Summary of Contents for Toshiba RAV-HM1601UTP Series
Page 1
FILE NO. SVM-22021-1 SERVICE MANUAL AIR-CONDITIONER (SPLIT TYPE) INDOOR UNIT <4-way cassette type> RAV-HM561UTP Series RAV-HM801UTP Series RAV-HM901UTP Series RAV-HM1101UTP Series RAV-HM1401UTP Series RAV-HM1601UTP Series Revised on Aug, 2022...
Original instruction Adoption of New Refrigerant This Air Conditioner is a new type which adopts a new refrigerant HFC (R32) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer. CONTENTS SAFETY CAUTION ........1. SPECIFICATIONS ........
The qualified service person is a person who installs, repairs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation...
Page 4
Definition of Protective Gear When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing. In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below.
Page 5
Warning Indications on the Air Conditioner Unit [Confirmation of warning label on the main unit] Confirm that labels are indicated on the specified positions If removing the label during parts replace, stick it as the original. WARNING WARNING ELECTRICAL SHOCK HAZARD ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies Disconnect all remote electric...
Page 6
PRECAUTIONS FOR SAFETY The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual. DANGER Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breaker for both the indoor and outdoor units to the OFF position. Otherwise, electric shocks may result.
Page 7
WARNING Before starting to repair the air conditioner, read carefully through the Service Manual, and repair the air conditioner by following its instructions. Only qualified service person (*1) is allowed to repair the air conditioner. Repair of the air conditioner by unqualified person may give rise to a fire, electric shocks, injury, water leaks and / or other problems.
Page 8
Do not modify the products. Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury. Prohibition of modification. When any of the electrical parts are to be replaced, ensure that the replacement parts satisfy the specifications given in the Service Manual (or use the parts contained on the parts list in the Service Manual).
Page 9
After repair work, surely assemble the disassembled parts, and connect and lead the removed wires as before. Perform the work so that the cabinet or panel does not catch the inner wires. If incorrect assembly or incorrect wire connection was done, a disaster such as a leak or fire is caused Assembly / at user’s side.
Page 10
When the service panel of the outdoor unit is to be opened in order for the compressor or the area around this part to be repaired immediately after the air conditioner has been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the service panel. If you fail to heed this warning, you will run the risk of burning yourself because the compressor pipes and other parts will be very hot to the touch.
Page 11
Declaration of Conformity Manufacturer: Toshiba Carrier (Thailand) Co., Ltd. 144/9 Moo 5, Bangkadi Industrial Park, Tivanon road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand TCF holder: TOSHIBA CARRIER EUROPE S.A.S Route de Thil 01120 Montluel FRANCE Hereby declares that the machinery described below:...
Page 12
Declaration of Conformity Manufacturer: Toshiba Carrier (Thailand) Co., Ltd. 144/9 Moo 5, Bangkadi Industrial Park, Tivanon road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand TCF holder: TOSHIBA CARRIER UK LTD. Porsham Close Belliver Industrial Estate Roborough Plymouth Devon PL6 7DB United Kingdom...
Page 16
• Refrigerant (R32) This air conditioner adopts a refrigerant HFC (R32) which does not deplete the ozone layer. 1. Safety Caution Concerned to Refrigerant R32 The pressure of R32 is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed.
Page 17
4. Tools 1. Required Tools for R32 Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types. 1) Tools exclusive for R32 (Those which cannot be used for conventional refrigerant (R22)) 2) Tools exclusive for R32 but can be also used for conventional refrigerant (R22) 3) Tools commonly used for R32 and for conventional refrigerant (R22) The table below shows the tools exclusive for R32 and their interchangeability.
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS) Indoor Unit RAV-HM561UTP * Ceiling Panel RBC-U32PGP-E 1000 or more 860 to 910 Ceiling open dimension An obstacle 1000 or more The space that is necessary for equipping and service Take-in port of wiring Bottom face of ceiling Indoor unit Bottom face of ceiling Refrigerant pipe connecting port...
Page 19
Indoor Unit 1000 RAV-HM561UTP * or more Ceiling Panel RBC-U33P-E 860 to 910 Ceilng open dimension An obstacle 1000 or more The space that is necessary for equipping and service Take-in port of wiring Bottom face of ceiling Bottom face of ceiling Indoor unit Refrigerant pipe connecting port Drain pipe...
