Daikin EWWD380BJYNN Service Manual
Daikin EWWD380BJYNN Service Manual

Daikin EWWD380BJYNN Service Manual

Water-cooled chillers
Table of Contents

Advertisement

Quick Links

ESIE07-06
Service Manual
EWWD-BJYNN
Water-cooled chillers

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EWWD380BJYNN and is the answer not in the manual?

Questions and answers

Summary of Contents for Daikin EWWD380BJYNN

  • Page 1 ESIE07-06 Service Manual EWWD-BJYNN Water-cooled chillers...
  • Page 3 ESIE07-06 Table of Contents Introduction About This Manual .................. i–i Characteristics ..................i–ii Safety Measures ..................i–iii Installation ....................i–iv Standard Accessories ................i–v Options (On Request) ................i–vi Nomenclatures ..................i–vii Part 1 System Outline General Outline What Is in This Chapter? ................ 1–3 Technical Specifications .................
  • Page 4: Table Of Contents

    ESIE07-06 Part 2 Functional Description Digital Controller What Is in This Chapter? ................. 2–3 General Description ................. 2–4 Main Control Features ................2–5 Component Description Digital Control............ 2–6 Controller Menus ..................2–33 Part 3 Troubleshooting Alarm What Is in This Chapter? ................. 3–3 Phase Monitoring Alarm ................
  • Page 5 ESIE07-06 Additional Checks for Troubleshooting What Is in This Chapter? ................ 3–39 PMFH Regulating Valve................3–40 Oil Flow Switch ..................3–42 Part 4 Commissioning What Is in This Chapter? ................ 4–3 ??? ......................4–4 Part 5 Maintenance Maintenance What Is in This Chapter ................5–3 Maintenance Schedule ................
  • Page 6 ESIE07-06 Table of Contents...
  • Page 7 ESIE07-06 Introduction Introduction About This Manual Target group Purpose of this manual Five parts This service manual consists of an introduction, five parts and an index: Part See page Part 1–System Outline 1–1 Part 2–Functional Description 2–1 Part 3–Troubleshooting 3–1 Part 4–Commissioning 4–1 Part 5–Maintenance...
  • Page 8 Introduction ESIE07-06 Characteristics...
  • Page 9: Safety Measures

    ESIE07-06 Introduction Safety Measures...
  • Page 10: Installation

    Introduction ESIE07-06 Installation...
  • Page 11: Standard Accessories

    ESIE07-06 Introduction Standard Accessories...
  • Page 12 Introduction ESIE07-06 Options (On Request)
  • Page 13 ESIE07-06 Introduction Nomenclatures...
  • Page 14 Introduction ESIE07-06 viii...
  • Page 15: System Outline

    ESIE07-06 Part 1 System Outline What is in this part? This part contains the following chapters: Chapter See page 1–General Outline 1–3 2–Piping Layout 1–11 3–Wiring Layouts 1–29 Part 1 – System Outline 1–1...
  • Page 16 ESIE07-06 1–2 Part 1 – System Outline...
  • Page 17: General Outline

    ESIE07-06 General Outline Part 1 General Outline What Is in This Chapter? Introduction This chapter contains the following information: ■ Technical specifications ■ Electrical specifications ■ Fouling factors ■ Operation limits ■ Outlook drawing Overview This chapter contains the following topics: Topic See page 1.2–Technical Specifications...
  • Page 18: Technical Specifications

    General Outline ESIE07-06 Technical Specifications EWWD EWWD EWWD EWWD EWWD EWWD EWWD EWWD 380BJY 460BJY 550BJY 750BJY 850BJY 900BJY C10BJ C11BJY Capacity Cooling Nominal 1050 (Eurovent con- ditions speci- fied in notes) Capacity steps stepless stepless stepless stepless stepless stepless stepless stepless 25-100...
  • Page 19 ESIE07-06 General Outline EWWD EWWD EWWD EWWD EWWD EWWD EWWD EWWD 380BJY 460BJY 550BJY 750BJY 850BJY 900BJY C10BJ C11BJY Compressor Type Semi-hermetic single screw compressor Refrigerant oil charge Model Quantity Speed 2950 2950 2950 2950 2950 2950 2950 2950 Sound level Sound pres- Cooling 81,5...
  • Page 20: Electrical Specifications

    General Outline ESIE07-06 Electrical Specifications EWWD EWWD EWWD EWWD EWWD EWWD EWWD EWWD 380BJY 460BJY 550BJY 750BJY 850BJY 900BJY C10BJ C11BJY Power supply Name Phase Frequency Voltage Voltage toler- Minimum -10% ance Maximum +10% Phase tolerance Minimum Maximum Unit Starting current Nominal running current cool- Maximum running current Max unit current for wires siz-...
  • Page 21: Fouling Factors

    ESIE07-06 General Outline Fouling Factors Evaporator fouling factors Fouling factors Cooling capacity Power input correc- COP correction fac- m²°C / kW correction factor tion factor 0,0176 1,000 1,000 1,000 0,0440 0,978 0,986 0,992 0,0880 0,957 0,974 0,983 0,1320 0,938 0,962 0,975 Condenser fouling factors...
  • Page 22: Operation Limits

    Remark ■ If there is no optimising of the refrigerant charge when changing the set point Daikin Europe NV cannot be held responsible for possible damage on the unit. ■ If the unit is not operating within the operation limits indicated in above picture, Daikin Europe NV cannot be held responsible for possible damage on the unit.
  • Page 23: Outlook Drawing

    ESIE07-06 General Outline Outlook Drawing Example of the outlook drawing for a flooded evaporator. All outlook drawings can be found on the passdoor.macquay.it EWWDC11BJYNN view “A” Unit weight Water cap. Shipping Operating Liters 6605 7170 Control box “Victaulic” coupling-furnished Connecting pipe-furnished view “A”...
  • Page 24 General Outline ESIE07-06 1–10 Part 1 – System Outline...
  • Page 25: Piping Layout

    ESIE07-06 Piping Layout Part 1 Piping Layout What Is in This Chapter? Introduction In this chapter a brief explanation will be given of all the refrigerant parts used in this unit. Overview This chapter contains the following topics: Topic See page 2.2–Functional Diagram 1–12 2.3–Refrigerant Description...
  • Page 26: Functional Diagram

