York YHJR Series Installation Manual
York YHJR Series Installation Manual

York YHJR Series Installation Manual

R-410a outdoor split-system heat pump

Advertisement

INSTALLATION MANUAL

R-410A OUTDOOR SPLIT-SYSTEM
HEAT PUMP
MODELS: 13 SEER & 14.5 SEER -
THG(D,F)/GHGD/THJ(D,F)/YHJ(D,F)/YHJR/THJR SERIES
1.5 TO 5 TONS - 1 & 3 PHASE
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
ORIFICE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
TXV INSTALLATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Typical Installation with Required Clearances . . . . . . . . . . . . . . . . . . .2
Tubing Hanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Orifice Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Outdoor Unit Control Box - Single Phase . . . . . . . . . . . . . . . . . . . . . . .7
Outdoor Unit Control Box - Three Phase . . . . . . . . . . . . . . . . . . . . . . .7
R-410A Saturation Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
TEST Input Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor
coil with sweat connect lines. Sweat connect units are factory charged
with refrigerant for a matching indoor coil plus 15 feet of field supplied
lines.
Matching indoor coils are available with a thermal expansion valve or
an orifice liquid feed sized for the most common usage. The orifice size
and/or refrigerant charge may need to be changed for some indoor-out-
door unit combinations, elevation differences, or total line lengths. Refer
to Application Data covering "General Piping Recommendations and
Refrigerant Line Length" (Part Number 247077).
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
LIST OF SECTIONS
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
SYSTEM START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
SYSTEM OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
INSTRUCTING THE OWNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
LIST OF FIGURES
Heat Pump Flow Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Time/Temp Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Demand Defrost Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Defrost Operation Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Wiring Diagram - Single Phase (Demand Defrost) . . . . . . . . . . . . . . 13
Wiring Diagram - Single Phase (Time-Temp) . . . . . . . . . . . . . . . . . . 14
Wiring Diagram - Three Phase (Demand Defrost) . . . . . . . . . . . . . . 15
Wiring Diagram - Three Phase (Time-Temp) . . . . . . . . . . . . . . . . . . 16
LIST OF TABLES
X/L Output Categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Defrost Initiate Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service, or maintenance
can cause injury or property damage. Refer to this manual for assis-
tance or for additional information, consult a qualified contractor,
installer, or service agency.
This product must be installed in strict compliance with the enclosed
installation instructions and any applicable local, state, and national
codes including, but not limited to building, electrical, and mechanical
codes.
INSPECTION
As soon as a unit is received, it should be inspected for possible dam-
age during transit. If damage is evident, the extent of the damage
should be noted on the carrier's delivery receipt. A separate request for
inspection by the carrier's agent should be made in writing. See Local
Distributor for more information.
®
835961-UIM-D-0213

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the YHJR Series and is the answer not in the manual?

Questions and answers

Summary of Contents for York YHJR Series

  • Page 1: Table Of Contents

    INSTALLATION MANUAL R-410A OUTDOOR SPLIT-SYSTEM HEAT PUMP MODELS: 13 SEER & 14.5 SEER - THG(D,F)/GHGD/THJ(D,F)/YHJ(D,F)/YHJR/THJR SERIES ® 1.5 TO 5 TONS – 1 & 3 PHASE LIST OF SECTIONS GENERAL ..........1 ELECTRICAL CONNECTIONS .
  • Page 2: Unit Installation

    835961-UIM-D-0213 Requirements For Installing/Servicing R-410A Equipment NOTICE • Gauge sets, hoses, refrigerant containers, and recovery system must be designed to handle the POE type oils, and the higher For multiple unit installations, units must be spaced a minimum of 24 pressures of R-410A.
  • Page 3: Tubing Hanger

    835961-UIM-D-0213 GROUND INSTALLATION PIPING CONNECTIONS The unit may be installed at ground level on a solid base that will not The outdoor unit must be connected to the indoor coil using field sup- shift or settle, causing strain on the refrigerant lines and possible leaks. plied refrigerant grade copper tubing that is internally clean and dry.
  • Page 4: Heat Protection

    835961-UIM-D-0213 PRECAUTIONS DURING BRAZING OF LINES 2. Braze the liquid line to the liquid valve at the outdoor unit. Be sure to wrap the valve body with a wet rag. Allow the nitrogen to continue All outdoor unit and evaporator coil connections are copper-to-copper flowing.
  • Page 5: Orifice Installation

    835961-UIM-D-0213 SECTION IV: ORIFICE INSTALLATION 3. Loosen and remove distributor cap seal. 4. Install the thermal expansion valve to the orifice distributor assembly with supplied fittings. Hand tighten and turn an additional 1/4 turn to seal. Do not overtighten fittings. 5.
  • Page 6: Evacuation

    835961-UIM-D-0213 SECTION VI: EVACUATION Total system charge is determined as follows: 1. Determine outdoor unit factory charge from Tabular Data Sheet. It will be necessary to evacuate the system to 500 microns or less. If a leak is suspected, leak test with dry nitrogen to locate the leak. Repair 2.
  • Page 7: Outdoor Unit Control Box - Single Phase

