Toshiba RAS-B05S4KVG-E Service Manual
Hide thumbs Also See for RAS-B05S4KVG-E:
Table of Contents

Advertisement

Quick Links

SERVICE MANUAL
Indoor Unit
RAS-B05S4KVG-E
RAS-B07S4KVG-E
RAS-B10S4KVG-E
RAS-B13S4KVG-E
RAS-B16S4KVG-E
RAS-B18S4KVG-E
R32
FILE NO. SVM-24006-2
SPLIT TYPE
Outdoor Unit
RAS-05E2AVG-E
RAS-07E2AVG-E
RAS-10E2AVG-E
RAS-13E2AVG-E
RAS-16E2AVG-E
RAS-18E2AVG-E
Revised on Jul, 2024

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RAS-B05S4KVG-E and is the answer not in the manual?

Questions and answers

Summary of Contents for Toshiba RAS-B05S4KVG-E

  • Page 1 FILE NO. SVM-24006-2 SERVICE MANUAL SPLIT TYPE Indoor Unit Outdoor Unit RAS-B05S4KVG-E RAS-05E2AVG-E RAS-B07S4KVG-E RAS-07E2AVG-E RAS-B10S4KVG-E RAS-10E2AVG-E RAS-B13S4KVG-E RAS-13E2AVG-E RAS-B16S4KVG-E RAS-16E2AVG-E RAS-B18S4KVG-E RAS-18E2AVG-E Revised on Jul, 2024...
  • Page 2: Table Of Contents

    CONTENTS 1. SAFETY PRECAUTIONS ................3 2. SPECIFICATIONS ..................7 3. REFRIGERANT R32 .................11 4. CONSTRUCTION VIEWS ................ 19 5. WIRING DIAGRAM .................. 23 6. SPECIFICATIONS OF ELECTRICAL PARTS ......... 26 7. REFRIGERANT CYCLE DIAGRAM ............27 8. CONTROL BLOCK DIAGRAM ..............32 9.
  • Page 3: Safety Precautions

    1. SAFETY PRECAUTIONS Read the precautions in this manual This appliance is fi lled with R32. carefully before operating the unit. (Flammable Material) Information included in the Operation Service personnel should be handing this equipment Manual and/or Installation Manual. with reference to the Installation Manual. Warning Indications on the Air Conditioner Unit Warning indication Description...
  • Page 4: New Refrigerant Air Conditioner Installation

    CAUTION New Refrigerant Air Conditioner Installation • THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R32) WHICH DOES NOT DESTROY OZONE LAYER. R32 refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the working pressure of R32 refrigerant is approx.
  • Page 5 WARNING • Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock switches. • Do not install in a place which cannot bear the weight of the unit. Personal injury and property damage can result if the unit falls.
  • Page 6: For Reference

    CAUTION • Exposure of unit to water or other moisture before installation may result in an electrical short. Do not store in a wet basement or expose to rain or water. • Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify the noise level of the unit or where noise or discharged air might disturb neighbors.
  • Page 7: Specifications

    2. SPECIFICATIONS 2-1. Specification RAS-B05S4KVG-E RAS-B07S4KVG-E Unit model Indoor Outdoor RAS-05E2AVG-E RAS-07E2AVG-E 1.50 2.00 Cooling capacity (kW) 0.75-2.00 Cooling capacity range (kW) 0.76-2.60 2.00 Heating capacity (kW) 2.50 Heating capacity range (kW) 0.80-3.00 0.82-3.30 Power supply 1Ph/50Hz/220-240V Electric Indoor Operation mode...
  • Page 8 Unit model Indoor RAS-B10S4KVG-E RAS-B13S4KVG-E Outdoor RAS-10E2AVG-E RAS-13E2AVG-E Cooling capacity (kW) 2.50 3.30 Cooling capacity range (kW) 0.80-3.00 1.20-3.60 3.20 Heating capacity (kW) 3.60 0.95-3.90 0.97-4.50 Heating capacity range (kW) Power supply 1Ph/50Hz/220-240V Electric Indoor Operation mode Cooling Heating Cooling Heating characteristic Running current...
  • Page 9 Unit model Indoor RAS -B16S4KVG-E RAS-18S4KVG-E Outdoor RAS -16E2AVG-E RAS-18E2AVG-E 4.20 5.00 Cooling capacity (kW) Cooling capacity range (kW) 1.40-4.70 1.45-5.50 Heating capacity (kW) 5.00 5.40 1.30-6.00 1.35-6.00 Heating capacity range (kW) Power supply 1Ph/50Hz/220-240V 1Ph/50Hz/220-240V Electric Indoor Operation mode Co o ling H ea ting Co o ling...
  • Page 10: Operation Characteristic Curve