Page 20
Indoor Unit RAV-HM801UTP * Ceiling Panel RBC-U32PGP-E 1000 or more 860 to 910 Ceiling open dimension An obstacle 1000 or more The space that is necessary for equipping and service n i l Indoor unit Bottom face of ceiling Drain upstanding size Refrigerant pipe connecting port Ø9.5 (Liquid side) Drain pipe...
Page 21
1000 Indoor Unit or more RAV-HM801UTP * Ceiling Panel RBC-U33P-E 860 to 910 Ceilng open dimension An obstacle 1000 or more The space that is necessary for equipping and service Take-in port of wiring Bottom face of ceiling Bottom face of ceiling Indoor unit Refrigerant pipe connecting port Drain pipe...
Page 22
Indoor Unit RAV-HM901UTP*, RAV-HM1101UTP * , RAV-HM1401UTP * , RAV-HM1601UTP* Ceiling Panel RBC-U32PGP-E 1000 or more 860 to 910 Ceiling open dimension An obstacle 1000 or more The space that is necessary for equipping and service Take-in port of wiring Bottom face of ceiling Indoor unit Bottom face of ceiling...
Page 23
Indoor Unit RAV-HM901UTP*, RAV-HM1101UTP * , RAV-HM1401UTP * , RAV-HM1601UTP* 1000 Ceiling Panel or more RBC-U33P-E 860 to 910 Ceilng open dimension An obstacle 1000 or more The space that is necessary for equipping and service Take-in port of wiring Bottom face of ceiling Refrigerant pipe connecting port Drain pipe...
3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM Indoor Unit • Single type (Combination of 1 indoor unit and 1 outdoor unit) (Indoor unit) Distributor (Strainer incorporated) TCJ sensor Strainer Heat exchanger TC sensor Heating Cooling Liquid side Gas side (Outer dia : ØB) (Outer dia : ØA) Capillary tube specifications To outdoor unit...
Page 25
Triple type (3 indoor units and 1 outdoor unit) Heating mode Cooling mode (Indoor unit A) (Indoor unit B) (Indoor unit C) TCJ sensor TCJ sensor TCJ sensor Distributor Distributor Distributor Strainer Strainer Strainer (with strainer) (with strainer) (with strainer) Heat Heat Heat...
Page 26
Double-twin type (4 indoor units and 1 outdoor unit) Heating mode Cooling mode (Indoor unit A) (Indoor unit B) TCJ sensor TCJ sensor Distributor Distributor (with strainer) (with strainer) Strainer Strainer Heat exchanger Heat exchanger TC sensor TC sensor Liquid-side Gas-side Liquid-side...
5. SPECIFICATIONS OF ELECTRICAL PARTS Indoor Unit RAV- HM561UTP , RAV-HM801UTP Parts name Type Specifications ICF-340D60-1 Fan motor (for indoor) Output (Rated) 60 W Thermo. sensor (TA-sensor) 328 mm 10 kΩ at 25°C Heat exchanger sensor (TCJ-sensor) Ø6 mm, 1000 mm 10 kΩ...
6-2. Control Specifications Item Outline of specifications Remarks When power 1) Distinction of outdoor unit supply is reset When the power supply is reset, the outdoors are distin- guished and the control is selected according to the distinguished result. 2) Setting of indoor fan speed and existence of air direction adjustment Based on EEPROM data, select setting of the indoor fan Air speed (rpm)/...
Page 32
Item Outline of specifications Remarks Room temp. 2) Using the CODE No. 06, the setup temperature in heating Shift of suction control operation can be corrected. temperature in heating (Continued) operation Setup data Setup temp. correction +0°C +2°C +4°C +6°C Setting at shipment Setup data Automatic...
Page 33
Item Outline of specifications Remarks Air speed selection 1) Operation with (HH), (H), (L) or [AUTO] mode is carried HH > H+ > H > L+ > out by the command from the remote controller. L > UL 2) When the air speed mode [AUTO] is selected, the air speed varies by the difference between Ta and Ts.
