Smiths SS5 DUAL Installation, Commissioning And User Instructions

Space saver

Advertisement

Space Saver
Installation, commissioning
and user manual
SS2E | SS3E | SS80E | SS5 DUAL
Issue 001 | November 2018
ENGLISH | UK | IRL | SmithsEP.co.uk
Issue 001 - November 2018 | SmithsEP.co.uk | 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SS5 DUAL and is the answer not in the manual?

Questions and answers

Summary of Contents for Smiths SS5 DUAL

  • Page 1 Space Saver Installation, commissioning and user manual SS2E | SS3E | SS80E | SS5 DUAL Issue 001 | November 2018 ENGLISH | UK | IRL | SmithsEP.co.uk Issue 001 - November 2018 | SmithsEP.co.uk | 1...
  • Page 2: Table Of Contents

    Product name: Installation - Controller Space Saver Pairing - Controller with Heaters Commissioning Product range: SS2E, SS3E, SS80E, SS5 DUAL Installation - with advanced features Commissioning Listed above confirms with the following European Fault finding Union directives: Low Voltage Directive (73/23/EEC)
  • Page 3: Symbols Used In This Guide

    Symbols This manual contains information and prescriptions marked by the following symbols: Ignoring these safety High temperature Ignoring these safety provisions marked by surface. provisions marked by the symbol “caution: Take utmost care the symbol “caution: electricity” may to prevent people hazard”...
  • Page 4: Application

    Important safety and installation instructions Prior to installation, read these installation and operating instructions. The installation and operation should also be in accordance with national regulations and accepted codes of good practice. 6. Electrical connection IMPORTANT: Connection to the power supply must be effected by means of a fixed power cable which is fitted with a plug-type connection or a two pole isolating switch with a minimum contact opening of 3 mm.
  • Page 5: Product Information

    Product dimensions and performance SS2E SS80E Heat output Power Heat output Heat Output Fused Mains Cable Consumption (kW) spur (kW) Power Heat Output Fused Mains Cable 0.6kW/1.2kW 0.6kW/1.2kW Consumption (kW) spur (kW) 1kW/2kW 1kW/2kW Voltage: 230V SS3E Heat output Power...
  • Page 6 Product dimensions and performance WALL CONTROLLER SS5 DUAL Pattress Pipe centres Heat output - electric mode Power Heat Output Fused Mains Cable Consumption (kW) spur (kW) 1.0kW Heat output - hydronic mode It is recommended that the Space Saver model chosen is capable of maintaining the calculated heat loss at normal heat output (l) enabling the boost setting (ll) to be used for faster heat up.
  • Page 7: Installation - Heater

    2b. Vent air through bleed Width A Height B* Model (mm) (mm) SS2E SS3E SS80 SS5 DUAL * The overall height of the grille is 100mm. Use care when cutting the opening. Issue 001 - November 2018 | SmithsEP.co.uk | 7...
  • Page 8: Installation - Controller

    5. Overlay grille (optional) 2c. Electrical connection - Heater • Isolate the electrical supply and connect the heater electric cable to the fused spur • The fused spur must not be directly above the heater, but should be accessible after completion of the installation •...
  • Page 9: Pairing Controller With Heaters

    Pairing controller • Run-back Timer This can be used to limit the run time of the with heaters heater from between 5 minutes and 2 hours. The Run-back Timer cannot used be used in In order to pair your appliance with the controller: conjunction with Temperature control for Setback (SETB).
  • Page 10: Commissioning

    Commissioning SS3E SS2E 1. Before switching the heater on, please ensure 1. Before switching the heater on, please ensure the fascia grille is free from obstruction the fascia grille is free from obstruction 2. Ensure your fused spur is switched ON 2.
  • Page 11 SS80E SS5 DUAL 1. Before switching the heater on, please ensure 1. Before switching the heater on, please ensure the fascia grille is free from obstruction the fascia grille is free from obstruction 2. Ensure your fused spur is switched ON 2.
  • Page 12: Installation - With Advanced Features

    Installation - with 2. Temperature control for Comfort (COMF) advanced features Switch 1 controls the display screen. If it is set to 1. Getting to know your ’ON’ the temperature is displayed as Fahrenheit. battery controller If it is set to ‘OFF’ the temperature is displayed as Celsius.
  • Page 13 3. Temperature control for In timer mode, switch 3 or 4 must be in the ‘ON’ position. This mode allows for 3 different settings Setback (SETB) which will alter the time period for each segment. Switch 3 - Each time period represents 5 minutes For this mode, the switches are set as shown below.
  • Page 14: Commissioning

