Page 7
SAL81.00T40 SAL81.03T10 SAL81.03T10/F05 These types of actuator are UL-listed versions Glossary and Index are arranged at the end of the document. Note 7 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure About this documentation 2024-04-11...
Copyright 1.4.2 This document may be duplicated and distributed only with the express permission of Siemens, and may be passed on only to authorized persons or companies with the required technical knowledge. 9 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL..
Siemens assumes no liability to the extent allowed under the law for any losses resulting from a failure to comply with the aforementioned points or for the improper compliance of the same.
For use in connection with Siemens 2-port or 3-port valves with 20/40 mm stroke, SAX.., SAV.. as control or shutoff valves for HVAC plants. For the operation of Siemens combi valves of type VPI46.40F9.5Q and SAY.. VPI46.50F12Q with 15 mm stroke as control valves in ventilation, air conditioning, and district heating systems.
1 pc. M5 x 20 mm incl. 1 pc. 12 mm ASK32N 4 pcs. M6 x 16 mm 1 pc. 12mm 1 pc. M5 x 20 mm incl. 14 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Engineering 2024-04-11...
Page 15
2 pcs. M8 x 50 mm 1 pc. 12 mm 1 pc. M5 x 20 mm incl. 1 pc. 16 mm 16 mm 12 mm 15 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Engineering 2024-04-11...
Page 17
Valves no longer in the active sale SAV..: This product line of actuators might not be available in all countries. Please talk to your local contact or consult your local internet pages of www.buildingtechnologies.siemens.com. Only in compbination with SKC.. 17 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL..
Page 19
Valves no longer in the active sale SAV..: This product line of actuators might not be available in all countries. Please talk to your local contact or consult your local internet pages of www.buildingtechnologies.siemens.com Only in combination with SKC.. 19 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL..
VKF41.. maximum flow speed with SAL.T0 actuator with water DN150/200 = 2.5 m/s, with SAL.T40 actuator with water DN150/200 = 4 m/s Only the hand lever ASK41.. or an actuator can be mounted, not both. 21 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
The signal peaks that occur in the potentiometer ASZ7.5 may result in error messages on Siemens SIMATIC. This is not the case when combined with Siemens HVAC controllers. The reason is that SIMATIC has a higher resolution and faster response time.
SQX31.06: Actuator for gas valves. Either replace complete valve-actuator combination or clarify required positioning time and replace only actuator. Consider if mounting set is required. 23 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
• Non-observance of the above may result in accidents and fires! • Do not touch the hot parts without prior protective measures to avoid burns. 24 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Engineering...
4 screws 2 pcs. M5 x 20 mm 2 pcs. M6 x 20 mm Single components from the spare part sets are not available. 25 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Engineering 2024-04-11...
DC voltage drop might lead to self-oscillations. • The operating voltage drop at AC/DC 24 V may be a maximum of 8% (4% above the G0 wire). 26 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
The engineering data specified in chapter "Equipment combinations" (page 16) are only guaranteed in connection with the Siemens valves listed. Note When using the actuators in connection with valves of other manufacture, correct functioning must be ensured by the user, and Siemens will assume no responsibility. 27 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL..
Risk of burns from hot surfaces! If you touch heated parts, you will get burns as result. • Allow to cool parts. • Wear protective gloves. Actuator’s stem retracted 28 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
If so, please take care for correct mounting, either by turning the actuator or by adjusting the fitting (e.g. use a second sealing to change fitting position). 29 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
If you touch heated parts, you will get burns as result. • Allow to cool parts. • Wear protective gloves. 5 mm 5 mm 30 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
Page 31
5 mm 4 mm Angle position errors between actuator shaft and valve stem must be corrected via manual control (refer to "Manual adjuster" page 80). 31 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling...
If you touch heated parts, you will get burns as result. • Allow to cool parts. • Wear protective gloves. 10 mm, ASK31N ASK32N 13 mm 90° 32 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
Page 33
4 mm, 5 mm 4 mm, 5 mm counterclockwise ASK31N 12 mm ASK32N 3.2a 3.2b 4 mm, 5 mm 4 mm, 5 mm ASK31N 12 mm ASK32N 33 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
Page 34
For further mounting positions of VBF 21.. and routing of the connection cables the rotary actuators and adapters must be mounted according to the sketches above. 34 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
If you touch heated parts, you will get burns as result. • Allow to cool parts. • Wear protective gloves. 12 mm (DN 40…125) 16 mm (DN 150 / 200) 36 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
Page 37
4 mm 6 mm 37 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
If you touch heated parts, you will get burns as result. • Allow to cool parts. • Wear protective gloves. – – 11 mm (DN 40…50) – 14 mm (DN 80…125) 38 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
Page 39
– 4 mm (DN 40…65) – 5 mm (DN 80…125) 39 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
If you touch heated parts, you will get burns as result. • Allow to cool parts. • Wear protective gloves. – – 11 mm (DN 40…50) – 14 mm (DN 80…125) – 40 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
Page 41
– 4 mm (DN 40…65) – 5 mm (DN 80…125) 41 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
There is an immediate risk of fatal injury in case of contact with live parts of SA..31... • Disconnect actuator from power. Actuator is mechanically connected to a Siemens valve. Observe compatibility and choice of combinations. Refer to "Accessories" (page 22).
