Ruskin IBD2G Installation Instructions Manual

Curtain type fire dampers for grille mounting

Advertisement

Quick Links

3900 Dr. Greaves Rd.
CURTAIN TYPE FIRE DAMPERS FOR GRILLE MOUNTING
APPLICATION
The Model G curtain fire damper is designed to be mounted behind
a grille in the wall or floor. Model G dampers are offset in the damper
sleeve for appropriate damper placement within the wall or floor.
Model G dampers are designed for one side-mounting angle instal-
lation. Sleeve and/or mounting angles may be factory or field fur-
nished. Grille may be installed on both sides of the wall or floor if no
duct connection is required (Grille by others).
STATIC FIRE DAMPERS
Not for use in Dynamic (fans on) Systems.
MODEL IBD2G and IBD2SSG MAXIMUM SIZE
Single Section
Vertical – 48"w x 30"h (1219 x 762) or 33"w x 48"h or (838
x 1219) or 36"w x 36"h (914 x 914).
Horizontal – 30"w x 45
/
1
x 965).
Multiple Section Assembly
Vertical – 90"w x 48"h (2286 x 1219) or 48"w x 72"h (1219 x
x 1829).
Horizontal – 90"w x 48"h (2286 x 1219) or 48"w x 90"h (1219
x 2286).
MODEL IBD20G MAXIMUM SIZE
Single Section
Vertical – 48"w x 30"h (1219 x 762) or 33"w x 48"h or (838
1219) or 36"w x 36"h (914 x 914).
Horizontal – 30"w x 45
/
1
x 965).
MODEL IBDTG, IBDT1G and IBDT2G MAXIMUM SIZE
Single Section
Vertical – 40"w x 48"h (1016 x 1219).
Horizontal – 36"w x 36"h (914 x 914).
Notes:
1. Dimensions shown in parentheses ( ) indicate millimeters.
2. All multiple section dampers are constructed of equal single
section sizes no greater than the maximum single section sizes
indicated above.
SEE COMPLETE MARKING
ON PRODUCT
California State Fire Marshal Listing No. 3225-245:0005
II-(D)IBDG-618/Replaces II-(D)IBDG-616
Kansas City, MO 64030
INSTALLATION INSTRUCTIONS
(D)IBD2G, (D)IBD2SSG, (D)IBD20G, (D)IBDTG
1
/
HOUR UL555 CLASSIFIED
1
2
"h (762 x 1156) or 33"w x 38"h (838
2
"h (762 x 1156) or 33"w x 38"h (838
2
ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION.
(816) 761-7476
DYNAMIC FIRE DAMPERS
Use in Dynamic (fans on) or Static (fans off) Systems
MODEL DIBD2G MAXIMUM SIZE
Single Section
Vertical – 33"w x 36"h (838 x 914).
Horizontal – 24"w x 24"h (610 x 610).
Multiple Section Assembly
Vertical – 72"w x 48"h (1828 x 1219) or 48"w x 72"h (1219 x
1829).
MODEL DIBDX2G MAXIMUM SIZE
Single Section
Horizontal – 18"w x 24"h (457 x 610) or 24"w x 18"h (610 x
457).
Multiple Section
Horizontal – 36"w x 48"h (914 x 1219) or 48"w x 36"h (1219 x
914).
MODEL DIBD2SSG MAXIMUM SIZE
Single Section
Vertical or Horizontal – 24"w x 24"h (610 x 610).
Multiple Section Assembly
Vertical – 72"w x 48"h (1829 x 1219) or 48"w x 72"h (1219 x
1829).
MODEL DIBD20G MAXIMUM SIZE
Single Section
Vertical – 33"w x 36"h (838 x 914).
Horizontal – 24"w x 24"h (610 x 610).
MODEL (D)IBDTG, (D)IBDT1G and (D)IBDT2G MAXIMUM SIZE
Single Section
Vertical – 24"w x 24"h (610 x 610).
INSTALLATION SUPPLEMENTS
Refer to the appropriate Ruskin installation instruction supplements
for additional information or special requirements:
• Optional Sealant of Dampers in Fire Rated Wall or Floor Openings
• Transfer Openings and Duct Terminations
• Optional FireStop Material
• Extension of Fire and Combination Fire and Smoke Damper
Sleeves
• Fire and Combination Fire and Smoke Dampers Installation in
Concrete Floor with Steel Deck
• Drivemate No. 14880 Breakaway Connection
• Flanged System Breakaway Connections
• Cavity Shaft Wall Metal Stud Framing
FAX (816) 765-8955
© Ruskin June 2018

Advertisement

loading
Need help?

Need help?

Do you have a question about the IBD2G and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Ruskin IBD2G

  • Page 1 INSTALLATION SUPPLEMENTS Notes: 1. Dimensions shown in parentheses ( ) indicate millimeters. Refer to the appropriate Ruskin installation instruction supplements for additional information or special requirements: 2. All multiple section dampers are constructed of equal single section sizes no greater than the maximum single section sizes •...
  • Page 2 1. Opening Clearance 6. Duct/Sleeve Connections a. Break-away Duct/Sleeve Connections The opening in the wall or floor shall be larger than the damper/ sleeve assembly to permit installation and expansion. The maxi- Rectangular ducts must use one or more of the connections mum opening size shall not exceed "...
  • Page 3: Vertical Installation

    VERTICAL INSTALLATION Wall See Note 3 See Note 3 See Note 1 Damper Damper Grill by Others Sleeve Sleeve Mounting Angle Mounting Angle See Note 5 See Note 5 STEEL STUD or MASONRY WALLS WOOD STUD Mounting angle may be located on top or underneath the wallboard (See Mounting angle to be mounted on top of wallboard (See note 5).
  • Page 4 FASTENER SPACING HORIZONTAL INSTALLATION VERTICAL INSTALLATION 6" (152) Max.c-c 3" (76) 6" (152) or Max. 12” (305) Max.c-c 3" (76) 6" (152) or Max. 12” (305) Max.c-c See Note 2 2" (51) Max. Mullion Plate See Note 2 See Note 2 FIGURE 1 FIGURE 2 REINFORCING PLATE...
  • Page 5 RECOMMENDED FRAMING FOR OPENINGS IN WOOD AND METAL STUD WALLS INSTRUCTIONS 1. Frame wall openings as shown in figure 1 or 2. 2. Double vertical studs are not required for openings 36"w x 36"h (914 x 914) or smaller. 3. All construction and fasteners must meet the requirements of the appropriate wall design and/or local codes.
  • Page 6 3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 www.ruskin.com...