JE Kang 1.02 Add your experience 2012/1/13 JE Kang 1.03 Modify the wrong letters 2012/2/13 JE Kang 1.04 Changed Crevis TEL 2013/4/4 JE KANG 1.05 Environment Spec. 50℃→55℃ (UL Temp) 2013/7/3 JE Kang Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
Expansion Module Status LED (I/O) ....................13 2.3.5. Field Power Status LED ........................13 Dimension ..................................14 3.1. NA-9171 ..............................14 3.2. NA-9173 ..............................14 Mechanical Set Up ..............................15 4.1. Total Expansion ............................15 Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
Certification c-UL-us UL Listed Industrial Control Equipment, certified for U.S. and Canada See UL File E235505 DNV CERTIFICATE No. A-10666 (NA-9173) LR/FCC CE Certificate EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
45mm x 99mm x 70mm Environment Condition Refer to Environment Specification Environmental Specifications Operating Temperature -20 to 55℃ Non-Operating Temperature -40℃ to 85℃ Relative Humidity 5%~90% non-condensing Operating Altitude 2000m Mounting DIN rail Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
Indicator 1 Green, Transmit Data (TXD) 1 Green/Red Expansion Module Status (I/O) 1 Green, Field Power Status Starter module – left side of FnIO system Module Location Field Power Detection About 11Vdc Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
2.3.3. Transmit Data LED(TXD) State LED is : To indicate : Not Powered Device is not on-line or may not be powered Adapter (Slave) transmit frame. Adapter transmit frame Flashing Green About 20msec flashing. Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
- Mismatch vendor code between adapter and expansion module. 2.3.5. Field Power Status LED State LED is : To indicate : Not Supplied Field Not supplied 24V dc field power Power Supplied Field Power Green Supplied 24V dc field power Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
As above figure in order to safeguard the FnIO module from jamming, it should be fixed onto the DIN rail with locking level. To do so, fold on the upper of the locking lever. To pull out the FnIO module, unfold the locking lever as below figure. Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
It is comprised of 6 data pin and 2 field power pin. Do not touch data and field power pins in order to avoid soiling and damage by ESD noise. Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
The Network Adapter Module forms the link between the field bus and the field devices with the Expansion Modules. The connection to different field bus systems can be established by each of the corresponding Network Adapter Module, e.g. for SyncNet, PROFIBUS, CANopen, DeviceNet, Ethernet/IP, CC-Link, MODBUS/Serial, MODBUS/TCP etc. Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
Token output port of Processor module. Serial Output Transmitter output port of Processor module. Serial Input Receiver input port of Processor module. Reserved Reserved for bypass Token. Field GND Field Ground. Field Vcc Field supply voltage (24Vdc). Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
Data Low Signal Common SHIELD Internally Shorted -3986-90102/Molex or 1862506/Phoenix Compatible with DeviceNet 5-pin Open Connector The use of an incorrect supply voltage or frequency can cause severe damage to the component. Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
To minimize the reflections from the end of the RS485-cable it is required to place a Line Termination near each of the 2 Ends of the Bus. Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
X 10 (MSD) X 1 (LSD) The above figure shows MAC ID 27(=2*10 + 7*1) of a slave node. MAC ID addresses have to be unique throughout the entire interconnected networks. Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
0x0800 ~ Read/Write Process output image bits 1, 5, 15 All output registers area is addressable by bit address. Size of output image bit is size of output image register * 16. Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
4: No Expansion Slot FP (Field Power) : 0: 24Vdc Field Power On. 1: 24Vdc Field Power Off ES (MODBUS Error Setup) : 0: No Error Setup 1: Error Setup Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
Page 25
Analog Input Ch1 low byte (Slot#8) Analog Input Ch0 high byte (Slot#8) 0x0007 Discrete In low 8pts (Slot#9) Analog Input Ch1 high byte (Slot#8) 0x0008 Empty, Always 0 Discrete In 4pts Discrete In high 8pts (Slot#9) (Slot#10) Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
Page 26
Input Assembly Priority : 1) Analog Input Data (Word type) 2) 8 or 16 points Discrete Input Data (Byte type) 3) 4 points Input Data (Bit type) 4) 2 points Input Data (Bit type) Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
Analog out Ch1 high byte Analog out Ch1 low byte (Slot#9) (Slot#9) 0x0808 Discrete out high 8pts Discrete out low 8pts (Slot#10) (Slot#10) Discrete out 4pts 0x0809 Empty, Don’t care Empty, Don’t care (Slot#11) Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
Page 28
Output Assembly Priority : 1) Analog Output Data (Word type) 2) 8 or 16 points Discrete Output Data (Byte type) 3) 4 points Output Data (Bit type) 4) 2 points Output Data (Bit type) Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
Write a number of output words Unicast / Broadcast Read a number of input words / 23 (0x17) Read / Write Multiple register Unicast Write a number of output words Refer to MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1a Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
Output Status 0x02 0x02 0x30, 0x32 “9F” Error Check (CRC/LRC) 0x8F, 0x6D 0x39, 0x46 End of Frame t1-t2-t3 CR, LF 0x0D, 0xA * In case of address 0x1015~0x1000 output bit value: 00000010_01010101. Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
“00” Input Status 0x00 0x00 0x30, 0x30 “75” Error Check (CRC/LRC) 0x50, 0x78 0x37, 0x35 End of Frame t1-t2-t3 CR, LF 0x0D, 0xA In case of address 0x0015~0x0000 output bit value: 00000000_10000000. Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
Description 0x0001(1) 0x0000, 0xFF00 Echo Request Data Reset Reset with Factory Default* 0x0001(1) 0x55AA Echo Request Data *All expansion slot configuration parameters are cleared. Sub-function 0x000A(10) Clear Counters and Diagnostic Register Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
Page 37
The response data field returns the quantity of watchdog error addressed to the remote device since its last restart, clear counters operation, or power–up. Sub-function Data Field (Request) Data Field (Response) Description 0x0065(101) 0x0000 Watchdog Error Count Sub-function 0x0066(102) Change Slave IO Output Status Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
0x0A 0x0A 0x30, 0x41 “D0” Error Check (CRC/LRC) 0xD1, 0x6A 0x44, 0x30 End of Frame t1-t2-t3 CR, LF 0x0D, 0xA In case of address 0x1015~0x1000 output bit value: 00000000_00000000 changes to 00000001_01010101. Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
1 word In ASCII mode byte-byte time gap is over setting value during receiving frame, this frame will be cancelled (dropped). 0x1028(4136) Read 2 words IO update time, main loop time. (100usec unit) Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
Reserved. Adapter IO identification vendor code. *, ** After the system is reset, the new “Set Value” action is applied. ** If the slot location is changed, set default value automatically (all expansion slots are live). Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
Page 46
*** Slot Configuration parameter saved by internal EEPROM during power cycle until slot position changed. *** All of output modules and special modules have the slot configuration parameter data. Refer to Document. (FnIO_Configuration_Parameter_Memory_Register_Rev1.01) Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
Check status in software for Master NET LED flashed green Failure of exchanging data with master configuration. Check BUS line cable for connection with master. NET LED is red Communication connecting lost Check duplication address. Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...
Page 49
Configuration of communication baud rate I/O size Configuration of each node Ground and environment - Check ground is contacted - Check environment factor (temperature, humidity, etc.) is in less than regular limit Copyright(C) CREVIS Co.,Ltd Support +82-31-899-4599 URL : www.crevis.co.kr...