Summary of Contents for ABB REC670 2.0

  • Page 1 ® Relion 670 series Bay control REC670 2.0 Product guide...
  • Page 2: Table Of Contents

    Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. Drawings and diagrams are not binding.
  • Page 3: Product Version

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Issued: July 2016 Revision: C 1. Application The auto-reclose for single-, two-, and/or three-phase reclose REC670 is used for the control, protection and monitoring of includes priority circuits for multi-breaker arrangements. It co- different types of bays in power networks.
  • Page 4 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Description of configuration A30 REC670 A30 – Double busbar in single breaker arrangement 12AI (6I + 6U) Control Control Control S CILO S CSWI S XSWI Control Control Control S CILO...
  • Page 5 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Description of configuration A31 REC670 A31 – Bus Coupler Bay arrangement 12AI (6I + 6U) Control Control Control S CILO S CSWI S XSWI QC21 QC11 Control Control Control S CILO...
  • Page 6: Description Of Configuration B30

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Description of configuration B30 REC670 B30 - Double breaker arrangement 12AI (6I + 6U) Control Control Control S CILO S CSWI S XSWI WA2_VT Control Control Control SC/VC S CILO S CSWI...
  • Page 7: Description Of Configuration C30

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Description of configuration C30 REC670C30 – Complete one-and a half breaker diameter arrangement 24AI (6I + 6U, 6I+6U) Control Control Control S CILO S CSWI S XSWI WA1_VT WA1_QA1 Control Control...
  • Page 8: Available Functions

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 2. Available functions Main protection functions = number of basic instances = option quantities 3-A03 = optional function included in packages A03 (refer to ordering details) IEC 61850 ANSI Function description...
  • Page 9: Current Protection

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Back-up protection functions IEC 61850 ANSI Function description Bay control REC670 Current protection PHPIOC Instantaneous phase overcurrent 1-C51 1-C51 2-C52 2-C53 protection OC4PTOC Four step phase overcurrent protection 1-C51 1-C51 2-C52...
  • Page 10: Multipurpose Protection

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 IEC 61850 ANSI Function description Bay control REC670 SAPFRC Rate-of-change frequency protection 6-E01 6-E01 6-E01 6-E01 FTAQFVR Frequency time accumulation protection 0-12 Multipurpose protection CVGAPC General current and voltage protection 4-F01...
  • Page 11: Secondary System Supervision

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Control and monitoring functions IEC 61850 ANSI Function description Bay control REC670 Control SESRSYN Synchrocheck, energizing check and synchronizing 0-6, 0-2 SMBRREC Autorecloser 0-6, 0-4 1-H04 1-H04 2-H05 3-H06 APC8 Apparatus control for single bay, max 8 apparatuses (1CB) incl.
  • Page 12 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 IEC 61850 ANSI Function description Bay control REC670 FUFSPVC Fuse failure supervision VDSPVC Fuse failure supervision based on voltage difference 1-G03 1-G03 1-G03 1-G03 Logic SMPPTRC Tripping logic TMAGAPC Trip matrix logic...
  • Page 13 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 IEC 61850 ANSI Function description Bay control REC670 CVMMXN, Measurements CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU AISVBAS Function block for service value presentation of secondary analog inputs EVENT Event function DRPRDRE, Disturbance report...
  • Page 14 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Communication IEC 61850 ANSI Function description Bay control REC670 Station communication LONSPA, SPA SPA communication protocol LON communication protocol HORZCOMM Network variables via LON PROTOCOL Operation selection between SPA and IEC 60870-5-103 for SLM...
  • Page 15 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 IEC 61850 ANSI Function description Bay control REC670 VCTRSEND Horizontal communication via GOOSE for VCTR GOOSEVCTRRC Horizontal communication via GOOSE for VCTR MULTICMDRCV, Multiple command and transmit 60/10 60/10 60/10 60/10...
  • Page 16 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 IEC 61850 ANSI Function description Bay control REC670 ZCLCPSCH Local acceleration logic 1-K01 1-K01 1-K01 1-K01 ECPSCH Scheme communication logic for residual 1-C51 1-C51 1-C52 1-C53 overcurrent protection ECRWPSCH Current reversal and weak-end infeed...
  • Page 17 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Basic IED functions Table 1. Basic IED functions IEC 61850 or function Description name INTERRSIG Self supervision with internal event list SELFSUPEVLST Self supervision with internal event list TIMESYNCHGEN Time synchronization module...
  • Page 18: Autorecloser Smbrrec

