Novelan LAD 7 Operating Manual

Novelan LAD 7 Operating Manual

Air/water heat pumps
Table of Contents

Advertisement

Quick Links

Operating Manual
Air/Water Heat Pumps
Dual / Outdoor Installation
LAD 5 • LAD 7 • LAD 9
LAD 5RX • LAD 7RX
UK
83053503iUK – Translation into English of the original German operating manual – Subject to change without notice.
w w w.novelan.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LAD 7 and is the answer not in the manual?

Questions and answers

Summary of Contents for Novelan LAD 7

  • Page 1 Operating Manual Air/Water Heat Pumps Dual / Outdoor Installation LAD 5 • LAD 7 • LAD 9 LAD 5RX • LAD 7RX 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. w w w.novelan.com...
  • Page 2: Please Read First

    Indicates suggestions that help to save energy, raw materials and costs. Reference to other sections of the operating manual. Reference other documents manufacturer. 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 3: Table Of Contents

    CONDENSATE PIPE ..............43 PRESSURE RELIEF ................. 14 CIRCUIT DIAGRAMS OVERFLOW VALVE ................ 14 LAD 5(RX) • LAD 7(RX) • LAD 9 ..........44 BUFFER TANK................. 14 CIRCULATING PUMPS ..............14 DOMESTIC WATER HEATING ............. 14 DOMESTIC HOT WATER TANK ........... 14 RINSING, FILLING AND BLEEDING THE SYSTEM ....
  • Page 4: Intended Use

    – Notify the manufacturer’s authorised written consent of the manufacturer. service centre. – Keep ignition sources away. 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 5: Customer Service

    For a current list and additional partners of the ATTENTION manufacturer, please visit www.novelan.com. Install the heat pump only outdoors and ope- rate only with outside air as the heat source. Do not restrict or block the air-conducting sides.
  • Page 6: Operating Principle Of Heat Pumps

    Operating manual for the heating and heat In order to ensure problem-free operation, the ice must pump regulator. be removed at regular intervals. Hydraulic module (Dual) operating manual. 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 7: Cleaning And Flushing Of Unit Components

    It is best to arrange a maintenance agreement with a heating installation company. The company will conduct the required maintenance at regular intervals. LAD 5(RX), LAD 7(RX) AND LAD WARNING! Do not use any objects, other than those allowed by the manufacturer, to accelerate the thawing process.
  • Page 8: Installation And Assembly

    NOTE. Observe the sound levels of the respective model. Overview “Technical data / scope of delivery”, “Sound” section and “Sound level” overview. 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 9: Sound

    The following sound pressure levels result, depending on the distance and installation variant with directivity factor Q. (see sketches page 10): Distance from the heat pump in m LAD 5 Directivity factor Sound pressure level at max. heating output in dB(A)
  • Page 10 Example: If the level difference between two unequal sound sources is 5 dB, the level increase is an additio- nal 1.2 dB. 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 11: Installation With Wall Bracket

    The two other cables must also be laid on site is sufficient to lay the condensate pipe vertically at least using reserve conduits. 90 cm into the ground. 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 12: Connection To The Heating Circuit

    Connect the unit to the fixed piping of the heating circuit via vibration decouplers (vibration installation - stainless steel corrugated pipes, 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 13: Electrical Connections

    Note the level of the tripping current. Overview “Technical data / scope of delivery”, “Electrics” section. See “Operating instructions hydraulic module” or “Compact Station Dual”. 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 14: Pressure Relief

    IN THE HYDRAULIC MODULE. See “Operating instructions hydraulic module” “Hydraulic connection” instructions. or “Compact Station Dual”. 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 15: Rinsing, Filling And Bleeding The System

    A system log should be kept, in which the relevant planning data is entered (VDI 2035). 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 16: Insulating The Hydraulic Connections

    Fill and bleed the heating circuit… In addition, open the bleeding valve on the condenser of the heat pump. Bleed condenser… 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 17: Commissioning

    In other countries: Send completion report for heat pump systems and general checklist to the manufacturer’s local partner… 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 18: Withdrawal From Service

    Recovered refrigerant cannot be used in other systems until it has been cleaned and examined. 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 19 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 20: Technical Data / Scope Of Delivery