Page 34
Item Outline of specifications Remarks Air speed Standard Type 1 Type 3 Type 6 CODE No. selection Selection of high [5d] (Continued): ceiling type SW501 (1)/(2) OFF/OFF ON/OFF OFF/ON ON/ON CODE No.: COOL HEAT COOL HEAT COOL HEAT COOL HEAT [5d] or selection of high ceiling on P .C.
Page 35
Item Outline of specifications Remarks Cool air discharge 1) In heating operation, the indoor fan is controlled In D and E zones, the preventive control based on the detected temperature of Tc sensor or priority is given to air Tcj sensor. As shown below, the upper limit of the volume selection setup revolution frequency is restricted.
Page 36
Item Outline of specifications Remarks High-temp. 1) The heating operation is performed as follows based on the release control detected temperature of Tc sensor or Tcj sensor. • When [M] zone is detected, the commanded frequency is However this control is decreased from the real operation frequency.
Page 37
Item Outline of specifications Remarks Louver control 1) Louver position setup The louver position at horizontal • When the louver position is changed, the position moves discharge position necessarily to downward discharge position once to return to at under RM80 the set position.
Page 38
Item Outline of specifications Remarks Louver control <<Selection of Swing mode>> (Continued) • For the Swing mode, the following three types of modes are SWING/FIX selectable and settable by keeping Swing/Direction button pushed for 4 seconds or more on the remote controller. Standard (4 pieces: same phase) swing →...
Page 39
Item Outline of specifications Remarks Louver control • If there is the locked louver in the unit, [ ] goes on the For the setting (Continued) remote controller screen. operation, refer to [How to set louver • While the following controls are performed, the louvers lock] of Installation operate even if executing the louver lock.
Page 40
Item Outline of specifications Remarks 1) Setting at the centerl controller side enables to select the Central control mode selection contents which can be operated on the remote controller at indoor unit side. ∗ In case of the wireless type, the display lamp does not change but the contents are same.
Page 41
Item Outline of specifications Remarks Self-clean operation 1) When cooling operation mode (AUTO COOL, COOL, DRY) stopped, the following (Dry operation) three self-clean operations are performed. Compressor Self-clean Drain pump Louver ON period operation period 0 to 10 min. None Fan only 10 to 60 min.
Page 42
Item Outline of specifications Remarks 8°C heating/ 1) This functional is intended for the cold latitudes and performs Frost protective objective heating operation (8°C heating operation). operation 2) This function is valid only for combination with the outdoor In a group connection, units (Super Digital Inverter (SDI) 4-series outdoor units).
Page 43
Item Outline of specifications Remarks Soft cooling * Wired remote controller : RBC-AMSU5∗ is required. This function cannot be 1) Sensation of draft can be suppressed by controlling used with remote performance and correcting the louver angle during cooling controllers that are not operation.
Page 44
Item Outline of specifications Remarks Communication 1) Communication type will be determined automatically by the • When performing combination of the indoor unit and the remote controller/ group control in type setting remote sensor. combination with a 2) However, this must be set to TCC-Link when connecting to a TCC-Link dedicated central control device exclusively for TCC-Link.
Page 45
Item Outline of specifications Remarks Rotation / DN [1C1] Data Rotation operation backup 0000 Unavailable (Factory default) operation (Continued) 0001 Available DN [1C2] Data Rotation interval 0001 1 day to 28days 0001: 1day (Factory default) 0028 DN [1C3] Data Rotation lap time 0000 0003: 30 minutes (Factory default) 0 to 70 minutes...
Page 46
Item Outline of specifications Remarks Power shift 1) This is control that, when air conditioners in different systems are installed in the same space controlled in a group, and the load within the space is imbalanced, lowers the used power within the whole group by limiting air conditioners having compressors that are operating at a highly inefficient frequency, and making up for insufficient performance by...
Page 47
Item Outline of specifications Remarks Free cooling 1) The external device can be operated in accordance with the outdoor temperature in cooling operations. Energy saving operations can be realized even if a cooling load exists in the winter, by combining a device that uses the outdoor temperature.
Page 48
Item Outline of specifications Remarks Secondary Secondary heating can be used while heating operations are performed. heating <Control Outline (Normal Mode)> 1) If the difference between the indoor temperature and the outdoor temperature is large while the air conditioner is operating, turn ON the secondary heating.