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 1. Basic IED functions, continued IEC 61850 or function Description name ALTRK Service tracking ACTIVLOG Activity logging parameters FSTACCS Field service tool access via SPA protocol over ethernet communication PCMACCS...
  • Page 19 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Apparatus control features: • Bus-section breaker for double busbars, A1A2_BS • Select-Execute principle to give high reliability • Bus-section disconnector for double busbars, A1A2_DC • Selection function to prevent simultaneous operation •...
  • Page 20 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 control and supervision, 6 binary inputs TCMYLTC as well as IED in "ChangeLock" state from remote. In this way, simple Tap changer control and supervision, 32 binary inputs commands can be sent directly to the IED outputs, without TCLYLTC are used for control of power transformers with a on- confirmation.
  • Page 21 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 The directional function needs voltage as it is voltage polarized NS4PTOC can be set directional or non-directional with memory. The function can be set to be directional or non- independently for each of the steps.
  • Page 22 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 transformer will experience forced ageing. As a consequence of cause unwanted operation of zero sequence or negative this the risk of internal phase-to-phase or phase-to-earth faults sequence current functions. will increase.
  • Page 23 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 6. Voltage protection 7. Frequency protection Two step undervoltage protection UV2PTUV Underfrequency protection SAPTUF Undervoltages can occur in the power system during faults or Underfrequency occurs as a result of a lack of generation in the abnormal conditions.
  • Page 24 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 the neutral point current on a separate input taken from another Frequency time accumulation protection FTAQFVR set of cores on the current transformer. Frequency time accumulation protection FTAQFVR is based on measured system frequency and time counters.
  • Page 25: Scheme Communication

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 (e.g. inputs and outputs) as the standard pre-processing overcurrent protection, the directional residual overcurrent function block SMAI. However the main difference is that it can protection can be supported with a logic that uses be used to extract any frequency component from the input communication channels.
  • Page 26 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 length, as well as all functionality necessary for correct co- • RSMEMORY function block is a flip-flop that can reset or set operation with autoreclosing functions. an output from two inputs respectively. Each block has two outputs where one is inverted.
  • Page 27: Monitoring

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 • measured voltages, currents, frequency, active, reactive Elapsed time integrator with limit transgression and overflow and apparent power and power factor supervision (TEIGAPC) • measured analog values from merging units The Elapsed time integrator function TEIGAPC is a function that •...
  • Page 28 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 report files may be uploaded to PCM600 for further analysis Disturbance recorder DRPRDRE using the disturbance handling tool. The Disturbance recorder function supplies fast, complete and reliable information about disturbances in the power system. It...
  • Page 29: Metering

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 measure value expander block (RANGE_XP) has been reverse direction. Energy values can be read or generated as introduced to enable translating the integer output signal from pulses. Maximum demand power values are also calculated by the measuring functions to 5 binary signals: below low-low limit, the function.
  • Page 30: Human Machine Interface

    IEDs. The LHMI is used for setting, monitoring and controlling. SPA communication protocol A single glass or plastic port is provided for the ABB SPA protocol. This allows extensions of simple substation 15. Basic IED functions automation systems but the main use is for Substation Monitoring Systems SMS.
  • Page 31: Remote Communication