    *) depending on component tolerances and flow **) comply with local regulations n.n. = not detectable w.w. = optional ¹) hot water return flow ²) hot water forward flowf 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 21 LAD 5 LAD 7 LAD 9 — ı • ı — — ı • ı — — ı • ı — — ı • — ı • — ı • • • • — — — 7,1 ı 4,8 8,5 ı 4,3 10,1 ı...
  • Page 22 *) depending on component tolerances and flow **) comply with local regulations n.n. = not detectable w.w. = optional ¹) hot water return flow ²) hot water forward flowf 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 23: Lad 5Rx Lad 7Rx

    • • • • • • — ı — ı — — ı — ı — — — — — 813545a 813546a 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 24: Performance Curves

    LAD 5 Heating mode Performance curves Qh (kW) Temp„ (°C) Pe (kW) 35°C 50°C 65°C Temp„ (°C) Temp„ (°C) ∆p (bar) ”p∆ “” (m³/h) 823165a Legende: DE823129L/170408 Legend: UK823129L/170408 “” Volumenstrom Heizwasser “” Volume flow, heating water Temp„ Temperatur Wärmequelle Temp„...
  • Page 25: Lad 7 Heating Mode

    LWD 70A Seite: 1/1 - / PEP006-2011 / Mödder / 13.05.2011 Zeichnungsnummer: 823166a a/-/Mödder / 24.10.2011 Datei: 823166 Leistungs- Druckverlustkurven LWD 70A.xls 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 26: Lad 9 Heating Mode

    Seite: 1/1 - / PEP006-2011 / Mödder / 13.05.2011 Zeichnungsnummer: 823165a a/ - /Mödder / 24.10.2011 Datei: 823165a Leistungs- Druckverlustkurven LWD 50A.xls 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 27: Lad 5Rx Heating Mode

    Leistungs-Druckverlustkurven Bezeichnung: Änd./Ä.M./Ersteller/Datum LWD 50A/RX Seite: 1/2 - / PEP003-2012 / Mödder / 01.08.2012 Zeichnungsnummer: 823169 Datei: 823169 Leistungs- Druckverlustkurven LWD 50ARX.xls 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 28: Lad 5Rx Cooling Mode

    - / PEP003-2012 / Mödder / 01.08.2012 Energy efficiency ratio / cooling capacity rate Zeichnungsnummer: 823169 Datei: 823169 Leistungs- Druckverlustkurven LWD 50ARX.xls ∆p” Pressure loss heat pump Compressor(s) 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 29: Lad 7Rx Heating Mode

    Leistungs-Druckverlustkurven Bezeichnung: Änd./Ä.M./Ersteller/Datum LWD 70A/RX Seite: 1/2 - / PEP003-2012 / Mödder / 01.08.2012 Zeichnungsnummer: 823170 Datei: 823170 Leistungs- Druckverlustkurven LWD 70ARX.xls 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 30: Lad 7Rx Cooling Mode

    Pressure loss heat pump Änd./Ä.M./Ersteller/Datum LWD 70ARX Seite: 2/2 - / PEP003-2012 / Mödder / 01.08.2012 Compressor(s) Zeichnungsnummer: 823170 Datei: 823170 Leistungs- Druckverlustkurven LWD 70ARX.xls 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 31: Dimensional Drawings

    Dimensional drawings LAD 5(RX) • LAD 7(RX) • LAD 9 DE819392 All dimensions in mm. Front view Side view Section (floor slab) Heating water flow G1" DIN ISO 228 flat gasket. Heating water return flow G1" DIN ISO 228 flat gasket.
  • Page 32: Installation Protection Areas

    LAD 5 (RX) • LAD 7(RX) • LAD 9 Installation protection areas 2,3m 0,5m 0,5m 3,3m Abbildung: Sicherheitsabstände zur Wärmepumpe Legende: DE819401 Technische Änderungen vorbehalten Figure: Safe distances from heat pump Legend: DE819401 Wärmepumpe Schutzbereich Heat pump bis zum Boden Protection area Türen, Fenster, Lichtschächte, usw.
  • Page 33: Wall Bracket Installation Plan

    Wall bracket installation plan LAD 5(RX) • LAD 7(RX) • LAD 9 WALL FEEDTHROUGH 1320 FS >800 FS >800 Legende: 819393-1c Technische Änderungen vorbehalten. Alle Maße in mm. Legend: 819393-1c We reserve the right to make changes without notice. Variante 1 All dimensions in mm.
  • Page 34: Floor Bracket Installation Plan