    2-2. Operation Characteristic Curve <Cooling> <Heating> RAS-B18S4KVG-E RAS-B18S4KVG-E RAS-B16S4KVG-E RAS-B16S4KVG-E RAS-B13S4KVG-E RAS-B10S4KVG-E RAS-B10S4KVG-E RAS-B13S4KVG-E RAS-B07S4KVG-E RAS-B05S4KVG-E RAS-B07S4KVG-E RAS-B05S4KVG-E Conditions Conditions Indoor : DB 20 C/WB 15 Indoor : DB 27 C/WB 19 Outdoor : DB 7 C/WB 6 Outdoor : DB 35...
  • Page 11: Refrigerant R32

    3. REFRIGERANT R32 3. If a refrigeration gas leakage occurs during This air conditioner adopts the new refrigerant HFC (R32) which does not damage the ozone layer. installation/servicing, be sure to ventilate fully. If the refrigerant gas comes into contact with fire, a The next section describes the precautions for air conditioner using the new refrigerant.
  • Page 12 Table 3-2-1 Thicknesses of annealed copper pipes Thickness (mm) Nominal diameter Outer diameter (mm) R32(R410A) 6.35 0.80 0.80 9.52 0.80 0.80 12.70 0.80 0.80 15.88 1.00 1.00 2. Joints For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm.
  • Page 13 d) Flare Processing Make certain that a clamp bar and copper pipe have been cleaned. ØD By means of the clamp bar, perform the flare processing correctly. Use either a flare tool for R32 or conven- tional flare tool. Flare processing dimensions differ according to the type of flare tool.
  • Page 14 Table 3-2-6 Flare and flare nut dimensions for R22 Dimension (mm) Nominal Outer diameter Thickness Flare nut width diameter (mm) (mm) (mm) 6.35 9.52 13.0 13.5 12.70 16.2 16.0 12.9 15.88 19.7 19.0 16.0 19.05 23.3 24.0 19.2 Fig. 3-2-2 Relations between flare nut and flare seal surface 2.
  • Page 15 3-3. Tools 3-3-1. Required Tools The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R32 is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
  • Page 16: Recharging Of Refrigerant

    3-4. Recharging of Refrigerant When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps. Recover the refrigerant, and check no refrigerant remains in the equipment. When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
  • Page 17: Brazing Of Pipes

    3-5. Brazing of Pipes 3-5-1. Materials for Brazing 3. Types of flux • Noncorrosive flux 1. Silver brazing filler Generally, it is a compound of borax and boric Silver brazing filler is an alloy mainly composed acid. of silver and copper. It is used to join iron, copper It is effective in case where the brazing tem- or copper alloy, and is relatively expensive though perature is higher than 800°C.
  • Page 18 3-5-3. Brazing As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified. Flow meter In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to Stop valve proceed with brazing while letting dry Nitrogen gas (N2) flow.
  • Page 19: Construction Views

    4. CONSTRUCTION VIEWS 4-1. Indoor Unit RAS-B05,07,10S4KVG-E Air filter Front panel Air filter Grille inlet Heat exchanger Air outlet Knock out system Wireless remote controller Installation plate hanger 17.5 Remote controller holder Drain hose (0.4m) Installation plate hanger Installation plate hanger Connecting pipe (0.40m) Connecting pipe (0.35m) (Flare...
  • Page 20 RAS-B13,16,18S4KVG-E Air filter Front panel Air filter Grille inlet 60 60 60 60 Wireless remote controller 100 42 17.5 Remote controller holder Drain hose (0.4m) Installation plate hanger Installation plate hanger Connecting pipe (0.35m) Connecting pipe (0.35m) (Flare 12.70mm ) (Flare 6.35mm ) Hanger...
  • Page 21: Outdoor Unit