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 with unsolicited events, time synchronizing and disturbance 18. Hardware description reporting is provided for communication to RTUs, Gateways or Hardware modules HMI systems. Power supply module PSM The power supply module is used to provide the correct internal...
  • Page 32 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 communication (SPA, IEC 60870-5-103 and DNP3 port) and High impedance resistor unit one port is dedicated for LON communication. The high impedance resistor unit, with resistors for pick-up value setting and a voltage dependent resistor, is available in a Line data communication module LDCM single phase unit and a three phase unit.
  • Page 33: Mounting Alternatives

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 IEC06000182-2-en.vsd IEC06000182 V2 EN Figure 8. A 1/2 x 19” size IED side-by-side with RHGS6. xx08000165.vsd IEC08000165 V1 EN Figure 7. Case with rear cover and 19” rack mounting kit Case size (mm)/(inches) 6U, 1/2 x 19”...
  • Page 34: Connection Diagrams

    1MRK511313-BEN C Product version: 2.0 19. Connection diagrams Connection diagrams for Configured products Connection diagrams Connection diagram, REC670 2.0, A30 1MRK002803-CA The connection diagrams are delivered on the IED Connectivity Connection diagram, REC670 2.0, A31 1MRK002803-CD package DVD as part of the product delivery.
  • Page 35: Technical Data

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 20. Technical data General Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified...
  • Page 36 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 4. MIM - mA input module Quantity: Rated value: Nominal range: Input resistance = 194 Ohm Input range ± 5, ± 10, ± 20mA 0-5, 0-10, 0-20, 4-20mA Power consumption each mA-board £...
  • Page 37 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Binary inputs and outputs Table 7. BIM - Binary input module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V RL ±20%...
  • Page 38 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 9. IOM - Binary input/output module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V RL ±20% 220/250 V RL ±20%...
  • Page 39 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 11. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2) Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay) Binary outputs...
  • Page 40: Influencing Factors

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 13. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage 250 V AC/DC Number of outputs...
  • Page 41 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 16. Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal Influence range Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01% / %...
  • Page 42 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Type tests according to standards Table 18. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV...
  • Page 43 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 20. Environmental tests Test Type test value Reference standard Cold operation test Test Ad for 16 h at -25°C IEC 60068-2-1 Cold storage test Test Ab for 16 h at -40°C...
  • Page 44: Differential Protection

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Differential protection Table 23. 1Ph High impedance differential protection HZPDIF Function Range or value Accuracy Operate voltage (10-900) V ± 1.0% of I at I ≤ I I=U/R ± 1.0% of I at I > I Reset ratio >95% at (30-900) V...
  • Page 45: Current Protection

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Current protection Table 24. Instantaneous phase overcurrent protection PHPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ± 1.0% of I at I ≤ I ± 1.0% of I at I > I Reset ratio >...
  • Page 46 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 26. Instantaneous residual overcurrent protection EFPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 47 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 28. Four step negative sequence overcurrent protection NS4PTOC Function Range or value Accuracy Operate value, negative (1-2500)% of lBase ± 1.0% of I at I £ I sequence current, step 1-4 ±...
  • Page 48 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 29. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy (0.25-200.00)% of lBase Operate level for 3I ·cosj ± 1.0% of I at I £ I directional residual ±...
  • Page 49 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 30. Thermal overload protection, one time constant LCPTTR/LFPTTR Function Range or value Accuracy Reference current (2-400)% of IBase ±1.0% of I Reference temperature (0-300)°C, (0 - 600)°F ±1.0°C, ±2.0°F Operate time: Time constant t = (1–1000)
  • Page 50 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 32. Breaker failure protection CCRBRF Function Range or value Accuracy Operate phase current (5-200)% of lBase ±1.0% of I at I £ I ±1.0% of I at I > I Reset ratio, phase current >...
  • Page 51 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 35. Directional underpower protection GUPPDUP Function Range or value Accuracy Power level (0.0–500.0)% of SBase ± 1.0% of S at S ≤ S for Step 1 and Step 2 ± 1.0% of S at S > S where ×...
  • Page 52 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 38. Capacitor bank protection CBPGAPC Function Range or value Accuracy Operate value, overcurrent (10-900)% of lBase ±2.0% of I at I ≤ I ±2.0% of I at I > I Reset ratio, overcurrent >95% at (100-900)% of IBase...
  • Page 53: Voltage Protection

