TJERNLUND VH1-3,4 VENT HOODS 8504027 REV 3 1098 Owner's Instructions

Advertisement

OWNERS INSTRUCTIONS
THESE INSTRUCTIONS
MUST REMAIN
WITH EQUIPMENT
DO NOT DESTROY
1.
Terminate the vent system so that proper minimum clearances are maintained as cited in the latest edition of the
National Fuel Gas Code (NFPA # 54) and the latest edition of NFPA #211, or as follows:
• Not be less than 7 feet above grade when located adjacent to public walk ways
• At least 3 feet above any forced air inlet located within 10 feet
• At least 4 feet below, 4 feet horizontally from or 1 foot above any door, window or gravity air inlet into any building
• At least 12 inches above grade.
THE MANUFACTURER ALSO RECOMMENDS:
• The vent terminal shall also not be installed closer than 3 feet from the inside corner of an L-shaped structure
• Not less than 2 feet from an adjacent building
• Flue gases are not directed so as to jeopardize people, overheat combustible structures or enter buildings
2.
Check vent pipe system for leakage. All vent pipe joints on "positive" side of power venter must be sealed.
3.
A vent system incorporating a Tjernlund VH1 Series vent hood should not exceed 550
4.
Termination of a sidewall vent system with a device other than the Tjernlund VH1 vent hood could affect system
performance and result in a possible safety hazard.
5.
Plan the vent system layout to avoid the possibility of accidental contact with concealed wiring or plumbing inside walls.
6.
Installation must be done by one experienced and familiar with venting of combustion gases.
P/N 8504027
TJERNLUND PRODUCTS, INC.
1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com
MODELS VH1-3" AND VH1-4" SERIES VENT HOODS
©1998, Tjernlund Products, Inc.
o
F. gross.
REV. 3 10/98

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VH1-3,4 VENT HOODS 8504027 REV 3 1098 and is the answer not in the manual?

Questions and answers

Summary of Contents for TJERNLUND VH1-3,4 VENT HOODS 8504027 REV 3 1098

  • Page 1 A vent system incorporating a Tjernlund VH1 Series vent hood should not exceed 550 F. gross. Termination of a sidewall vent system with a device other than the Tjernlund VH1 vent hood could affect system performance and result in a possible safety hazard.
  • Page 2 TJERNLUND LIMITED ONE YEAR WARRANTY Tjernlund Products, Inc. warrants to the original purchaser of this product that the product will be free from defects due to faulty material or workmanship for a period of (1) year from the date of original purchase or delivery to the original purchaser, whichever is earlier. Remedies under this warranty are limited to repairing or replacing, at our option, any product which shall, within the above stated warranty period, be returned to Tjernlund Products, Inc.
  • Page 3 ENSURE THAT PROPOSED VENT TERMINATION CLEARANCES ARE MET BEFORE ATTEMPTING TO CUT HOLE THROUGH EXTERIOR WALL.
  • Page 4 VH1-3 & VH1-4 VENT HOOD INSTALLATION TEMPLATE 1. Attach the Vent Hood Mounting Template to the interior of the wall the vent hood will be penetrating. 2. Ensure that proposed vent termination clearances are met before attempting to cut opening through exterior wall. 3.

Table of Contents