    4-2. Outdoor Unit (RAS-05,07,10,13E2AVG-E) (Unit : mm) - 21 -...
  • Page 22: Installation Dimension

    (RAS-16,18E2AVG-E) (Unit : mm) Ø6 hole R5.5 Ø6 hole Ø11x14 hole A detail Drawing (Back leg) Ø 11 x 14 Hole Drain outlet B Detail Drawing (Front leg) (For 8 - 10 anchor bolt) Ø Ø FAN-GUARD Ø 436 COVER-PV Liquid side (Flare 6.35)
  • Page 23: Wiring Diagram

    5. WIRING DIAGRAM RAS-B05S4KVG-E / RAS-05E2AVG-E RAS-B07S4KVG-E / RAS-10E2AVG-E RAS-B10S4KVG-E / RAS-13E2AVG-E RAS-B13S4KVG-E / RAS-16E2AVG-E 2 3 L N 1 2 3 1 2 3 6.3A 250V~ t° t° t° COLOR INDICATION RED : RED WHI : WHITE YEL : YELLOW BLK : BLACK GRN&YEL :...
  • Page 24 RAS-B16S4KVG-E / RAS-16E2AVG-E 2 3 L N 1 2 3 1 2 3 6.3A 250V~ t° t° t° COLOR INDICATION RED : RED WHI : WHITE YEL : YELLOW BLK : BLACK GRN&YEL : GREEN&YELLOW - 24 -...
  • Page 25 RAS-B18S4KVG-E / RAS-18E2AVG-E Case of Inverter Multi System (IMS) model 2 3 L N Outdoor Unit 1 2 3 1 2 3 CN30 CN31 CN28 (WHI) 6.3A 250V~ Serial Communication Circuit CN63 (RED) t° CN36 (WHI) CN62 CN32 CN61 (WHI) (YEL) POWER SUPPLY CIRCUIT...
  • Page 26: Specifications Of Electrical Parts

    6. SPECIFICATIONS OF ELECTRICAL PARTS 6-1. Indoor Unit Parts name Type name Specifications WDF-340-30CA Fan Motor (for indoor) RAS-B05,07,10,13,16 DC 340V, 42W WDF-340-30 DC 340V, 42W RAS-B18 Room temp. sensor (TA-sensor) 10kΩ at 25°C Heat exchanger temp. sensor (TC-sensor) 10kΩ at 25°C Heat exchanger temp.
  • Page 27: Refrigerant Cycle Diagram

    7. REFRIGERANT CYCLE DIAGRAM 7-1. Refrigerant Cycle Diagram RAS-B05S4KVG-E / RAS-05E2AVG-E RAS-B07S4KVG-E / RAS-07E2AVG-E Temp. measurement INDOOR UNIT Indoor heat exchanger Cross flow fan Max. : 15m Min. : 2m Pressure measurement Chargeless : 15m Deoxidized copper pipe Gauge attaching port Outer dia.
  • Page 28 RAS-B10S4KVG-E / RAS-10E2AVG-E Temp. measurement INDOOR UNIT Indoor heat exchanger Cross flow fan Max. : 15m Min. : 2m Pressure measurement Chargeless : 15m Deoxidized copper pipe Gauge attaching port Outer dia. : 6.35mm Vacuum pump connecting port Thickness : 0.8mm Sectional shape Deoxidized copper pipe of heat insulator...
  • Page 29 RAS-B13S4KVG-E / RAS-13E2AVG-E Temp. measurement INDOOR UNIT Indoor heat exchanger Cross flow fan Max. : 15m Min. : 2m Pressure measurement Chargeless : 15m Deoxidized copper pipe Gauge attaching port Outer dia. : 6.35mm Vacuum pump connecting port Thickness : 0.8mm Sectional shape Deoxidized copper pipe of heat insulator...
  • Page 30 RAS-B16S4KVG-E / RAS-16E2AVG-E RAS-B18S4KVG-E / RAS-18E2AVG-E Temp. measurement INDOOR UNIT Indoor heat exchanger Cross flow fan Max. : 20m Min. : 2m Pressure measurement Chargeless : 15m Deoxidized copper pipe Gauge attaching port Outer dia. : 6.35mm Vacuum pump connecting port Thickness : 0.8mm Sectional shape Deoxidized copper pipe...
  • Page 31: Operation Data