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Voltage protection Table 39. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1.0–100.0)% of ±0.5% of U Absolute hysteresis (0.0–50.0)% of UBase ±0.5% of U...
  • Page 54 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 40. Two step overvoltage protection OV2PTOV Function Range or value Accuracy Operate voltage, step 1 and 2 (1.0-200.0)% of UBase ±0.5% of U at U ≤ U ±0.5% of U at U > U Absolute hysteresis (0.0–50.0)% of...
  • Page 55 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 42. Voltage differential protection VDCPTOV Function Range or value Accuracy Voltage difference for alarm and (2.0–100.0) % of UBase ±0.5% of U trip UBase Under voltage level (1.0–100.0) % of ±0.5% of U...
  • Page 56: Frequency Protection

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Frequency protection Table 44. Underfrequency protection SAPTUF Function Range or value Accuracy Operate value, start function, at symmetrical three (35.00-75.00) Hz ± 2.0 mHz phase voltage Operate time, start at f + 0.02 Hz to f...
  • Page 57 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 46. Rate-of-change frequency protection SAPFRC Function Range or value Accuracy Operate value, start function (-10.00-10.00) Hz/s ±10.0 mHz/s Operate value, restore enable frequency (45.00-65.00) Hz ±2.0 mHz Definite restore time delay (0.000-60.000) s...
  • Page 58: Multipurpose Protection

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Multipurpose protection Table 48. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, - NegSeq, -3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1-phase2, phase2- phase3, phase3-phase1, MaxPh-Ph,...
  • Page 59 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 48. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Independent time delay, undervoltage at 1.2 to 0.8 x U , step 1 - (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is...
  • Page 60 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 49. Voltage-restrained time overcurrent protection VRPVOC Function Range or value Accuracy Start overcurrent (2.0 - 5000.0)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio, overcurrent >...
  • Page 61: Secondary System Supervision

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Secondary system supervision Table 50. Current circuit supervision CCSSPVC Function Range or value Accuracy Operate current (10-200)% of IBase ±10.0% of I at I ≤ I ±10.0% of I at I > I Reset ratio, Operate current >90%...
  • Page 62 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 52. Fuse failure supervision VDSPVC Function Range or value Accuracy Operate value, block of main fuse (10.0-80.0)% of UBase ±0.5% of Ur failure Reset ratio <110% Operate time, block of main fuse Min.
  • Page 63 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Control Table 53. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase ±...
  • Page 64 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 54. Autorecloser SMBRREC Function Range or value Accuracy Number of autoreclosing shots 1 - 5 Autoreclosing open time: shot 1 - t1 1Ph (0.000-120.000) s ± 0.2% or ± 35 ms...
  • Page 65 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 55. Voltage control TR1ATCC and TR8ATCC Function Range or value Accuracy Transformer reactance (0.1–200.0)Ω, primary Time delay for lower command when fast step down mode is activated (1.0–100.0) s Voltage control set voltage (85.0–120.0)% of UBase...
  • Page 66 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 55. Voltage control TR1ATCC and TR8ATCC, continued Function Range or value Accuracy Time after position change before the value is accepted (1–60) s ± 0.2% or ± 200 ms whichever is greater Tap changer constant time-out (1–120) s...
  • Page 67: Scheme Communication

