Keypad with built-in 4-zone expander and relay

Advertisement

• Keypad address
• Zone expander enable
• Zone expander address
• Zone type
These settings are maintained even when keypad power is
removed.
The keypad options may only be programmed within 60
seconds of applying power. After that, they are not
accessible for editing or viewing. The Address can still be
viewed by holding down the 1 and 3 keys for approximately
three (3) seconds. To re-enter programming mode, remove
and reapply power and proceed as follows:
Perform the following steps to change the keypad options.
1.
Enter the keypad's local program mode within 60
seconds of power-up by pressing and holding down the
[1] and [3] keys at the same time for 3 seconds. The
current keypad address will be displayed with the
cursor under the "tens" digit.
=
CON ADDRESS
CON ADDRESS
CON ADDRESS
CON ADDRESS
31 31 31 31
2. If the current keypad address setting is acceptable (the
default = 31), press the [
Expander Enable field and go to step 3.
To change the current keypad address, first reset the
current address to "00" as follows: press [0] to clear the
"tens" digits. The cursor will move to the "ones" digit
position. Press [0] again to clear the "ones" digit. The
cursor will move back to the "tens" digit position. Now
set the desired keypad address as follows:
Enter the proper "tens" digit for the keypad's address.
The cursor will move to the "ones" digit. Enter the
proper "ones" digit for the keypad's address. Press the
[
] key to store the displayed address and to advance
to the Zone Expander Enable field.
3. By pressing the [1] key, you can toggle the Zone
Expander Enable option (default = OFF).
ZONE EXPANDER
ZONE EXPANDER
ZONE EXPANDER
ZONE EXPANDER
=
OFF [1
OFF [1
ON]
ON]
OFF [1
OFF [1
ON]
ON]
a. To use zone contacts or relay, set the option to ON.
Use the [
] key to advance to the next option. The
Zone Expander Address field will appear. Go to
step 4.
b. To use the 6164/6164US as regular keypad, set the
option to OFF. Use the [
next option. The Tamper field will appear. Go to
step 6.
4. Set the Expander zone address in the same way as the
keypad address.
=
EXP ADDRESS
EXP ADDRESS
EXP ADDRESS
EXP ADDRESS
01 01 01 01
Consult the control panel's installation guide to select the
correct address (default = 01). Use the [
to the Zone Type option.
In order to use the built-in zones and relay, the panel
must be programmed in the same way as for a 4229

module.
5. By pressing the [1] key, you can toggle the Zone Type
option.
WWW.DIYALARMFORUM.COM
• Tamper enable
• Display option
• Sound option
• Language option
] key to advance to the Zone
] key to advance to the
] key to advance
WWW.DIYALARMFORUM.COM
ZONE TYPE
ZONE TYPE
ZONE TYPE
ZONE TYPE
=
EOLR [1
EOLR [1
DBALAN] ] ] ]
DBALAN
EOLR [1
EOLR [1
DBALAN
DBALAN
Either conventional EOL resistor supervised zones or
double-balanced zones (see Fig. 3) may be selected
(default = conventional EOLR). Consult the panel's
installation guide for proper zone type selection. Use
the [
] key to advance to the Tamper option.
6. By pressing the [1] key, you can toggle the Tamper
Enable option (default = OFF).
TAMPER
TAMPER
TAMPER
TAMPER
=
OFF [1
OFF [1
ON]
ON]
OFF [1
OFF [1
ON]
ON]
Refer to the control panel's installation guide to see if
the tamper feature is supported. Use the [
advance to the LCD display option.
7. By pressing either the [1], [2], or [3] keys you can
select the LCD display option.
DISPLAY
DISPLAY
DISPLAY
DISPLAY
=
=
1 1 1 1
ON ON ON ON 2 2 2 2
KEY
KEY 3 3 3 3
KEY
KEY
Option 1:
The display is always active.
Option 2:
The display and LEDs are blanked until a
key is pressed, then displays for 45
seconds after the last key was pressed.
Option 3:
The display and LEDs are blanked 45
seconds after the panel is armed and
remains
disarmed (default = 1).
Use the [
] key to advance to the Sounds option.
8. By pressing the [1] key, you can toggle the Sounds
option (default = ALL SOUNDS).
SOUNDS
SOUNDS
SOUNDS
SOUNDS
=
ALL [1
ALL [1
ALARM]
ALARM]
ALL [1
ALL [1
ALARM]
ALARM]
a. To produce all sounds set the option to ALL
SOUNDS.
b. To produce only key click and alarm sounds set the
option to ALARM.
Use the [
] key to advance to the Language option.
Use only English as the language for UL installations.
9. For languages other than English enter [*]. For
English language press [#]. This will also store the
displayed settings and exit from the local programming
mode.
LANGUAGE?
LANGUAGE?
LANGUAGE?
LANGUAGE?
* = YES
YES # = NO NO NO NO
YES
YES
Press [#] to advance to each of the listed languages.
Place the cursor placed to the left of the selected
language and press [
language prompts.
DEU ENG ESP FR
DEU ENG ESP FR
DEU ENG ESP FR
DEU ENG ESP FR
IT NL RUS
IT NL RUS
IT NL RUS
IT NL RUS
- 3 -
=
DIS
DIS
DIS
DIS
blanked
until
the
] to continue with the selected
] key to
panel
is