11
Airflow
Serratia marcescens
Velocity
Positive hole count
fpm
500
181
500
193
500
208
500
117
500
118
Total Corrected
Particle counts
1000
168
1000
167
1000
169
1000
1000
Total Corrected
Particle counts
Serratia
marcescens
Positive hole
(fpm)
count
1000
30
1000
32
1000
88
1000
145
Total
Corrected
Particle Counts
500
13
500
19
500
57
500
92
Total
Corrected
Particle Counts
Corrected Particle
Counts
241
263
294
138
140
= 1076
218
216
220
91
103
92
103
= 860
Corrected
CFU/FT
Particle
of air
Counts
(count/min)
31
33
99
180
= 343
31.18
Control:
107.50
13
19
61
105
= 198
18.00
Control:
269.00
3
CFU/FT
of air
(count/min)
269.00
107.50
3
%Survival
Log
CFU/Control
Reduction
29.01
0.54
6.69
1.17
%
Effective
70.99
93.31
Page 6