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Scheme communication Table 56. Scheme communication logic for distance or overcurrent protection ZCPSCH Function Range or value Accuracy Scheme type Intertrip Permissive Underreach Permissive Overreach Blocking Co-ordination time for blocking (0.000-60.000) s ±...
  • Page 68 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Logic Table 60. Tripping logic common 3-phase output SMPPTRC Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s ± 0.2% or ± 30 ms whichever is greater 3-pole trip delay (0.020-0.500) s...
  • Page 69 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 62. Configurable logic blocks Q/T Logic block Quantity with cycle time Range or value Accuracy medium normal ANDQT ORQT INVERTERQT XORQT SRMEMORYQT RSMEMORYQT TIMERSETQT (0.000-90000.000) s ± 0.5% ± 10 ms PULSETIMERQT (0.000-90000.000) s...
  • Page 70 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 65. Number of TEIGAPC instances Function Quantity with cycle time 3 ms 8 ms 100 ms TEIGAPC...
  • Page 71 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Monitoring Table 66. Measurements CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) × f ± 2.0 mHz Voltage (0.1-1.5) ×U ± 0.5% of U at U£U ± 0.5% of U at U > U Connected current (0.2-4.0) ×...
  • Page 72 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 70. Current sequence component measurement CMSQI Function Range or value Accuracy Current positive sequence, I1 (0.1–4.0) × I ± 0.3% of I at I ≤ 0.5 × I Three phase settings ±...
  • Page 73 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 74. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 100, first in - first out...
  • Page 74 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 78. Event recorder Function Value Buffer capacity Maximum number of events in disturbance report Maximum number of disturbance reports Resolution 1 ms Accuracy Depending on time synchronizing Table 79. Trip value recorder...
  • Page 75 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Metering Table 81. Pulse-counter logic PCFCNT Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value Table 82. Energy metering ETPMMTR...
  • Page 76: Station Communication

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Station communication Table 83. Communication protocols Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 60870–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0 Communication speed for the IEDs 300–19200 Bd...
  • Page 77 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 89. SLM – SPA/IEC 60870-5-103/DNP3 port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (1000m/3000ft m typically *)
  • Page 78: Remote Communication

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Remote communication Table 93. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fiber Graded-index Singlemode 9/125 µm Singlemode 9/125 µm...
  • Page 79: Connection System

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Hardware Table 94. Case Material Steel sheet Front plate Steel sheet profile with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) Table 95. Water and dust protection level according to IEC 60529...
  • Page 80 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Basic IED functions Table 99. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out Table 100. Time synchronization, time tagging...
  • Page 81 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 103. IRIG-B Quantity Rated value Number of channels IRIG-B Number of optical channels Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp – high level...
  • Page 82 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Inverse characteristic Table 104. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: k = (0.05-2.00) in steps of 0.01 ANSI/IEEE C37.112 , ± 2.0% or ± 40 ms whichever is greater æ...
  • Page 83 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 105. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: k = (0.05-2.00) in steps of 0.01 IEC 60255-151, ± 2.0% or ± 40 ms whichever is greater æ...
  • Page 84 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 107. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 85 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 108. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 86 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 109. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of ±5.0% or ±45 ms whichever is greater 0.01 æ...
  • Page 87: Ordering For Customized Ied

