FOUR FUNCTION AIR SWITCH WITH TIMER
MODEL: RC2343PT
INPUT VOLTAGE: 120 VOLT OR
RATING: 20 AMP. (R), 1 HP.-120 V.; 20 AMP. (R), 2 HP.-240 V.
SUITABLE FOR INDOOR/OUTDOOR USE (TYPE 3R) AND FOR
POOL/SPA APPLICATIONS.
CAUTION, RISK OF ELECTRIC SHOCK
Install at least 5 ft. (at least 3 meters in Canada) from the inside
edge of pool/spa. Mount at least 1 foot (30 cm) from the ground
with the arrows up.
...do not permit children to operate this control or use the Pool/Spa
unless they are closely supervised at all times.
...always disconnect electricity before servicing this control or the
equipment connected to it. THIS CONTROL IS NOT TO BE USED
AS A POWER DISCONNECT.
This Air Switch is designed to control a pump,
(single or two speed, 120 V. or 240V.), and
a blower (120 V. or 240 V.) safely, without
electricity at the spa side. Timer automatically
controls pump (LO speed, if two speed pump)
for desired filtration cycle. Each time pressure
is applied to the remote air button, the pump
the blower will operate sequentially
and/or
as shown in the table.
TO WIRE: Follow diagram below. Wire according to National Electrical Code
(including article 680) and Local Electrical Code Requirements. Use COPPER
conductors ONLY. For rated minimum 75˚C. Ground installation. Install dead-
front. KEEP DOOR CLOSED AT ALL TIMES.
TO PUMP
SEE
NOTE
240V.
TWO SPEED
PUMP
For single speed pump and/or 120 Volt equipment, follow wiring above except:
240 V. Single Speed Pump - Connect both BLUE and GRAY leads to LOAD
1 of pump.
120 V. Two Speed Pump - Connect NEUTRAL to WHITE
COMMON of pump.
120 V. Single Speed Pump - Connect NEUTRAL to WHITE lead and pump
NEUTRAL. Connect both BLUE and GRAY leads to pump LOAD
terminal.
120 V. Blower-Connect NEUTRAL to blower NEUTRAL.
120 V. Freeze Protection - Connect NEUTRAL to Freeze Protection
NEUTRAL.
No Freeze Protection - Permanently insulate (cap) BROWN lead.
INTERMATIC INCORPORATED
158RC11810
240 VOLT - 60 HZ.
TO BLOWER
240V.
BLOWER
COMMON
SPRING GROVE, ILLINOIS 60081-9698
EQUIPMENT
P
SINGLE
U
SPEED
M
TWO
P
SPEED
BLOWER
PUMP INPUT
MUST ALWAYS BE USED
NOTE: BROWN LEAD IS FOR FREEZE
PROTECTION INPUT. INSULATE IF NOT
USED.
LINE 1
NEUT.
LINE 2
LINE 3
LINE 4
ANSI/UL508
ANSI/UL1563
NEC Sec. 680
SEQUENCE
1
2
3
TIMER ON
ON
ON/OFF
TIMER HIGH HIGH OFF
LOW
OFF
OFF
ON
TYPICAL WIRING
240V. TWO SPEED PUMP
240V. BLOWER
240V. FREEZE PROTECTION
IMPORTANT
NEUTRAL WIRE
240V.
PUMP
INPUT
240V.
BLOWER
INPUT
lead and
4
OFF
ON