Page 49
Item Outline of specifications Remarks Secondary DN [C5] Data Secondary heating mode heating (Continued) 0000 Normal mode (Factory default) 0001 Flip mode DN [C6] Data : Set temp. out (high) [ºC] -0015 "-0015": -15ºC to "0015": 15ºC "0000": 0ºC (Factory default) 0015 DN [C7] Data...
7. TROUBLESHOOTING 7-1. Summary of Troubleshooting <Wired remote controller type> 1. Before troubleshooting 1) Required tools/instruments – • screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch • Tester, thermometer, pressure gauge, etc. 2) Confirmation points before check a) The following operations are normal.
Page 53
<Wireless remote controller type> 1. Before troubleshooting 1) Required tools/instruments – • screwdrivers, spanners, radio cutting pliers, nippers, etc. • Tester, thermometer, pressure gauge, etc. 2) Confirmation points before check a) The following operations are normal. 1. Compressor does not operate. •...
7-2. Troubleshooting 7-2-1. Outline of judgment The primary judgment to check whether a trouble occurred in the indoor unit or outdoor unit is carried out with the following method. Method to judge the troubled position by flashing indication on the display part of the indoor unit (sensors of the receiving part) The indoor unit monitors the operating status of the air conditioner, and the blocked contents of self-diagnosis are displayed restricted to the following cases if a protective circuit works.
Page 55
Lamp indication Check code Cause of trouble occurrence Operation Timer Ready Heat exchanger sensor (TCJ) trouble Heat exchanger sensor (TC) trouble Indoor unit sensor trouble Alternate flash Room air temperature sensor (TA) trouble Discharge temp. sensor (TD) trouble Temp. sensor (TE) trouble Operation Timer Ready Temp.
Page 56
7-2-2. Others (Other than Check Code) Lamp indication Check code Cause of trouble occurrence Operation Timer Ready — During test run Simultaneous flash Operation Timer Ready Disagreement of cool/heat — (Automatic cool/heat setting to automatic cool/heat prohibited model, or setting of heating to cooling-only model) Alternate flash - 56 -...
Page 58
Trouble mode detected by indoor unit Operation of diagnostic function Judgment and measures Check Status of Cause of operation Condition code air conditioner 1. Check cables of remote controller and communication adapters. No communication from remote Displayed when Stop trouble is controller (including wireless) and •...
Page 59
Trouble mode detected by remote controller or central controller (Link adapter) Operation of diagnostic function Judgment and measures Status of Check code Cause of operation Condition air conditioner Power supply trouble of remote controller, Indoor EEPROM trouble 1. Check remote controller inter-unit wiring. No communication with header indoor unit 2.
Page 60
7-2-4. Diagnostic Procedure for Each Check Code (Indoor Unit) Check code [E01 trouble] Correct inter-unit cable Is inter-unit cable of A and B normal? of remote controller Is the connector on the harness or Correct connection of connector. the harness from terminal block of Check circuit wiring.
Page 61
[E04 trouble] Is group address setup of Does outdoor operate? Check CODE No. [14]. remote controller correct? Are wiring in indoor unit and Correct wiring and 1, 2, 3 inter-unit cables correct? inter-unit cables. Correct wiring of connector Are wirings of terminal blocks and terminal blocks.
Page 62
Option parts : Application control kit (TCB-PCUC2E) [E11 trouble] Is the connection for the UART communication connector Repair of connector (Indoor P.C. board CN521 connection. red/Application control kit CN1 red) normal? Is connector Replacement of the lead wire for the UART connector’s lead wire.
Page 63
[E18 trouble] Correct inter-unit cable Is inter-unit cable of A and B normal? of remote controller. Is the connector on the harness or the Correct connection of connector. harness from terminal block of indoor unit Check circuit wiring. connected correctly? Is group control operation? Check power connection status of indoor unit...
Page 64
[L20 trouble] Are wiring connections to communication lines Correct wiring connection. Uh (U3, U4) normal? Replace central controller Is the multiple same central (including "1:1 model" connection interface) control system addresses connected? and indoor P.C. board (MCC-1643). Correct central control system address. [L30 trouble] Do outside devices normally work? Replace outside devices.