Page 44
If a live wire gets in contact with the screws the whole actuator housing is a live. • Fit the screw covers first. Plug-in space A No.: 1 Click Turn to 0% 44 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
Page 45
Observe "Connection terminals" (page 88) First, observe "Special notes on mounting” (page 43). Function module AZX61.1 Set function module (page 64) Nr.: 3 Plug-in space B Click 45 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
• Fit the screw covers first. Plug-in space A No.: 1 Click Adjust switch position (refer also to "Manual operation" page 80) 46 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
Page 47
If a live wire gets in contact with the screws the whole actuator housing is a live. • Fit the screw covers first. Plug-in space B No.: 1 Click 47 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
Page 48
Adjust switch position (refer also to "Manual operation" page 80) No.: 1 When initial situation: 0 Ω When initial situation: ∞ Ω Observe "Wiring" (page 50) Observe "Connection terminals" (page 88) 48 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
Page 49
When fitting the stem heating element, stroke actuator and valve must be assembled. The stem heating element is powered separately. First, observe "Special notes on mounting” (page 43). 10 mm 14 mm 8 mm 49 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
Page 51
Metric Inch thread ½“ Prior to installation, the following preconditions must be satisfied: • Actuator is mechanically connected to a Siemens valve. • Housing cover is removed (step 6 "Special notes on mounting", page 43). Communicating Device contains fixed actuators connecting cable.
Mechanically • Environmental conditions specified in chapter "Technical data" (page 84) • Actuator is mechanically connected to a Siemens valve • Actuator is in "Manual operation" mode (page 80). The actuator can be operated with the help of the "Manual adjuster" (see page 80).
Page 54
• If function module AZX61.1 is used, observe information given in chapter Notes "Changeover of acting direction" (page 65). • Observe information given in chapter "Acting direction and flow characteristic" on page 67. 54 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
Page 55
(65%) position (65%) Actuator’s stem Actuator’s spindle Check position value with maintains the maintains the ~ 485 Ω ~ 511 Ω ohmmeter position position 55 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
• The actuator parameters (direction for opening, position limits, position adjustment etc.) can be read via the Modbus register. Documents can be downloaded at http://www.siemens.com/bt/download Full or partial configuration via bus The actuators can be configured via bus connection if the settings prior to commissioning allow for a connection to the Modbus master/programming tool (no address conflicts and correct baud rates/transmission format settings).
Invalid configuration, e.g. Min = Max Blue Flickering once after address indication Bus termination active Dark Dark Fail safe function activated or no power applied Only for SA..61../MO 57 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
Page 58
7. Save address: Press button until LED is – release button → The address is saved and displayed 1x for confirmation 58 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
• Dispose of the device through channels provided for this purpose. • Comply with all local and currently applicable laws and regulations. 59 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2024-04-11...
Observe information given in chapter "Acting direction and flow characteristic" on page 67. Internal control ensures very constant positioning times and determination of the actuator’s position. 60 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control...
Page 61
Actual position time [ms] (power applied) applied Accurate position feedback is made possible with the help of a potentiometer Notes (page 82). 61 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control 2024-04-11...
Notes "Changeover of acting direction" (page 65). • Observe the information given in chapter "Acting direction and flow characteristic" on page 67. 63 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control 2024-04-11...
• Can only be used with voltage input. Notes • Maximum input voltage is DC 30 V. If the configuration is invalid, the actuator operates on DC 0…10 V. 64 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control...
Y = 0 V resp. direction Z = 0 Ω. This applies to all Siemens valves according to "Equipment combinations" (page 16). • With valves whose stem is retracted in the fully closed position, "direct acting"...
Positioning signal Stroke Volumetric flow Acting direction: Direct Acting direction: Reverse Note SAX61.03/MO: Positioning signal and flow characteristic selection are not permissible. 66 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control 2024-04-11...
Actuator Actuator Positioning signal Y, Z Position feedback U 10 V log = equal- percentage 10 V lin = linear 67 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control 2024-04-11...