    Piping Layout ESIE07-06 Functional Diagram Typical refrigerant circuit COMPRESSOR COMPRESSOR SAFETY VALVE EVAPORATOR SAFETY VALVE FLOAT WATER OUTLET VALVE CONDENSER WATER INLET LOW PRESSURE SWITCH F12 - 22 LP HIGH PRESSURE SWITCH F13 - 23 HP OIL LEVEL READOUT OLS1 - 2 LIQUID SOLENOID VALVE OIL INJECTION SOLENOID VALVE Y3 - 4...
  • Page 27: Refrigerant Description

    ESIE07-06 Piping Layout Refrigerant Description The low temperature refrigerant gas coming form the evaporator to the compressor cools the electric motor. Later it is compressed and during this phase the refrigerant is mixed up to the oil coming from the separator. The high-pressure oil refrigerant mixture is conveyed inside the oil separator of centrifugal high efficiency type.
  • Page 28: Evaporator

    Piping Layout ESIE07-06 Evaporator The evaporator is flooded shell-and-tube with the refrigerant out the tubes and the water inside them. Normally no maintenance and service operation is required. When it is necessary to replace a tube it is easy to remove the old one. 1–14 Part 1 –...
  • Page 29: Condenser

    ESIE07-06 Piping Layout Condenser The condenser is shell-and-tube with the refrigerant out the tubes and the water inside them. The condenser tubes are externally finned and expanded on the tube plate. All units have an integrated subcooling in the condenser also equipped with a safety valve. If required it is possible to remove and replace the tubes.
  • Page 30: Liquid Control Valve And Float Valve

    Piping Layout ESIE07-06 Liquid Control Valve and Float Valve The Danfoss SV(H) float valve + PMFH main valve + pilot solenoid valve combination is used to maintain a constant liquid level within a shell and tube condenser on the high pressure of the system. The float valve is attached to the vessel by branch connections at a point corresponding to the desired liquid level.
  • Page 31 ESIE07-06 Piping Layout When the liquid level within the vessel rises, the float within the SV(H) float chamber also rises, raising the float arm. The float arm actuates a needle valve. As the float rises, the needle valve is withdrawn from its seat and opens the float valve orifice, relieving pilot pressure PS through the orifice.
  • Page 32: Refrigerant Level Sensor

    Piping Layout ESIE07-06 Refrigerant Level Sensor The level sensor includes a floating element checking the refrigerant level inside the condenser and controlling the expansion valve indirectly monitoring the refrigerant flow. A regulating valve, installed on the sensor flange, allows to level stabilizing. This valve is factory set during the test and normally does not require any further adjustment on the field unless on particularly unstable plant where an additional regulation must be operated from qualified personnel only.
  • Page 33: Compressor

    ESIE07-06 Piping Layout Compressor The compressor is controlled by a special motor, installed on the end of the main driving shaft. It consists of two screwed cast iron element: the main one includes all moving parts as the main rotor and the two satellites, the second element includes the three-phases 2-poles electric motor.
  • Page 34: Compressor Operation

    Piping Layout ESIE07-06 Compressor Operation With the single-screw compressor the refrigerant suction, compression and discharge process is operated by a continue flow for each satellite. During this operation the volume is progressively reduced compressing the refrigerant. After the compression, the gas is discharged through the ports properly designed.
  • Page 35: Capacity Control

    ESIE07-06 Piping Layout 2.10 Capacity Control Capacity control The compressors are provided with infinitely variable capacity control as standard. This system allows mechanism unit load to be equal to plant demand. Stepless capacity control is permitted by a pair of sliding valves, fitted in the compressor, one for each half of the symmetrical compression process.
  • Page 36 Piping Layout ESIE07-06 SOLENOID SOLENOID CAPACITY CONTROL ACTION VALVE A VALVE B Load compressor Oil is vented from the capacity control cylinder. The De-energised action of the suction/discharge differential pressure on Energised (open) (close) the slide/piston assembly overcomes the force of the unloading spring and moves the slide valve towards the maximum load position.
  • Page 37: Oil System Control

    ESIE07-06 Piping Layout 2.11 Oil System Control Each screw compressor is connected to a tank (oil separator) separating and collecting the oil from discharge gas. The discharge gas pressure pushes the oil into the compressor where, after passing through a high capacity filter, it is conveyed to the main injection port for compressor seal and lubrication of all moving parts.
  • Page 38: Lubrication Oils

    Piping Layout ESIE07-06 2.12 Lubrication Oils Besides lubricating the bearing and other moving parts, the oil has the equally important task of granting the seal during the compression, improving the efficiency. Therefore more oil is injected than is required for lubrication alone. Lubricating oil approved by McQuay is mentioned on the compressor label.
  • Page 39: Liquid Injection

    ESIE07-06 Piping Layout 2.13 Liquid Injection The liquid injection is used to cool down the compressor when the discharge temperature becomes higher than 85°C. All units produced from August 2009 have this control standard on the unit. This liquid injection is optional for units manufactured before August 2009. Oil Injection Discharge Line...
  • Page 40: Oil Recovery System

    Piping Layout ESIE07-06 2.14 Oil Recovery System Each compressor includes a system to recover the oil accumulated inside the evaporator during the normal operation. This system consists of a set pump able to collect continuously all the oil from the evaporator preventing from the accumulation due to the low speed refrigerant gas.
  • Page 41: Heaters

    ESIE07-06 Piping Layout 2.15 Heaters The compressor and the oil separator are supplied with resistances for heating the compressor and the oil inside the separator, to prevent the migration and the condensation of the refrigerant during shutdown unit. The auxiliary circuit should be energised for at least 12 hours prior to start up compressor. The compressor and oil temperatures should be sufficiently high before starting the system lowering at the minimum problems of lubrication and liquid blows.
  • Page 42 Piping Layout ESIE07-06 1–28 Part 1 – System Outline...
  • Page 43: Wiring Layouts

    ESIE07-06 Wiring Layouts Part 1 Wiring Layouts What Is in This Chapter? Introduction This chapter gives an example of a wiring diagram. All wiring diagrams are available on the passdoor.macquay.it Overview This chapter contains the following topics: Topic See page 3.2–Example Wiring Diagram 1–30 Part 1 –...
  • Page 44: Example Wiring Diagram

    Wiring Layouts ESIE07-06 Example Wiring Diagram 1–30 Part 1 – System Outline...
  • Page 45: Functional Description

    ESIE07-06 Part 2 Functional Description What is in this part? This part contains the following chapters: Chapter See page 1–Digital Controller 2–3 Part 2 – Functional Description 2–1...
  • Page 46 ESIE07-06 2–2 Part 2 – Functional Description...
  • Page 47: Digital Controller