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 21. Ordering for customized IED Table 110. General guidelines Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions.
  • Page 88 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 115. Differential functions Function Function Ordering no Positi Available Selected Notes and identification rules 1Ph High impedance differential protection HZPDIF 1MRK005904-HA Table 116. Impedance protection siti Table 117. Current protection itio Table 118.
  • Page 89 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 122. Frequency functions Function Function Ordering no positi Available Selected Notes and identification rules Underfrequency protection SAPTUF 1MRK005914-AA Overfrequency protection SAPTOF 1MRK005914-BA Rate-of-change frequency protection SAPFRC 1MRK005914-CA Frequency time accumulation protection...
  • Page 90 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 130. Control functions Function Function Ordering no Positi Available Selected Notes and identification rules Synchrocheck, energizing check and synchronizing SESRSYN 1MRK005917-AA Rule: Can only be ordered with Apparatus control APC8/...
  • Page 91 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 134. Logic functions Function Function Ordering no Positi Available Selected Notes and identification rules Configurable logic blocks Q/T 1MRK005922-ML Extension logic package 1MRK005922-AX Table 135. Monitoring Position Table 136. Monitoring functions...
  • Page 92 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 141. Mounting selection Mounting details with IP40 of protection from the front Selection Notes and Rules No mounting kit included 19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 19"...
  • Page 93 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 144. Analog system selection Analog system Selection Notes and Rules No first TRM included Note: Only the same type of TRM (compression or ringlug) in the Compression terminals same terminal.
  • Page 94 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 146. Maximum quantity of I/O modules, with ring lug terminals, module limits se above Case sizes Maximum in case Possible locations for I/O modules with ringlug 1/1 x 19”, one (1) TRM P3, P5, P7, P9, P11, P13, P15 1/1 x 19”, two (2) TRM...
  • Page 95 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Table 147. Binary input/output module selection Binary input/output Selection Notes and Rules modules Slot position (rear view) Note! Max 3 positions in 1/2 rack, 8 in 3/4 rack with 1 TRM, 5 in 3/4...
  • Page 96 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 SOM Static output Note: SOM must not to be placed module, 12 outputs, in position nearest to NUM; 1/2 48-60 VDC case slot P5, 3/4 case 1 TRM slot P10, 3/4 case 2 TRM slot P7, 1/1...
  • Page 97: Ordering For Pre-Configured Ied

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 22. Ordering for pre-configured IED Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
  • Page 98 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Software options Notes and Rules No option All fields in the ordering form do not need to be filled in High impedance differential protections - 3 blocks Note: A02 only in A30/A31/B30,...
  • Page 99 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Mounting details with IP40 of protection from the front Notes and Rules No mounting kit included 19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 19" rack mounting kit for 3/4 x 19" case or 3xRGHS6 19"...
  • Page 100 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Binary input/output module, mA and time synchronizating Notes and Rules boards. For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used. Note: 1BIM and 1 BOM included in A30 and A31. 2 BIM and 1 BOM included in B30 and C30.
  • Page 101 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Remote end communication, DNP serial comm. and time synchronization modules Notes and Rules Slot position (rear view) Available slots in 1/2 case with 1 TRM █ █ █ █ Note: Max 1 LDCM in 1/2 case Available slots in 3/4 and 1/1 case with 1 TRM █...
  • Page 102: Ordering For Accessories

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 23. Ordering for Accessories Accessories GPS antenna and mounting details GPS antenna, including mounting kits Quantity: 1MRK 001 640-AA Cable for antenna, 20 m Quantity: 1MRK 001 665-AA Cable for antenna, 40 m...
  • Page 103 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 External resistor unit High impedance resistor unit 1-ph with resistor and voltage dependent resistor for 20-100V operating voltage Quantity: RK 795 101-MA High impedance resistor unit 3-ph with resistor and voltage dependent resistor for 20-100V...
  • Page 104 Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 User documentation Rule: Specify the number of printed manuals requested Application manual Quantity: 1MRK 511 310-UEN ANSI Quantity: 1MRK 511 310-UUS Technical manual Quantity: 1MRK 511 311-UEN ANSI Quantity: 1MRK 511 311-UUS...
  • Page 105: Reference Information

    Bay control REC670 2.0 1MRK511313-BEN C Product version: 2.0 Engineering manual, 670 series Quantity: 1MRK 511 308-UEN ANSI Quantity: 1MRK 511 308-UUS Cyber security guideline Quantity: 1MRK 511 309-UEN Reference information For our reference and statistics we would be pleased to be provided with the following application data:...
  • Page 107 For more information please contact: Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. ABB AB does ABB AB not accept any responsibility whatsoever for potential errors Substation Automation Products or possible lack of information in this document.