Page 65
[P10 trouble] Is connection of float switch connector Correct connection (Indoor control board CN34) of connector. normal? Replace indoor P.C. board Does float switch work? Is circuit wiring normal? (MCC-1643). Check and correct wiring and wire circuit. Does drain pump work? Replace drain pump Is power of and indoor P.C.
Page 66
[P12 trouble] Power off. Is the connector Repair the connector CN210 of indoor unit connection. P.C. board connected correctly? Disconnect the connector CN210 to the indoor P.C. board Does the Replace the indoor fan turn smoothly when fan motor. turned by hand? Is each resistance value on the motor side of the...
Page 67
[P19 trouble] Is operation of 4-way valve normal? (Check the pipe temp., etc. Refer to the service manual of the outdoor unit. during cooling/heating operation. Replace outdoor temperature sensors. TE sensor TS sensor Indoor TC sensor [F02 trouble] Is connection of TC sensor connector Correct connection of connector.
Page 68
[F30 trouble] Is connection of the occupancy Correct the connector sensor connector connection. (CN214) normal? By the wired remote controller, change the Is DN code [B5] setup? enable DN code [B5] from [0000] → [0001] Is the Occupancy Exchange the Occupancy sensor unit normal? sensor unit Replace the indoor...
Page 69
[C06 trouble] (“1:1 model” connection interface) Are Uh (U3, U4) communication lines normal? n i l Correct connection of connector. Is connection of connector normal? CN51 of “1:1 model” connection interface (TCC-LINK adapter) P.C. board (MCC-1440) and CN050 of indoor P.C. board Check connection of A and B terminal blocks.
Page 70
[E03 trouble] (Header indoor unit) [E03 trouble] is detected when the indoor unit cannot receive a signal from the remote controller (also central controller). Check A and B remote controllers and communication lines of the central control system Uh (U3, U4). As communication is impossible, this check code [E03] is not displayed on the remote controller and the central controller.
Page 71
Temperature sensor Temperature – Resistance value characteristic table TA, TC, TCJ sensors Representative value Resistance value (kΩ Ω Ω Ω Ω ) Temperature (°C) (Minimum value) (Standard value) (Maximum value) 32.33 33.80 35.30 19.63 20.35 21.09 12.23 12.59 12.95 9.75 10.00 10.25 7.764...
8. REPLACEMENT OF SERVICE P.C. BOARD Indoor Unit CAUTION ∗∗∗ ∗ <Model name: RAV-HM UTP- > For this model, please make all the following settings. CODE No.(DN) Setting data Description 0004 Global model <Note: when replacing the P.C. board for indoor unit servicing> The nonvolatile memory (hereafter called EEPROM, IC503) on the indoor unit P.C.
Page 73
[1] Setting data read out from EEPROM The setting data modified on the site, other than factory-set value, stored in the EEPROM shall be read out. ∗ ∗ ∗ ∗ ∗ <RBC-ASCU1 > (header unit No. when the group operation control) Step2 Step3 Step1...
Page 74
CODE No. required at least 1. The Code No. for the Indoor unit type and Indoor unit capacity are Contents required to set the rotation number setting of the fan. Type 2. If the system/indoor/group addresses are different from those Indoor unit capacity before replacement, the auto-address setting mode starts and the Line address...
Page 75
[2] P.C. Board for indoor unit servicing replacement procedures Step 1 Replace the P.C. board to the P.C. board for indoor unit servicing. At this time, perform the same setting of the jumper wire (J01, J08, J09) setting (cut), switch SW501, (short-circuit) connector CN34 as the setting of the P.C.
Page 76
[3] Writing the setting data to EEPROM ∗ ∗ ∗ ∗ ∗ <RBC-ASCU1 > The settings stored in the EEPROM of the P.C. board for indoor unit servicing are the factory-set values. Step 1 Push and hold the [menu + ] buttons at same time for more than 10 seconds.
Page 77
<RBC-AMTU3∗ ∗ ∗ ∗ ∗ > The settings stored in the EEPROM of the P.C. board for indoor unit servicing are the factory-set values. Step 1 Push buttons on the remote controller simultaneously for more than 4 seconds. ∗ In the group control operation, the unit No. displayed for the first time is the header unit No.. At this time, the CODE No.