    ESIE07-06 Digital Controller Part 2 Digital Controller What Is in This Chapter? Introduction This chapter contains information on the menus and the functions used to control the system. Understanding these functions is vital when diagnosing a malfunction that is related to the functional control.
  • Page 48: General Description

    Digital Controller ESIE07-06 General Description The Microtech II C Plus control panel contains a microprocessor based controller which provides all monitoring and control functions required for the safe, efficient operation of the Chiller. The operator can monitor all operating conditions by using the panel's built in 4 line by 20 character keypad/display or by using an IBM compatible computer running MicroPlant monitor software release 2.0 and later.
  • Page 49: Main Control Features

    ESIE07-06 Digital Controller Main Control Features ■ Control of evaporator outlet or condenser outlet or both temperature. ■ Control of leaving water within a ± 0,1°C (with a steady-state load). ■ Management of sudden load reduction up to 50% with max 3°C controlled temperature obscillation.
  • Page 50: Component Description Digital Control

    Digital Controller ESIE07-06 Component Description Digital Control Overview Topic See page 1.4.1–Control Panel 2–7 1.4.2–Keypad Keys 2–8 1.4.3–Keypad Keys and Their Functions 2–9 1.4.4–Screen Categories 2–11 1.4.5–Adjusting Contrast of the Display 2–12 1.4.6–Network Addresses 2–13 1.4.7–Layout Microprocessor Board 2–14 1.4.8–Layout Double Circuit 2–15 1.4.9–Explanation Connectors Microprocessor Board 2–16...
  • Page 51: Control Panel

    ESIE07-06 Digital Controller 1.4.1 Control Panel Part 2 – Functional Description 2–7...
  • Page 52: Keypad Keys

    Digital Controller ESIE07-06 1.4.2 Keypad Keys 2–8 Part 2 – Functional Description...
  • Page 53 ESIE07-06 Digital Controller 1.4.3 Keypad Keys and Their Functions With this button it is possible to set the following parameters: ■ Setpoint limits (cooling and/or heating) ■ Minimum / maximum set point (cooling and/or heating) ■ Regulation parameters ■ Startup and shutdown parameters ■...
  • Page 54 Digital Controller ESIE07-06 It allows the changeover between chiller to heat pump (only if enabled). It allows the changeover between heat pump to chiller (only if enabled). Key On/Off unit. It indicates the presence of possible anomalies and their causes. It allows the passage to the previous display screen.
  • Page 55 ESIE07-06 Digital Controller 1.4.4 Screen Categories Using the keypad you can access the different menus of the program. In particular there are 9 screen categories, shortly introduced in the following table with the keys to use to access them and with the type of operation they allow.
  • Page 56 Digital Controller ESIE07-06 1.4.5 Adjusting Contrast of the Display When you use a remote controller it is possible to adjust the contrast. At the back of the upper left corner of the remote controller you will find a hole where you can adjust the brightness of the remote controller with a small screw driver.
  • Page 57: Network Addresses

    ESIE07-06 Digital Controller 1.4.6 Network Addresses To get the correct functionality of the net system PLAN, it is necessary to address correctly the microprocessor boards and the terminal. This components have, as previously described, a series of microswitches that must be set up as specified in the following chart. Net component Microswitches PLAN component...
  • Page 58 Digital Controller ESIE07-06 1.4.7 Layout Microprocessor Board Power supply G (+), G0 (-) Status LED Fuse 250 Vac Universal analog inputs (NTC, 0/1 V, 0/10 V, 0/20 mA, 4/20 mA) Passive analog inputs (NTC, PT1000, On- off) Analog outputs 0/10 V 24 Vac/Vdc Digital inputs 230 Vac or 24 Vac/Vdc Digital inputs Synoptic terminal connection...
  • Page 59 ESIE07-06 Digital Controller 1.4.8 Layout Double Circuit RXT - RXT + PCO 1 PCO 2 address 01 address 02 LOCAL DISPLAY address 16 remote display address 17 Part 2 – Functional Description 2–15...
  • Page 60 Digital Controller ESIE07-06 1.4.9 Explanation Connectors Microprocessor Board Overview Topic See page 1.4.9.1–Explanation Connectors Single Circuit Star / Delta 2–17 1.4.9.2–Explanation Connectors Single Circuit Softstarter 2–20 1.4.9.3–Explanation Connectors Double Circuit Star / Delta 2–23 1.4.9.4–Explanation Connectors Double Circuit Softstarter 2–28 2–16 Part 2 –...
  • Page 61 ESIE07-06 Digital Controller 1.4.9.1 Explanation Connectors Single Circuit Star / Delta Block Connection Wiring symbol Description 24 V power supply microprocessor board Low pressure transmitter Oil pressure transmitter Compressor load transmitter Ground terminal + VDC Power supply Discharge sensor Leaving condenser water sensor Power supply Power supply 2 way water valve installed outlet condenser...
  • Page 62 Digital Controller ESIE07-06 ID13H Not used ID13 Not used IDC13 Not used ID14 Not used ID14H Not used Synoptic terminal connector Terminal connector for display and download software RX/ TX- RX / TX+ Plan connection Line contactor relay Not used Not used Power supply Power supply 230 V...
  • Page 63 ESIE07-06 Digital Controller NO14 Remote alarm (230 V / max 8 amp) Remote alarm (230 V / max 8 amp) NC14 Not used NO15 Liquid line solenoid valve Power supply NC15 Not used Part 2 – Functional Description 2–19...
  • Page 64 Digital Controller ESIE07-06 1.4.9.2 Explanation Connectors Single Circuit Softstarter Block Connection Wiring symbol Description 24 V power supply microprocessor board Low pressure transmitter Oil pressure transmitter Compressor load transmitter Ground terminal + VDC Power supply Discharge sensor Leaving Condenser water sensor Power supply Power supply 2 way water valve installed outlet condenser...
  • Page 65 ESIE07-06 Digital Controller ID13H Not used ID13 Not used IDC13 Not used ID14 Not used ID14H Not used Synoptic terminal connector Terminal connector for display and download software RX/ TX- RX / TX+ Plan connection Line contactor relay Not used Not used Power supply Power supply 230 V...
  • Page 66 Digital Controller ESIE07-06 NO14 Remote alarm (230 V / max 8 amp) Remote alarm (230 V / max 8 amp) NC14 Not used NO15 Liquid line solenoid valve Power supply NC15 Not used 2–22 Part 2 – Functional Description...
  • Page 67 ESIE07-06 Digital Controller 1.4.9.3 Explanation Connectors Double Circuit Star / Delta Circuit 1 Block Connection Wiring symbol Description 24 V power supply microprocessor board Low pressure transmitter Oil pressure transmitter circuit 1 Compressor load transmitter circuit 1 Ground terminal + VDC Power supply Discharge sensor circuit 1 Leaving condenser water sensor...
  • Page 68 Digital Controller ESIE07-06 ID13H Not used ID13 Not used IDC13 Not used ID14 Not used ID14H Not used Synoptic terminal connector Terminal connector for display and download software RX/ TX- RX / TX+ Plan connection Line contactor relay circuit 1 Not used Not used Power supply...
  • Page 69 ESIE07-06 Digital Controller NO14 Remote alarm (230 V / max 8 amp) Remote alarm (230 V / max 8 amp) NC14 Not used NO15 Liquid line solenoid valve circuit 1 Power supply NC15 Not used Circuit 2 Block Connection Wiring symbol Description 24 V power supply microprocessor board Not used...
  • Page 70 Digital Controller ESIE07-06 Not used ID10 Not used ID11 Not used ID12 Not used IDC9 Power supply 24 V ID13H Not used ID13 Not used IDC13 Not used ID14 Not used ID14H Not used Synoptic terminal connector Not used RX/ TX- RX / TX+ Plan connection Line contactor relay circuit 2...
  • Page 71 ESIE07-06 Digital Controller Not used Not used Not used BC10 Not used NO14 Not used Not used NC14 Not used NO15 Not used Not used NC15 Not used Part 2 – Functional Description 2–27...
  • Page 72 Digital Controller ESIE07-06 1.4.9.4 Explanation Connectors Double Circuit Softstarter Circuit 1 Block Connection Wiring symbol Description 24 V power supply microprocessor board Low pressure transmitter circuit 1 Oil pressure transmitter circuit 1 Compressor load transmitter circuit 1 Ground terminal + VDC Power supply Discharge sensor circuit 1 Leaving condenser water sensor...
  • Page 73 ESIE07-06 Digital Controller ID13H Not used ID13 Not used IDC13 Not used ID14 Not used ID14H Not used Synoptic terminal connector Terminal connector for display and download software RX/ TX- RX / TX+ Plan connection Line contactor relay circuit 1 Not used Not used Power supply...
  • Page 74 Digital Controller ESIE07-06 NO14 Remote alarm (230 V / max 8 amp) Remote alarm (230 V / max 8 amp) NC14 Not used NO15 Liquid line solenoid valve circuit 1 Power supply NC15 Not used Circuit 2 Block Connection Wiring symbol Description 24 V power supply microprocessor board Not used...
  • Page 75 ESIE07-06 Digital Controller Not used ID10 Not used ID11 Not used ID12 Not used IDC9 Power supply 24 V ID13H Not used ID13 Not used IDC13 Not used ID14 Not used ID14H Not used Synoptic terminal connector Not used RX/ TX- RX / TX+ Plan connection Line contactor relay circuit 2...
  • Page 76 Digital Controller ESIE07-06 Not used Not used Not used BC10 Not used NO14 Not used Not used NC14 Not used NO15 Not used Not used NC15 Not used 2–32 Part 2 – Functional Description...
  • Page 77: Controller Menus