    LAD 5(RX) • LAD 7(RX) • LAD 9 Floor bracket installation plan HYDRAULIC CONNECTION PIPE 1320 FS >800 FS >800 Legende: 819393-2c Technische Änderungen vorbehalten. Legend: 819393-2c Alle Maße in mm. We reserve the right to make changes without notice.
  • Page 35: Floor Bracket Installation Plan

    Floor bracket installation plan LAD 5 (RX) • LAD 7 (RX) • LAD 9 WALL FEEDTHROUGH 1320 FS >800 FS >800 Legende: 819393-2c Technische Änderungen vorbehalten. Legend: 819393-3c Alle Maße in mm. We reserve the right to make changes without notice.
  • Page 36: Floor Bracket Installation Plan

    LAD 5 (RX) • LAD 7 (RX) • LAD 9 Floor bracket installation plan HYDRAULIC CONNECTION PIPE 1320 FS >800 FS >800 Legende: 819393-4c Technische Änderungen vorbehalten. Alle Maße in mm. Legend: 819393-4c We reserve the right to make changes without notice.
  • Page 37: Drilling Pattern For Wall Bracket

    Drilling pattern for wall bracket LAD 5(RX) • LAD 7(RX) • LAD 9 WALL FEEDTHROUGH Ø12 Legende: 819393-5c Technische Änderungen vorbehalten. Alle Maße in mm. BB1 Bohrbild für Wandkonsole (Zubehör) an Befestigungswand zu V1 Legend: 819393-5c Vorderansicht We reserve the right to make changes without notice.
  • Page 38: Drilling Pattern For Wall Bracket

    LAD 5(RX) • LAD 7(RX) • LAD 9 Drilling pattern for wall bracket HYDRAULIC CONNECTION PIPE Ø12 Legende: 819393-6c Technische Änderungen vorbehalten. Alle Maße in mm. Legend: 819393-6c BB2 Bohrbild für Wandkonsole (Zubehör) an Befestigungswand zu V2 We reserve the right to make changes without notice.
  • Page 39: View Of Foundation

    View of foundation LAD 5(RX) • LAD 7(RX) • LAD 9 WALL FEEDTHROUGH 1320 1190 >1300 1320 Legend: 819393-7c Legende: 819393-7c We reserve the right to make changes without notice. Technische Änderungen vorbehalten. All dimensions in mm. Alle Maße in mm.
  • Page 40: View Of Foundation

    LAD 5(RX) • LAD 7(RX) • LAD 9 View of foundation HYDRAULIC CONNECTION PIPE 1320 >1300 1190 X (1 : 5) Ø12 Legende: 819393-8c Technische Änderungen vorbehalten. Legend: 819393-8c Alle Maße in mm. We reserve the right to make changes without notice.
  • Page 41: Minimum Clearances

    Minimum clearances LAD 5(RX) • LAD 7(RX) • LAD 9 >3000 Legende: 819393-10c Technische Änderungen vorbehalten. Alle Maße in mm. FW2 Funktionsnotwendige Mindestabstände Draufsicht Fertigaußenfassade Legend: 819393-10c Luftrichtung We reserve the right to make changes without notice. All dimensions in mm.
  • Page 42: Outside Connection Of Condensate Pipe

    LAD 5(RX) • LAD 7(RX) • LAD 9 Outside connection of condensate pipe Legende: 819400-1 Technische Änderungen vorbehalten. Legend: 819400-1 Installation instructions for connecting the condensate pipe outside the building Aufstellungshinweise für Anschluß der Kondensatleitung außerhalb des Gravel layer for absorbing up to 50l condensation water per day Gebäudes.
  • Page 43: Inside Connection Of

    Inside connection of LAD 5(RX) • LAD 7(RX) • LAD 9 condensate pipe Legende: 819400-2 Technische Änerungen vorbehalten. Aufstellungshinweise für Anschluß der Kondensatleitung innerhalb des Gebäudes. Wichtig: Beim Anschluss der Kondensatleitung innerhalb eines Gebäudes muss ein Syphon eingebaut werden, der mit dem Abflussrohr gasdicht abschließt (siehe Abbildung 2a).
  • Page 44: Circuit Diagrams

    LAD 5(RX) • LAD 7(RX) • LAD 9 Circuit diagram 1/2 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 45 Circuit diagram 2/2 LAD 5(RX) • LAD 7(RX) • LAD 9 DI14 OUT1 OUT3 OUT4 OUT5 Green Yellow white Brown AIN1 AIN2 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 46 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...
  • Page 47 83053503iUK – Translation into English of the original German operating manual – Subject to change without notice. www.novelan.com...