Page 78
Table 1. Type: CODE No. 10 Table 2. Indoor unit capacity: CODE No. 11 Setting data Type Type name abb. Setting data Type 0001∗ 4-way Cassette Type RAV-HM∗∗∗UTP-∗ 0000∗ Disable CAUTION ∗ 0009 <Model name: RAV-HM***UTP*> For this model, please make all the following settings. 0012 0013 0015...
9. SETUP AT LOCAL SITE AND OTHERS 9-1. Indoor Unit 9-1-1. Test Run Setup on Remote Controller <RBC-ASCU1∗ ∗ ∗ ∗ ∗ > Be sure to stop the air conditioner before making settings. (Change the setup while the air conditioner is not working.) Push and hold OFF timer button and [ ] setting button simultaneously for 10 seconds or more.
Page 80
<RBC-AMTU3∗ ∗ ∗ ∗ ∗ > 1. When pushing button on the remote controller for 4 seconds or more, “TEST” is displayed on LC display. Then push button. • “TEST” is displayed on LC display during operation of Test Run. •...
Page 81
<Overview of test run operations using the wireless remote controller> Cooling test run: ON/OFF → 18 °C → 17 °C → 18 °C → 17 °C → 18 °C → 17 °C → 18 °C → (test run) → ON/OFF Heating test run: ON/OFF →...
Page 82
9-1-4. Function Selection Setup <Procedure> Perform setting while the air conditioner stops. <RBC-ASCU1∗ ∗ ∗ ∗ ∗ > 2,4,5 Push and hold menu button and [ ] setting button simultaneously for 10 seconds or more. • After a while, the display flashes as shown in the figure. “ALL” is displayed as indoor unit numbers during initial communication immediately after the power has been turned on.
Page 83
<RBC-AMTU3∗ ∗ ∗ ∗ ∗ > Push the buttons simultaneously and hold for at least 4 seconds. CODE No. The unit No. displayed first is the address of the header indoor unit in group SET DATA 00 01 SETTING TEST UNIT No.
Page 84
Function CODE No. (DN Code) table (includes all functions needed to perform applied control on site) Item Description At shipment Filter display delay timer 0000: None 0001: 150H 0002 : 2500H 0002: 2500H 0003: 5000H 0004: 10000H Dirty state of filter 0000: Standard 0000: Standard 0001: High degree of dirt (Half of standard time)
Page 85
Item Description At shipment 77 Dual set point 0000: Unavailable 0002: Available 0000: Unavailable Thermostat OFF fan 0000: Remoto controller setting 0001: Extremely low speed (UL) 0001: Extremely low speedin cooling mode 0002: Fan OFF 0003: Low speed (L) speed (UL) b3 Soft cooling 0000: Unavailable 0001: Available...
Page 86
Item Description At shipment 120 Defrost shift 0000: Unavailable 0001: Available 0001: Available 121 Draft prevention control 0000: Unavailable 0001: Available 0001: Available 1C1 Rotation operation 0000: Unavailable 0001: Available 0000: Unavailable 1C2 Rotation interval 0001: 1 day 0028: 28 days 0001: 1 day 1C3 Rotation lap time 0000: 0...
Page 87
9-1-5. Wiring and Setting of Remote Controller Control 2-remote controller control (Controlled by 2 remote controllers) This control is to operate 1 or multiple indoor units are operated by 2 remote controllers. (Max. 2 remote controllers are connectable.) • When connected 2 remote controllers •...
Page 88
<Wireless remote controller> Wireless remote controller A-B selection Using 2 wireless remote controllers for the respective air conditioners, when the 2 air conditioners are closely installed. Address (A-B selection) must be changed on both signal receiving unit and wireless remote controller. Wireless remote controller B setup 1.
Page 89
9-1-6. Monitor Function of Remote Controller Switch Calling of sensor temperature display <Contents> Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service monitor mode from the remote controller. <Procedure> <RBC-ASCU1∗ ∗ ∗ ∗ ∗ > Push the [menu] button for over 10 seconds.