    835961-UIM-D-0213 Power wiring, control (low voltage) wiring, disconnect switches and over current protection must be supplied by the installer. Wire size should be sized per NEC requirements. Refrigerant charging should only be carried out by a qualified air con- ditioning contractor. All field wiring must USE COPPER CONDUCTORS ONLY and be in accordance with Local, National, Fire, Safety &...
  • Page 8: Typical Field Wiring (Air Handler / Electrical Heat) - (Three Phase)

    835961-UIM-D-0213 ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES THERMOSTAT INDOOR UNIT OUTDOOR UNIT LOW VOLTAGE TERMINAL BLOCK DEFROST IN AIR HANDLER WITH ELECTRIC HEAT CONTROL CONTACTOR B or C B or C GND. SCREW L or X W1/66...
  • Page 9: R-410A Saturation Properties

    835961-UIM-D-0213 SECTION IX: SYSTEM START-UP WITH POWER TO UNIT AND THERMOSTAT IN COOLING POSITION: ENERGIZE CRANKCASE HEATER 1. In the cooling cycle, discharge gas is pumped to the outdoor coil If this unit is equipped with a crankcase heater for the compressor, a which is the condenser.
  • Page 10: Test Input Functionality

    835961-UIM-D-0213 will not energize any additional relays until the voltage level increases. If the voltage drops below approximately 16 VAC, the control will imme- RUN TIME diately de-energize the relay outputs and will not energize any relays TEST Test until the voltage level increases. TEST INPUT RUN TIME The control includes a TEST input connector that can be used for vari-...
  • Page 11: Defrost Initiate Curves

    835961-UIM-D-0213 For instance, the X/L output will be energized with two flashes when NOTICE defrost curve 2 is active. The control only reads the jumper input when the Y and W thermostat inputs are de-energized. If a jumper position is The defrost thermostat delay will make the coil temperature about 75- changed while either of these inputs is energized, the control will not act 80°...
  • Page 12: Instructing The Owner

    835961-UIM-D-0213 REGION C TERMINATE CURVE Defrost Terminated REGION E REGION D No call for defrost Time Defrost (6 hour) prevented Defrost prevented from starting INHIBIT CURVE REGION B REGION A No call for Defrost Time Defrost (6 hour) allowed Call for Defrost AMBIENT TEMPERATURE FIGURE 13: Defrost Operation Curves COOLING OPERATION...
  • Page 13: Wiring Diagram

    835961-UIM-D-0213 SECTION VII: WIRING DIAGRAM FIGURE 14: Wiring Diagram - Single Phase (Demand Defrost) Johnson Controls Unitary Products...
  • Page 14: Wiring Diagram - Single Phase (Time-Temp)

    835961-UIM-D-0213 LEGEND COLOR CODE DANGER - SHOCK HAZARD CAP - CAPACITOR BLK - BLACK TURN OFF ELECTRICAL POWER BEFORE SERVICING TO PREVENT POSSIBLE DAMAGE TO THE EQUIPMENT - CONTACTOR COIL BLU - BLUE AND POSSIBLE PERSONAL INJURY. CCH - CRANKCASE HEATER BRN - BROWN HPS - HIGH PRESS SWITCH GRN - GREEN...
  • Page 15: Wiring Diagram - Three Phase (Demand Defrost)

    835961-UIM-D-0213 LEGEND COLOR CODE DANGER - SHOCK HAZARD TURN OFF ELECTRICAL POWER BEFORE SERVICING - AMBIENT SENSOR BLK - BLACK TO PREVENT POSSIBLE DAMAGE TO THE EQUIPMENT CAP - CAPACITOR BLU - BLUE AND POSSIBLE PERSONAL INJURY. - CONTACTOR COIL BRN - BROWN CCH - CRANKCASE HEATER BR/WH -...
  • Page 16: Wiring Diagram - Three Phase (Time-Temp)

    835961-UIM-D-0213 COLOR CODE LEGEND DANGER - SHOCK HAZARD TURN OFF ELECTRICAL POWER BEFORE SERVICING BLK - BLACK CAP - CAPACITOR TO PREVENT POSSIBLE DAMAGE TO THE EQUIPMENT AND POSSIBLE PERSONAL INJURY. BLU - BLUE - CONTACTOR COIL BRN - BROWN CCH - CRANKCASE HEATER CAUTION GRN - GREEN...
  • Page 17 835961-UIM-D-0213 NOTES Johnson Controls Unitary Products...
  • Page 18: Start Up Sheet

    835961-UIM-D-0213 SECTION VIII: START UP SHEET Heat Pump and Supplementary Heat Start-Up Sheet Print Form Reset Form Proper start-up is critical to customer comfort and equipment longevity Start-Up Date Technician Performing Start-Up Installing Contractor Name Owner Information Name Address City State or Province Zip or Postal Code Equipment Data...
  • Page 19: Defrost Control Board

    835961-UIM-D-0213 Air Side: System Total External Static Pressure Supply static before indoor coil (in w.c.") Supply static after indoor coil (in w.c.") Return Static (in w.c.") before filter Return Static (in w.c.") after filter (furnace side) Total External Static Pressure Maximum Rated ESP (in w.c.") COOL ADJUST...
  • Page 20 Explain the importance of regular filter replacement and equipment maintenance Comments Section Subject to change without notice. Published in U.S.A. 835961-UIM-D-0213 Copyright © 2013 by Johnson Controls, Inc. All rights reserved. Supersedes: 835961-UIM-C-0712 York International Corp. 5005 York Drive Norman, OK 73069...