    ESIE07-06 Digital Controller Controller Menus Overview Topic See page 1.5.1–Read Out Menu 2–34 1.5.2–Service Menu 2–37 1.5.3–Set Point Menu 2–51 1.5.4–User Menu 2–52 1.5.5–Maintenance Menu 2–56 1.5.6–Auxiliary Maintenance Menu 2–58 1.5.7–Input / Output Menu 2–61 Part 2 – Functional Description 2–33...
  • Page 78: Read Out Menu

    Digital Controller ESIE07-06 1.5.1 Read Out Menu Unit status 00/00/00 00:00 Unit Status: Cooling Staging 0000 Stp Source: Local ■ Information on the status of the unit ■ White rectangle: Circuit / unit switch OFF ■ Black rectangle: Circuit / unit switch ON ■...
  • Page 79 ESIE07-06 Digital Controller Approach values Press Cond 00.0 barg Press Evap 00.0 barg Press. Ratio 00.0 Low and high pressure value of the unit. For a double circuit there is only one low and high pressure point. Details refer to the piping diagram of the unit. The pressure ratio is used to guarantee a good operation of the unit.
  • Page 80 Digital Controller ESIE07-06 Detail compressor Staging Down Staging Staging Fixed Compressor For each compressor above information is available. Cooling tower Cooling tower Available steps Active steps Information available if steps selected. Available steps to control the head pressure. Cooling tower Cooling tower Valve position Information available if valve selected.
  • Page 81: Service Menu