Page 90
CODE No. Data name Unit CODE No. Data name Unit Room temperature Outdoor heat exchanger (Coil) temperature (TE) °C °C (Remote controller) Outside temperature (TO) °C Indoor suction temperature (TA) °C Compressor discharge temperature (TD) °C Indoor heat exchanger (Coil) Compressor suction temperature (TS) °C °C...
Page 91
Calling of trouble history <Contents> The trouble contents in the past can be called. <Procedure> ∗ ∗ ∗ ∗ ∗ <RBC-ASCU1 > (1) Confirmation and check If a problem occurs with the air conditioner, the OFF timer indicator alternately shows the check code and the indoor Unit No.
Page 92
<RBC-AMTU3∗ ∗ ∗ ∗ ∗ > Push buttons simultaneously for 4 seconds or more to call the service check mode. 01 01 01 01 01 Service Check goes on, the CODE No. is displayed, and then the content of the latest alarm is displayed. The number and trouble contents of the indoor unit in which an TEMP.
Page 93
Indoor unit power-ON sequence • The unit without power feed waits entirely → Waiting status is released by system start Power ON • Reboot when power is fed on the way <By indoor unit which receives power feed from outdoor unit> <Automatic address judgment>...
9-2. Setup at Local Site / Others Model name: TCB-PCNT30TLE2 9-2-1. 1:1 Model Connection Interface (TCC-LINK adapter) 1. Function This model is an optional P.C. board to connect the indoor unit to 1:1 model connection interface. (Communication protocol:TU2C-Link or TCC-Link) 2.
Page 95
4. Wiring Specifications • Use 2-core with no polar wire. No. of wires Size • Match the length of wire to wire length of the central control Up to 1000m: twisted wire 1.25mm system. If mixed in the SMMS system, the wire length is Up to 2000m: twisted wire 2.0mm lengthened with all indoor/outdoor inter-unit wire length at side.
6. External view of P.C. board assembly Terminator (SW01) 7. Address setup In addition to set up the central control address, it is necessary to change the indoor unit number. (Line/Indoor/Group address). For details, refer to 1:1 model connection interface Installation Manual. 9-3.
10. ADDRESS SETUP 10-1. Address Setup <Address setup procedure> When an outdoor unit and an indoor unit are connected and they are twin or when an outdoor unit is connected to each indoor unit respectively in the group operation even if multiple refrigerant lines are provided, the automatic address setup completes with power-ON of the outdoor unit.
10-2. Address Setup & Group Control <Terminology> Indoor unit No. : N – n = Outdoor unit line address N – Indoor unit address n Group address : 0 = Single (Not group control) 1 = Header unit in group control 2 = Follower unit in group control Header unit (= 1) : The representative of multiple indoor units in group operation sends/receives signals to/...
Page 99
3. Single group operation • Each indoor unit controls the outdoor unit individually. Header/Sub Header/Sub Header/Master Header/Sub Header/Sub 4. Multiple groups operation (Manual address setting) Header/Sub Header/Sub Follower/Sub Header/Master Follower/Sub • Master unit: The master unit receives the indoor unit data (thermostat status) of the sub (Without identical line address &...
Page 100
10-2-2. Automatic Address Example from Unset Address (No miswiring) 1. Standard (One outdoor unit) (1-1) (1-2) Individual Header/Master Follower/Sub (Header/Master) Only turning on source power supply (Automatic completion) 2. Group operation (Multiple outdoor units = Multiple indoor units with serial communication only, without twin) Header/Sub Header/Sub Header/Master...
10-3. Address Setup (Manual Setting from Remote Controller) In case that addresses of the indoor units will be determined prior to piping work after wiring work • Set an indoor unit per a remote controller. (Example of 2-lines wiring) • Turn on power supply. (Solid line: Wiring, Broken line: Refrigerant pipe) Outdoor Outdoor...
Page 102
<Indoor unit address> Push the [menu] button until the CODE No. flashes. And using the [ ] buttons, specify the CODE No.13. Push the [menu] button until the SET DATA flashes. And using the [ ] buttons, set an indoor unit address. Push the [OFF timer] button to confirm the SET DATA.
Page 103
MAINTENANCE / CHECK LIST Aiming in environmental preservation, it is strictly recommended to clean and maintain the indoor/outdoor units of the operating air conditioning system regularly to secure effective operation of the air conditioner. It is also recommended to maintain the units once a year regularly when operating the air conditioner for a long time.