With this function it’s granted that the position feedback U – which was zero during manual operation and synchronization - always represents the real mechanical position of the actuator. 68 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
(2), valve opens. Detection of lower end position. • The detected values are stored (3). Then the 100% actuator follows the positioning signal. 69 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control 2024-04-11...
50%. From now on, the actuator follows the positioning signal. When the valve plug reaches its seat for the first time, the actuator readjusts its stroke model. 70 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control...
If the attempts made are unsuccessful, the actuator continues to follow the positioning signal within the restricted range only and the actuator LED continues to blink green (refer to "Indicators" on page 81). 71 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
To match the actuator to production-related mechanical tolerances of the individual valves, accurate positioning and position feedback must be ensured, if calibration is performed when the plant is commissioned (page 53). During commissioning, 73 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
After the synchronization, the actuator follows the pending setpoint, the LED on the cover changes to continuous green and, on the cable adapter, blinking green (communication active). The warning in register 769 is reset. 74 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
“Setpoint / actual value” rotation, resolution 0.01, i.e. 0% = 0 and 100% = 10000. The actual value reported by the device, with the same resolution. 76 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
Page 77
“Positioning signal cha- logarithmic characteristic, in order to achieve a linear input/output signal relation racteristic betw. Y and U” (cf. “Parameter” table, page 75). 77 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control...
Page 78
“Load” is called within 60 seconds in this “Bus config. register. Otherwise, all changes are discarded. Command” Register 516 “Startup setpoint” 78 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control 2024-04-11...
The stem coupling (1) and neck coupling (2) Mounting sets are available for use with butterfly ensures full backward compatibility with all types and slipper valves. of Siemens large-stroke valves produced since 1975. 4.14.3 Manual adjuster Automatic When the motor drives the manual adjuster turns.
Start calibration again. Calibration error Blinking If error re-occurs immediately: check Clogged valve valve Dark Dark No power or electronics faulty Check operating voltage 81 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control 2024-04-11...
SAV.. R = 0 + 8.55 Ohm x rotary angle (°) SAL.. Actuator position in relation to nominal stroke/nominal angular rotation [%] 82 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control 2024-04-11...
Mounting sets ASK31N, ASK32N, ASK33N and ASK35Nenable the actuators to be Mounting sets fitted to slipper valves VBF21.., DN65…150 and butterfly valves VKF41.. and ASK3..N VKF45 (page 30-37). 83 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control 2024-04-11...
Switch-on current 3-position actuators (typical) SA..31.. 2.3 A 2.3 A 2.3 A 2.3 A SA..81.. 4.5 A 4.5 A 4.5 A 4.5 A 84 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Technical data 2024-04-11...
Page 85
As per EN 60730 tion Actuators SA..31.. AC 230 V Actuators SA..61.. AC / DC 24 V Actuators SA..81.. AC / DC 24 V 85 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Technical data 2024-04-11...
Page 86
AWG = American wire gauge Also with weather shield ASK39.1 SA..61../MO are not suitable for outdoor applications. Up to 150 °C with horizontal mounting position The documents can be downloaded from http://siemens.com/bt/download. UL recognized component 86 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves...
1x ASC10.51 AC 24 V...230 V / 6 (2) A S3 S2 or 1 x ASZ7.5 S3 S2 AC/DC 24 V 87 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Connection diagrams and dimensions 2024-04-11...
AC/DC 24 V / 30 W / 50 VA / inrush current max. 8.5 A Stem heating element ASZ6.6 System neutral (SN) (red) System potential (SP) (black) 89 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Connection diagrams and dimensions 2024-04-11...
SAX..U: 1.850 kg SAY..U: 1.850 kg Device equipped with a fixed connection cable – Left cable entry is used Dimensions in mm 92 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Connection diagrams and dimensions...
External Modbus converter 6.4.2 Type [mm] [kg] 0.15 SA../MO Already included in total weight Dimensions in mm 93 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Connection diagrams and dimensions 2024-04-11...
1.475 1.600 1.625 With ASK39.1 1.710 1.835 1.860 With mounting set ASK3..N Type SAL.. with ASK3..N With ASK39.1 Dimensions in mm 94 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Connection diagrams and dimensions 2024-04-11...
/ maxV Maximum permissible differential pressure at which the motorized valve will close Δp securely against the pressure (close off pressure). slotted screwdriver 96 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Glossary 2024-04-11...
Page 97
Stroke actuators ........92, 93 Fixing the coupling .......... 80 Direct acting..........65, 67 Manual operation ..........80 Directives ............86 Manual adjustment ........60, 63, 74 97 / 100 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Index 2024-04-11...