    ESIE07-06 Digital Controller 1.5.2 Service Menu Introduction To enter this menu a password is required. We strongly advice you not to give the password to unauthorised persons. Manufactory password Insert manufacturer password 0000 To enter this menu a password is required. To enter the menu the unit must be switch OFF to avoid possible damage.
  • Page 82 Digital Controller ESIE07-06 Analogue input Description Evaporator pressure transducer Oil pressure transducer Capacity sliding valve Delivery (discharge temperature) Leaving water condenser Extern set point signal (4 – 20 mA) Demand limit (4 – 20 mA) High pressure transducer Entering water evaporator Leaving water evaporator Low pressure probe configuration...
  • Page 83 ESIE07-06 Digital Controller The PID controller receives signals from sensors and computes corrective action to the actuators from a computation based on the error (proportional), the sum of all previous errors (integral) and the rate of change of the error (derivative). Number of pulses Number of pulses to load comp.
  • Page 84 Digital Controller ESIE07-06 Reload compressor Last comp. reload at comp. stop When both compressors are at minimum load the compressor with the lowest capacity step will stop and the other compressor will reload to a capacity step equal to the sum of the minimum capacity steps of both compressors.
  • Page 85 ESIE07-06 Digital Controller Limitations Cond. P. hold 00.0 00.0 Cond. P. down 00.0 Evap. P. hold Evap. P. down 00.0 Condenser pressure hold: If the high pressure reaches the hold value, the compressor remains at the same capacity steps. Condenser pressure down: If the high pressure is above the high pressure hold value, the compressor starts unloading.
  • Page 86 Digital Controller ESIE07-06 Freeze up prevention Freeze prevent 00.0 °C Setpoint Diff. 00.0 °C Outlet Temp. possible for the compressor to upload 4°C possible to reset Anti-freeze Alarm Freeze Prevention 3°C Setpoint Freeze up prevention (load down) Anti-freeze Alarm 2°C Setpoint Anti-freeze Alarm (shutdown)
  • Page 87 ESIE07-06 Digital Controller Tower control steps Tower steps Quantity of capacity steps for the tower control. Maximum steps is 3. Tower control Tower control Type : Steps Input : Temperature If steps are selected: Fan step 1: Set point + (differential / 3) Fan step 2: Set point + ((differential*2)/3) Fan step 3: Set point + differential 1°...
  • Page 88 Digital Controller ESIE07-06 Label Tower control Type : Steps Input : Pressure ratio Tower control Pressure ratio When selecting the input as pressure ratio, the speed of the tower control can be controlled. When the pressure ratio is at minimum set point there is no tower control. Fan step 1: Set point + (PR max –...
  • Page 89 ESIE07-06 Digital Controller Flow switch control Enable Evaporator flow alarm Enable condensator flow alarm There is a possibility to enable or disable the flow control on evaporator and or condenser. We strongly recommend NOT to disable these inputs. Evaporator flow alarm Evaporat.
  • Page 90 Digital Controller ESIE07-06 Phase and Oil heating alarm Enable phase alarm Enable Oil Heating Control From the factory both setting are set to Y. Phase alarm: Check if the sequence of the phases is correct (details refer to commissioning). Oil Heating: When the discharge superheat is below 5°C the compressor will not start and “Oil heating” will be displayed on the screen.
  • Page 91 ESIE07-06 Digital Controller Pressure ratio alarm Pressure ratio alarm Setpoints Min Load Max Load Pressure ratio 25% cap. 100% cap. The pressure ratio is related to the load of the unit. This control is incorporated to guarantee an optimum oil circulation in the circuit. Formula to calculate the pressure ratio: discharge pressure (Abs) pressure ratio =...
  • Page 92 Digital Controller ESIE07-06 Principal: The Level switch uses light reflecting from a conical glass prism as a means of detecting the absence of a fluid at this level of the glass cone. When no fluid covers the lower half of the cone infra-red light from the module reflects from the mirror-like inner surface of the cone back to a light detector signalling the electronic module to switch.
  • Page 93 ESIE07-06 Digital Controller Differential: If the leaving water of the evaporator increases above the set point + the differential, safety can be resetted. Liquid injection Liquid injection Setpoint 000.0 °C Diff. 00.0 °C Set point: If the oil temperature become higher than the set point, the liquid line solenoid valve is activated.
  • Page 94 Digital Controller ESIE07-06 On communication loss On comm. loss Local This control is only used in the CSC mode. Local: If there is a communication loss between the different units, the units starts working locally. Alarm: If there is no communication, all units connected into the network goes into failure. Communication speed Supervisor Com.
  • Page 95: Set Point Menu

    When changing the set point in cooling or heating or pursuit, the refrigerant charged must be optimised. ■ If there is no optimising of the refrigerant charge when changing the set point Daikin Europe NV cannot be held responsible for possible damage on the unit. Actual set point...
  • Page 96 Digital Controller ESIE07-06 1.5.4 User Menu Introduction To enter the user menu, a password is required. We strongly advice not to give this password to unauthorized persons. Set point limits Cooling temperature setpoint limits 00.0 °C High 00.0 °C For a cooling only unit the installer can select the lowest and highest allowable set point. For a heat pump and pursuit unit installer can do the same settings for the heating mode.
  • Page 97 When using double set point, a optimising of the refrigerant is required after every change of the set point. ■ If there is no optimising of the refrigerant charge when changing the set point Daikin Europe NV cannot be held responsible for possible damage on the unit. Enable softload...
  • Page 98 Digital Controller ESIE07-06 SoftLoad Max Stage Rem. Time Max Time High chilled water temperature En high ChW Temp °C Temp. Setp. 00.0 Max Stage Default High chilled water temperature is selected to NO. Temperature set point: This temperature can be programmed by the installer. Maximum stage: Maximum allowable capacity of the unit if the function is programmed.
  • Page 99 ESIE07-06 Digital Controller Lag timer pump Delay on switching the main pump off When the unit is switching OFF, the main pump keeps on running for the programmed time. Remote signals Digital input remote on/off Digital input remote Summer/Winter There is a possibility to control the unit from a distance. Remote ON / OFF: To enable this function following actions need to be done: 1.
  • Page 100: Maintenance Menu

    Digital Controller ESIE07-06 1.5.5 Maintenance Menu Introduction In this menu you can only read values. Running hours pump Hour counter 000000 Pump Evap. Pump cond. 000000 Indication of the total running hours of the condenser and evaporator pumps. Running hours compressor Compressor 000000...
  • Page 101 ESIE07-06 Digital Controller PID request Global PID request Load Unload Standby Indication of Load up / unloading or stand by is requested. This is used for the cooling and heating mode. Part 2 – Functional Description 2–57...
  • Page 102 Digital Controller ESIE07-06 1.5.6 Auxiliary Maintenance Menu Introduction This menu can be found in the maintenance menu. A password is required to enter this additional menu. Setting hour counter evaporator Evap. pump h. count. Threshold 000x1000 Reset Adjust 000000 Maintenance menu for the evaporator pump. Threshold: Installer can program after how many hours there should be maintenance on the pump.
  • Page 103 ESIE07-06 Digital Controller Compressor starts counter Comp. Starts Reset Adjust 00000 Possible to reset the amount of compressor starts. This can be done for both compressors. Enable digital input Enable digital in U: t Filter Delay time Offset Inputs probes offset Possible to program an offset on the probes.
  • Page 104 Digital Controller ESIE07-06 Calibration capacity sensor Adjustable comp. Load sensor HS_205 Comp. Type Every screw compressor of the Frame 4 series can be equipped with a sensor that detects the position of the capacity control slide. The position data is sent to the controller through a 4-20 mA proportional signal.
  • Page 105: Input / Output Menu