11. DETACHMENTS 4-way cassette type WARNING CAUTION Be sure to stop operation of the air conditioner Be sure to put on gloves during working time; before work and then turn off switch of the breaker. otherwise an injury will be caused by a part etc. Part name Procedure Remarks...
Page 105
Part name Procedure Remarks 3) Remove a strap connecting the panel and the suction grille and then remove the suction grille. Hinge Hook for falling-preventive strap Hole for ceiling panel hook 2. Attachment 1) Hook the suction grille to the panel. 2) Attach strap of the suction grille to the panel as before.
Page 106
Part name Procedure Remarks <RBC-U32P**> 1. Detachment Adjust corner cap 1) Pull knob of the adjust corner cap to Pulling direction the arrow direction, remove strap of the adjust corner cap from pin of the panel and then remove all the 4 corners of the cap.
Page 107
Part name Procedure Remarks <RBC-U33P**> 1. Detachment 1) Pull the knob of the adjust corner cap to the arrow direction. Ceiling panel Adjust corner NOTE : The adjust corner cap will be kept being hung with a falling-preventive strap. 2. Attachment 1) Hook the fall-prevention strap securely to Strap of Claw (Hook here)
Page 108
Part name Procedure Remarks <RBC-U32P**> 1. Detachment Ceiling panel Clamper 1) Carry out works of item 1 of and item 1 of 3 . 2) Remove the flap connector (CN510, White, 20P) connected to the control P .C. board and then remove the lead wire from the clamp.
Page 109
Part name Procedure Remarks <RBC-U33P**> 1. Detachment Clamper 1) Carry out works of item 1 of and item 1 of 3 . 2) Remove the flap connector (CN510, White, 20P) connected to the control P .C. board and then remove the lead wire from the clamp.
Page 110
Remarks Part name Procedure Control 1. Detachment Clamp P .C. board 1) Carry out work of item 1 of 2. 2) Remove connectors which are connected from the control P.C. board to the other parts and then remove wiring from the clamp. CN510 : Louver motor (20P, White) CN214 : Signal receiving unit (9P, White)
Page 111
Part name Procedure Remarks 1. Detachment Drain cap Drain cap (outside) 1) Carry out work of item 1 of 2) Loosen screws (3 positions) fixing the drain cap (outside) and then turn the drain cap to the arrow mark direction to remove it. CLOSE CLOSE CLOSE...
Page 112
Part name Procedure Remarks 1. Detachment Fan motor Fixing screw A 1) Carry out work of item 1 of 2) Remove connectors which are connected from the control P .C. board to the other parts and then remove each wiring from the clamp.
Page 113
Part name Procedure Remarks 2. Attachment Fan motor M6 nut (Continued) 2) Fix the fan motor lead, TC sensor and TCJ sensor with the clamp of the bell mouth. 3) Mount the electric parts box with the fixing screws A and B. (Ø4 ×...
Page 114
Part name Procedure Remarks 1. Detachment Drain pump Fixing screw A 1) Carry out works of item 1 of and item 1 of 6 . 2) Remove the drain pump connector Drain por Drain port ain port (CN504, White, 2P) connected to the control P .C.
Page 115
Part name Procedure Remarks 1. Detachment Float switch assembly 1) Carry out works of item 1 of and works from 1) to 5). Float s Float switch assemb Float switch assembly witch assembly 2) Remove the fixing screw and then remove the float switch assembly.
Page 116
Part name Procedure Remarks 1. Detachment Heat exchanger 1) Recover the refrigerant gas. 2) Carry out work of item 1 of 3) Remove refrigerant pipe at indoor unit side. 4) Remove the fixing screws and then remove the piping cover. (Ø4 × 10, 3 pcs.) 5) Remove the drain hose from the drain pump and remove the fixing screws to Fixing screws (Ø4 ×10)
Page 124
WARNINGS ON REFRIGERANT LEAKAGE Check of Concentration Limit The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit. The refrigerant R32 which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer.
Need help?
Do you have a question about the RAV-HM1601UTP Series and is the answer not in the manual?
Questions and answers