Cautions and Warnings
DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect
the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify Simplex.
ELECTRICAL HAZARD - Disconnect electrical power when making any internal adjustments or repairs.
Servicing should be performed by qualified Simplex Representatives.
STATIC HAZARD - Static electricity can damage components. Therefore, handle as follows:
1.
Ground yourself before opening or installing components.
2.
Keep uninstalled component wrapped in anti-static material at all times (use the 553-484 Static Control Kit).
RADIO FREQUENCY ENERGY - This equipment generates, uses, and can radiate radio frequency energy and
if not installed and used in accordance with the instruction manual, may cause interference to radio
communications. It has been tested and found to comply with the limits for a Class A computing device pursuant
to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such
interference when operated in a commercial environment. Operation of this equipment in a residential area may
cause interference in which case the user, at his own expense, will be required to take whatever measures may be
required to correct the interference.
TrueAlert
A/V Operation
The 4903 TrueAlert Audible/Visible (A/V) unit (see Table 1) is a wall-mounted
notification appliance that provides an audible and/or visible indication of an alarm
condition when activated from a TrueAlert-compatible control panel of a UL-listed,
Simplex Fire Alarm System. When the notification appliance emits sound and/or
light, it indicates the possibility of an emergency situation that requires your
immediate attention.
The TrueAlert A/V unit is a notification appliance that operates only on a
TrueAlert-compatible Signaling Line Circuit (SLC). The appliance is
supervised via communications with the TrueAlert Addressable Controller
(rather than via conventional appliance supervision).
The A/V unit responds to communication signals over the SLC from a
TrueAlert-compatible panel. Coded messages from the TrueAlert controller turn on
the A/V strobe and horn. The A/V can only be operated through a 4009-9401
TrueAlert Addressable Controller using Simplex TrueAlert Comm Channel
communications.
The A/V horn provides selectable high/low volume sound pressure levels with audible output types of Steady, Temporal, and
March Time (fast/slow). The compatible TrueAlert Addressable Controller or FACP is used to configure the features.
Note: The TrueAlert A/V will not operate on a conventional NAC.
TrueAlert A/Vs are available rated at 15 candela, 75 candela, and 110 candela. Each model is available with a red or white cover.
Table 1 lists the available A/V models.
Wall-Mount A/V 15 CANDELA
Wall-Mount A/V 75 CANDELA
Wall-Mount A/V 110 CANDELA
Wall-Mount A/V 15 CANDELA
Wall-Mount A/V 75 CANDELA
Wall-Mount A/V 110 CANDELA
 2000 Simplex Time Recorder Co., Westminster, MA 01441-0001 USA
All specifications and other information shown were current as of publication, and are subject to change without notice.
TrueAlert is a trademark of Simplex Time Recorder Company.
Suffix "C" or "CA" following an eight-digit product ID number denotes ULC-listed product.
Table 1. Wall-Mount TrueAlert A/V Models
Description
4903 TrueAlert
Installation Instructions
Figure 1. TrueAlert A/V
Model
A/V Cover Color
4903-9450
4903-9451
4903-9452
4903-9453
White
4903-9454
4903-9455
A/V
Red
574-768
Rev. B

Advertisement

loading
Need help?

Need help?

Do you have a question about the TrueAlert 4903-9450 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Simplex TrueAlert 4903-9450

  • Page 1 DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify Simplex. ELECTRICAL HAZARD - Disconnect electrical power when making any internal adjustments or repairs.
  • Page 2 TrueAlert A/V Wiring Warning: Make sure that all electrical power is disconnected before starting the installation. Caution: Connect wiring to terminals as shown. Do not loop wires under terminals. Break wire runs to provide supervision of connections. Strip lead insulation to 3/8” maximum. At the enclosure box, run contractor wiring through the cutout slot and connect the wires to the CKT + and CKT - terminals at the front of the A/V unit.
  • Page 3 Mounting the TrueAlert A/V See Figure 3 for mounting the TrueAlert A/V to the enclosure box. When surface mounting the A/V, either the  4905-9937 or 4905-9940 TrueAlert Surface Mount Skirt is recommended. Refer to the 4905 TrueAlert Skirt Installation Instructions (574-790) for this mounting application. 1.
  • Page 4 Setting the A/V Address Each TrueAlert notification appliance has a unique address. Each appliance’s address is set via an eight-position DIP switch, as shown in Table 2 (see Figure 3 for the general DIP switch location). DIP switch position 1 is the least significant bit (LSB) and position 8 is the most significant bit (MSB).
  • Page 5 Current and Sound Pressure Measurements Refer to Table 3 for current rating information. Table 3. TrueAlert A/V Units – Strobe Current Rating Chart Candela Input (Vrms) In-Rush (V mA) Peak (mA) Nominal Avg. (mA rms) High Volume Setting Low Volume Setting Supervision Current: 1 TrueAlert Unit Load.
  • Page 6 Local Authority Having Jurisdiction (AHJ) Requirements Notification appliances are not intended for installation within hazardous locations as defined by the National Electrical Code (NEC) or the NFPA. Contact Simplex for information on explosion-proof notification appliances designed for hazardous environments. 574-768...