    ESIE07-06 Digital Controller 1.5.7 Input / Output Menu Introduction Using this menu you can read the status of the digital in-and outputs and the analogue. Software version CODE: Flooded .000P2 00/00/00 Indication of software version and date the software was produced. Digital input and output Digital inputs...
  • Page 106 Digital Controller ESIE07-06 Digital outputs COMPRESSOR CARD 1 COMPRESSOR CARD 2 Line contactor, compressor #1 Line contactor, compressor #2 Star contactor, compressor #1 Star contactor, compressor #2 Delta contactor, compressor #1 Delta contactor, compressor #2 Liquid injection, compressor #1 Liquid injection, compressor #2 Load solenoid, compressor #1 Load solenoid, compressor #2 Unload solenoid, compressor #1...
  • Page 107 ESIE07-06 Digital Controller Analogue inputs Analog inputs: B10: Lvg Evap 00.0 °C Actual operation values of the unit. Analogue outputs Analog outputs 00.0 V 00.0 V COMPRESSOR CARD 1 COMPRESSOR CARD 2 Valve output, condensation control ...... Valve output, evaporation control (only HP ......
  • Page 108 Digital Controller ESIE07-06 It is so, possible to find not the sensors or, if this exists, they can be of 2 different types. 1. Sensor with Reset Button: Such sensor incorporates on the head, near to the electric connection, a reset button protected by a circular hood (see figure below).
  • Page 109: Troubleshooting

    ESIE07-06 Part 3 Troubleshooting What is in this part? This part contains the following chapters: Chapter See page 1–Alarm 3–3 2–Additional Checks for Troubleshooting 3–39 Part 3 – Troubleshooting 3–1...
  • Page 110 ESIE07-06 3–2 Part 3 – Troubleshooting...
  • Page 111: Alarm

    ESIE07-06 Alarm Part 3 Alarm What Is in This Chapter? Introduction Overview This chapter contains the following topics: Topic See page 1.2–Phase Monitoring Alarm 3–5 1.3–Anti Freeze Alarm 3–7 1.4–Low Evaporator Pressure Alarm 3–8 1.5–Evaporator Flow Alarm 3–10 1.6–Condenser Flow Alarm 3–11 1.7–High Discharge Temperature Alarm 3–12...
  • Page 112 Alarm ESIE07-06 Topic See page 1.27–Condenser Pump Maintenance 3–32 1.28–Compressor Maintenance 3–33 1.29–Evaporator Pump Maintenance 3–34 1.30–Unit 1 Offline 3–35 1.31–Unit 2 Offline 3–36 1.32–Clock Card Alarm 3–37 3–4 Part 3 – Troubleshooting...
  • Page 113: Phase Monitoring Alarm

    ESIE07-06 Alarm Phase Monitoring Alarm Symbol Indication on Phase Monitor Alarm screen Digital input Default setting Safety Default Value Reason 1. Incorrect sequence of the phases. 2. Failure of one of the phases. 3. Incorrect power supply. Countermeasure 1. Change 2 phases. 2.
  • Page 114 Alarm ESIE07-06 Program procedure Three dashes (– – – V) appear in the upper line of the display instead of the current voltage value, if the value falls outside the allowed supply voltage limits. 3–6 Part 3 – Troubleshooting...
  • Page 115: Anti Freeze Alarm

    ESIE07-06 Alarm Anti Freeze Alarm Symbol Indication on Lvg Water Freeze Alarm screen Digital input Default setting Safety Default Value Reason 1. Alarm during operation ■ Water flow in the system too low ■ Incorrect setting of the freeze up setting alarm ■...
  • Page 116: Low Evaporator Pressure Alarm

    Alarm ESIE07-06 Low Evaporator Pressure Alarm Symbol Indication on Low Evap Pressure Alarm screen Analogue input Default setting Safety Default Value Reason 1. Shortage of refrigerant. 2. Liquid valve closed. 3. Incorrect setting of the spindle of the floating valve: If this spindle is almost closed, the unit will go into low pressure.
  • Page 117 ESIE07-06 Alarm 2. Liquid stop valve closed: ■ Open liquid line solenoid valve. 3. Incorrect setting of the spindle of the floating valve. ■ Part 3 – Troubleshooting 3–9...
  • Page 118: Evaporator Flow Alarm

    Alarm ESIE07-06 Evaporator Flow Alarm Symbol Indication on Loss Evap Water Flow Alarm screen Digital input Default setting Safety Default Value Reason 1. No flow. 2. Not enough flow. 3. Incorrect installation of the flow switch. 4. Incorrect operation of the flow switch. Countermeasure 1.
  • Page 119: Condenser Flow Alarm

    ESIE07-06 Alarm Condenser Flow Alarm Symbol Indication on Loss Cond Water Flow Alarm screen Digital input Default setting Safety Default Value Reason 1. No flow. 2. Not enough flow. 3. Incorrect installation of the flow switch. 4. Incorrect operation of the flow switch. Countermeasure 1.
  • Page 120: High Discharge Temperature Alarm

    Alarm ESIE07-06 High Discharge Temperature Alarm Symbol Indication on High Discharge Temp Alarm screen Digital input Default setting Safety Default Value Reason 1. Lack of refrigerant. 2. No liquid injection when discharge temperature is higher than 85°C. 3. Incorrect discharge temperature sensor. Countermeasure 1.
  • Page 121: Transition Fault

    ESIE07-06 Alarm Transition Fault Symbol Indication on Failed Trans Start Alarm screen Digital input Reason The starting sequence of the contactors could not be completed. Countermeasure Check the wiring between the contactors. When testing the sequence it is better to do a dry run (compressors disconnected). Part 3 –...
  • Page 122: Low Oil Pressure Alarm

    Alarm ESIE07-06 Low Oil Pressure Alarm Symbol Indication on screen Digital input Default setting Safety Default Value Reason 1. Incorrect operation of the injector. 2. Unit is operating out of the operation range. 3. ??? Countermeasure 3–14 Part 3 – Troubleshooting...
  • Page 123: Mechanical Low Pressure Alarm

    ESIE07-06 Alarm 1.10 Mechanical Low Pressure Alarm Symbol Indication on Low Mech. Pressure Alarm screen Digital input Default setting Safety Default Value Reason When the low pressure drops below the set point of the mechanical low pressure switch, the unit will generate a low pressure alarm.
  • Page 124: High Oil Pressure Differential Alarm

    Alarm ESIE07-06 1.11 High Oil Pressure Differential Alarm Symbol Indication on High Oil Press Diff Alarm screen Digital input Default setting Safety Default Value Reason This problem is related to a big pressure drop across the oil filter or incorrect oil pressure sensor or high pressure sensor.
  • Page 125: Mechanical High Pressure Alarm