    Commissioning - see page 10 Fault finding In the event of any difficulty, please contact us on +44 (0) 1245 324560. Fault Checking/Solution Check the power supply is switched ON Check fuse in fused spur Check the fan switch is set to ON Fan does not run/no heat output Check the battery in the controller and replace if necessary Check the wireless controller thermostat is calling for heat...
  • Page 15: User Manual

    Space Saver User manual SS2E | SS3E | SS80E | SS5 DUAL Issue 001 | November 2018 ENGLISH | UK | IRL | SmithsEP.co.uk Issue 001 - November 2018 | SmithsEP.co.uk | 15...
  • Page 16: Important Safety Guidance

    Important safety and installation instructions Please read this user manual before operating this appliance. The operation should also be in accordance with national regulations and accepted codes of good practice. This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
  • Page 17: Introduction

    How it works - Heater • Run-back Timer This can be used to limit the run time of the heater from between 5 minutes and 2 hours. Cooler air is drawn in by the fan and heated as it passes through the heating element before being The Run-back Timer cannot used be used in discharged gently back into the room.
  • Page 18: Operation

    How to operate SS2E Basic setting enabled Temperature control for Comfort (COMF) enabled 1. Ensure your fused spur is switched ON 2. Ensure the wireless controller is switched ON 1. Ensure your fused spur is switched ON 3. Switch the upper fan switch to ON 2.
  • Page 19 SS2E Temperature control for Comfort How to operate – Run back Timer (COMF) and Temperature control mode enabled for Setback (SETB) enabled 1. Ensure your fused spur is switched ON 2. Ensure the wireless controller is switched ON 1. Ensure your fused spur is switched ON 3.
  • Page 20 How to operate SS3E Basic setting enabled Temperature control for Comfort (COMF) enabled 1. Ensure your fused spur is switched ON 2. Ensure the wireless controller is switched ON 1. Ensure your fused spur is switched ON 3. Ensure the heater is paired with the wireless 2.
  • Page 21 SS3E Temperature control for Comfort How to operate – Run back Timer (COMF) and Temperature control mode enabled for Setback (SETB) enabled 1. Ensure your fused spur is switched ON 2. Ensure the wireless controller is switched ON 1. Ensure your fused spur is switched ON. 3.
  • Page 22 How to operate SS80E Basic setting enabled Temperature control for Comfort (COMF) enabled 1. Ensure your fused spur is switched ON 2. Ensure the wireless controller is switched ON 1. Ensure your fused spur is switched ON 3. Ensure the wireless controller is paired (page 9) 2.
  • Page 23 SS80E Temperature control for Comfort How to operate – Run back Timer (COMF) and Temperature control mode enabled for Setback (SETB) enabled 1. Ensure your fused spur is switched ON 2. Ensure the wireless controller is switched ON 1. Ensure your fused spur is switched ON 3.
  • Page 24 How to operate SS5 DUAL Basic setting enabled Temperature control for Comfort (COMF) enabled 1. Set the upper rocker switch on the fascia grille to the right (blue) and the lower switch to the 1. Ensure your fused spur is switched ON left or right - the fan should run 2.
  • Page 25 SS5 DUAL Temperature control for Comfort How to operate – Run back Timer (COMF) and Temperature control mode enabled for Setback (SETB) enabled 1. Ensure your fused spur is switched ON 2. Ensure the wireless controller is switched ON 1. Ensure your fused spur is switched ON 3.
  • Page 26: Fault Finding

    Fault finding This Space Saver is covered by a free 5-year parts and labour guarantee. Please refer to the Fault finding table below for advice. In the event of difficulty, please contact us on +44 (0) 1245 324560. Fault Checking/Solution Check the power supply is switched ON Check fuse in fused spur Check the fan switch is set to ON...
  • Page 27: Registering Your Product

    Registering your product Disposal As part of the policy of continuous product Thank you for purchasing a Smith’s product. It has improvement, Smith’s Environmental Products LTD been designed and manufactured to the highest reserves the right to alter specification without quality standards to ensure it gives you efficient prior notice.
  • Page 28: Smithsep.co.uk | Issue 001 - November

    Happy to help To view the full product information download the datasheet at: Smith’s Environmental Products Ltd is one of the leading manufacturers of heating and cooling www.SmithsEP.co.uk products in the UK. We are committed to achieving the highest standards and our faith is For product information, customer services or supported by a free five year parts and labour sales support call us on +44 (0) 1245 324900...