    ESIE07-06 Alarm 1.12 Mechanical High Pressure Alarm Symbol Indication on High Mech Pressure Alarm screen Digital input Default setting Safety Default Value Reason When the high pressure drops above the set point of the mechanical high pressure switch, the unit will generate a low pressure alarm.
  • Page 126: Oil Level Alarm

    Alarm ESIE07-06 1.13 Oil Level Alarm Symbol Indication on No Oil Run Alarm screen Digital input Default setting Safety Default Value Reason This alarm is generated if the oil flow is too low. 1. Part damage. 2. Overcharge of refrigerant. 3.
  • Page 127: Compressor Overload

    ESIE07-06 Alarm 1.14 Compressor Overload Symbol Indication on Compressor overload screen Digital input Default setting Safety Default Value Reason The internal clixon of the compressor can be activated due to the following reasons: 1. Shortage of refrigerant. 2. No liquid injection. 3.
  • Page 128: Low Pressure Ratio Alarm

    Alarm ESIE07-06 1.15 Low Pressure Ratio Alarm Symbol Indication on Low Pressure Ratio Alarm screen Digital input Default setting Safety Default Value Reason 1. Unit is operating out of the operation limits. Countermeasure The pressure ratio is related to the load of the unit. This control is incorporated to guarantee an optimum oil circulation in the circuit.
  • Page 129: High Pressure Sensor Alarm

    ESIE07-06 Alarm 1.16 High Pressure Sensor Alarm Symbol Reason 1. Wrong or poor electrical connection. 2. Incorrect operation of the high pressure transducer. Countermeasure 1. Rectify the wiring. 2. Verify the function of the transducer. (Procedure refers to …..) Part 3 – Troubleshooting 3–21...
  • Page 130: Low Pressure Sensor Alarm

    Alarm ESIE07-06 1.17 Low Pressure Sensor Alarm Symbol Reason 1. Wrong or poor electrical connection. 2. Incorrect operation of the low pressure transducer. Countermeasure 1. Rectify the wiring. 2. Verify the function of the transducer. (Procedure refers to …..) 3–22 Part 3 –...
  • Page 131: Oil Pressure Sensor Alarm

    ESIE07-06 Alarm 1.18 Oil Pressure Sensor Alarm Symbol Reason 1. Wrong or poor electrical connection. 2. Incorrect operation of the low pressure transducer. Countermeasure 1. Rectify the wiring. 2. Verify the function of the transducer. (Procedure refers to …..) Part 3 – Troubleshooting 3–23...
  • Page 132: Load Sensor Fault

    Alarm ESIE07-06 1.19 Load Sensor Fault Symbol Reason 1. Possible bad electrical connection of the sensor. 2. Incorrect operation of the capacity sensor of the compressor. Countermeasure 3–24 Part 3 – Troubleshooting...
  • Page 133: Discharge Temperature Sensor Fault

    ESIE07-06 Alarm 1.20 Discharge Temperature Sensor Fault Symbol Indication on Bad Disch Temp Sensor screen Reason Possible bad electrical connection of the sensor. Countermeasure Check the electrical connections of the sensor. Part 3 – Troubleshooting 3–25...
  • Page 134: Condenser Temperature Sensor Fault

    Alarm ESIE07-06 1.21 Condenser Temperature Sensor Fault Symbol Indication on Bad Cond Lvg Temp Sensor screen Reason Possible bad electrical connection of the sensor. Countermeasure Check the electrical connections of the sensor. Remark If this fault is generated the unit keeps on running in his minimum capacity step of 35% when programmed in heating mode.
  • Page 135: Set Point Override Input Fault

    ESIE07-06 Alarm 1.22 Set Point Override Input Fault Symbol Reason Countermeasure Part 3 – Troubleshooting 3–27...
  • Page 136: Demand Limit Input Fault

    Alarm ESIE07-06 1.23 Demand Limit Input Fault Symbol Reason Countermeasure 3–28 Part 3 – Troubleshooting...
  • Page 137: Condensation Pressure Sensor Fault

    ESIE07-06 Alarm 1.24 Condensation Pressure Sensor Fault Symbol Reason Pressure sensor defect Countermeasure Part 3 – Troubleshooting 3–29...
  • Page 138: Evaporator Inlet Temperature Sensor Fault

    Alarm ESIE07-06 1.25 Evaporator Inlet Temperature Sensor Fault Symbol Indication on Bad Evap Ent Temp Sensor screen Reason 1. Possible bad electrical connection of the sensor (indication -99,9). Countermeasure 1. Check the electrical connections of the sensor. Remark The unit switches OFF in the cooling and heating mode if the value of the sensor is -99,9°C. The unit switches OFF in the cooling and heating mode if the value of the sensor is +99,9°C.
  • Page 139: Evaporator Outlet Temperature Sensor Fault

    ESIE07-06 Alarm 1.26 Evaporator Outlet Temperature Sensor Fault Symbol Indication on Bad Evap Lvg Temp screen Reason 1. Possible bad electrical connection of the sensor (indication -99,9). Countermeasure 1. Check the electrical connections of the sensor. Remark The unit switches OFF in the cooling and heating mode if the value of the sensor is -99,9°C and indicates leaving water freeze alarm.
  • Page 140: Condenser Pump Maintenance

    Alarm ESIE07-06 1.27 Condenser Pump Maintenance Symbol Reason Running hours pump exceeds the programmed maintenance hours. Countermeasure Do maintenance on the pump and reset the running hours of the pump. 3–32 Part 3 – Troubleshooting...
  • Page 141: Compressor Maintenance

    ESIE07-06 Alarm 1.28 Compressor Maintenance Symbol Reason Running hours compressor exceeds the programmed maintenance hours. Countermeasure Do maintenance on the compressor and reset the running hours of the compressor. Part 3 – Troubleshooting 3–33...
  • Page 142: Evaporator Pump Maintenance

    Alarm ESIE07-06 1.29 Evaporator Pump Maintenance Symbol Reason Running hours evaporator pump exceeds the programmed maintenance hours. Countermeasure Do maintenance on the evaporator pump and reset the running hours of the pump. 3–34 Part 3 – Troubleshooting...
  • Page 143: Unit 1 Offline

    ESIE07-06 Alarm 1.30 Unit 1 Offline Symbol Reason Countermeasure Part 3 – Troubleshooting 3–35...
  • Page 144: Unit 2 Offline

    Alarm ESIE07-06 1.31 Unit 2 Offline Symbol Reason Countermeasure 3–36 Part 3 – Troubleshooting...
  • Page 145: Clock Card Alarm

    ESIE07-06 Alarm 1.32 Clock Card Alarm Symbol Reason Countermeasure Part 3 – Troubleshooting 3–37...
  • Page 146 Alarm ESIE07-06 3–38 Part 3 – Troubleshooting...
  • Page 147: Additional Checks For Troubleshooting

    ESIE07-06 Additional Checks for Troubleshooting Part 3 Additional Checks for Troubleshooting What Is in This Chapter? Introduction Overview This chapter contains the following topics: Topic See page 2.2–PMFH Regulating Valve 3–40 2.3–Oil Flow Switch 3–42 Part 3 – Troubleshooting 3–39...
  • Page 148: Pmfh Regulating Valve

    Additional Checks for Troubleshooting ESIE07-06 PMFH Regulating Valve Introduction The Danfoss SV(H) float valve + PMFH main valve + pilot solenoid valve in combination is used to maintain a constant liquid level within a shell and tube condenser on the high pressure of the unit. The float valve is attached to the vessel by branch connections at a point corresponding to the desired liquid level.
  • Page 149 ESIE07-06 Additional Checks for Troubleshooting 2. Fault: Liquid level in vessel abnormally low SYMPTOMS PROBABLE CAUSE REMEDY Level gauge shows abnormally SV(H) needle valve leaking: Dismantle SV(H) and check low liquid level. worn, damaged or jammed in needle valve assembly. ‘open’...
  • Page 150: Oil Flow Switch

    Additional Checks for Troubleshooting ESIE07-06 Oil Flow Switch Introduction The opto-electronic sensor detects the absence or presence of oil and is used to switch an electrical circuit. Principal Light From LED Probe Dry Reflected Light to Photo Transistor Probe Wetted Light From LED An infra-red light-emitting diode (LED) is used as the light source.
  • Page 151 ESIE07-06 Part 4 Commissioning What is in this part? This part contains the following chapters: Chapter See page 1–??? 4–3 Part 4 – Commissioning 4–1...
  • Page 152 ESIE07-06 4–2 Part 4 – Commissioning...
  • Page 153: What Is In This Chapter

    ESIE07-06 Part 4 What Is in This Chapter? Introduction Overview This chapter contains the following topics: Topic See page 1.2–??? 4–4 Part 4 – Commissioning 4–3...
  • Page 154 ESIE07-06 Label Phase reverse protector 4–4 Part 4 – Commissioning...
  • Page 155 ESIE07-06 Part 5 Maintenance What is in this part? This part contains the following chapters: Chapter See page 1–Maintenance 5–3 Part 5 – Maintenance 5–1...
  • Page 156 ESIE07-06 5–2 Part 5 – Maintenance...
  • Page 157: Maintenance

    ESIE07-06 Maintenance Part 5 Maintenance What Is in This Chapter Introduction Overview This chapter covers the following topics: Topic See page 1.2–Maintenance Schedule 5–4 1.3–Replacing Oil Filter 5–5 1.4–Pumping Out Compressor 5–8 1.5–Replacing Capacity Sensor 5–9 1.6–Calibration of Capacity Sensor 5–10 1.7–PFMH Regulating Valve 5–11...
  • Page 158: Maintenance Schedule

    Maintenance ESIE07-06 Maintenance Schedule Maintenance Planned maintenance exercises are initiated at intervals of calendar months or compressor operating interval hours, whichever time period expires first. Daily 1. Check the oil level in the oil separator. 2. Check and record following items: Item Value Water temperature evaporator and condenser...
  • Page 159: Replacing Oil Filter

    ESIE07-06 Maintenance Replacing Oil Filter Introduction Replacement of the oil filter is only required if the pressure drop across the oil filter is approximately between the 1,5 and 2,5 bar. Action prior to Before removing the oil filter following procedure must be followed: replacing oil filter Step Action...
  • Page 160 Maintenance ESIE07-06 (c) Withdraw the oil filter and spindle. (d) Discard the dirty filter element. Use clean paper to remove dirt and sediment from inside the filter housing. Replacing oil filter Step Action (e) The new oil filter element inside its protective wrapping. (f) Fit a new spindle ‘O’...
  • Page 161 ESIE07-06 Maintenance (g) Insert the filter/spindle assembly into the housing. (h) Locate the oil filter cover onto the housing flange. Insert the hex head cover screws, tighten to 59 N m (44 lbf ft). Procedure before restarting the unit Step Action Charge the compressor with nitrogen for leak test If leak test OK, remove nitrogen...
  • Page 162: Pumping Out Compressor

    Maintenance ESIE07-06 Pumping Out Compressor Introduction Pumping out the compressor is required when some repair or maintenance work needs to be done. Procedure Remark: This procedure can be used when a discharge and a suction valve is installed on the compressor.
  • Page 163: Replacing Capacity Sensor

    ESIE07-06 Maintenance Replacing Capacity Sensor Introduction In the event of malfunction, the HBLVDT electronics module can be replaced without opening the refrigerant circuit. Remark The electronics inside the module can be damaged by static discharges so take all relevant precautions, including earthing yourself before touching the module. Also, it is important that the 24 Vdc power supply to the HBLVDT is turned off before removing the old module or fitting the new one.
  • Page 164: Calibration Of Capacity Sensor

    Maintenance ESIE07-06 Calibration of Capacity Sensor Introduction There are two versions of the HBLVDT depending on the method of calibrating the 4 to 20 mA signal for maximum and minimum load: ■ Calibration via suitable software within the pico² controller. ■...
  • Page 165: Pfmh Regulating Valve

    ESIE07-06 Maintenance PFMH Regulating Valve Introduction No routine maintenance is required. Interval The strainer, fitted at the inlet to the liquid line, should be cleaned after the first 200 hours operation, and then annually, or at intervals of 5000 operating hours, whichever is the sooner. Experience of running the plant may suggest that more frequent cleaning is necessary.
  • Page 166: Replacement Of Refrigerant Oil

    Maintenance ESIE07-06 Replacement of Refrigerant Oil Introduction 5–12 Part 5 – Maintenance...
  • Page 167 EWWD380BJYNN-EWWDC11BJYNN ........
  • Page 168 EWWD380BJYNN-EWWDC11BJYNN ........

This manual is also suitable for:

Ewwd460bjynnEwwd550bjynnEwwd750bjynnEwwd850bjynnEwwd900bjynnEwwdc10bjynn ... Show all

Table of Contents