    7-2. Operation Data <Cooling> Temperature Model name Standard Heat exchanger Indoor Outdoor Compressor Connecting condition(°C) pipe temp. RAS- pressure fan mode fan mode revolution piping Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps) B05S4KVG-E High 27/19 35/- 1.2 to 1.3 43 to 44 High 14 to 16...
  • Page 32: Control Block Diagram

    8. CONTROL BLOCK DIAGRAM 8-1. Indoor Unit Indoor Unit Control Panel M.C.U Functions Operation Heat Exchanger Sensor • Louver Control Display Timer • 3-minute Delay at Restart for Compressor Temperature Sensor Display • Motor Revolution Control Hi power Infrared Rays Signal Receiver Display •...
  • Page 33: Outdoor Unit (Inverter Assembly)

    8-2. Outdoor Unit (Inverter Assembly) RAS-B05S4KVG-E / RAS-05E2AVG-E RAS-B07S4KVG-E / RAS-07E2AVG-E RAS-B10S4KVG-E / RAS-10E2AVG-E RAS-B13S4KVG-E / RAS-16E2AVG-E - 33 -...
  • Page 34 RAS-B16S4KVG-E / RAS-16E2AVG-E RAS-B18S4KVG-E / RAS-18E2AVG-E - 34 -...
  • Page 35: Operation Description

    9. OPERATION DESCRIPTION 9-1. Outline of Air Conditioner Control • Detection of inverter input current and current release operation This air conditioner is a capacity-variable type air conditioner. Its system can control the speed of • Over-current detection and prevention operation compressor motor according to load.
  • Page 36 9-2. Operation Description 1. Basic operation ...................... 1. Operation control ....................2. Cooling/Heating operation ................3. AUTO operation ....................4. DRY operation ....................2. Indoor fan motor control ..................3. Outdoor fan motor control ..................4. Capacity control ..................... 5. Current release control ..................6.
  • Page 37: Operation Control

    Item Operation flow and applicable data, etc. Description 1. Basic 1. Operation control operation Receiving the user’s operation condition setup, the operation statuses of indoor/outdoor units are controlled. 1) The operation conditions are selected by the remote controller as shown in the below. 2) A signal is sent by ON button of the remote controller.
  • Page 38: Basic Operation

    Item Operation flow and applicable data, etc. Description 2. Cooling/Heating operation 1. Basic operation The operations are performed in the following parts by controls according to cooling/heating conditions. 1) Receiving the operation ON signal of the remote controller, the cooling or heating operation signal starts being transferred form the indoor controller to the outdoor unit.
  • Page 39 +1.0 *5 : Fan speed = (M + –L) x 1/4 + L +0.5 (Linear approximation L(W7) from M+ and L) (Table 1) Indoor fan air flow rate Fan speed level RAS-B05S4KVG-E RAS-B07S4KVG-E Mode Cooling Heating Cooling Heating Cool Heat...
  • Page 40: Indoor Fan Motor Control

    Item Operation flow and applicable data, etc. Description 2. Indoor fan motor control Fan speed level Mode RAS-B10S4KVG-E RAS-B13S4KVG-E Cooling Heating Cooling Heating Cool Heat Fan speed Air flow rate Fan speed Air flow rate Fan speed Air flow rate Fan speed Air flow rate (rpm)
  • Page 41 Item Operation flow and applicable data, etc. Description 2. Indoor fan <In heating operation> 1) When setting the fan speed to L, motor control L+, M, M+ or H on the remote controller, the operation is per- formed with the constant speed HEAT ON shown in Fig.
  • Page 42: Outdoor Fan Motor Control

    Item Operation flow and applicable data, etc. Description 3. Outdoor fan The blowing air volume at the outdoor unit side is controlled. 1) The operation command sent motor control from the remote controller is Receiving the operation command from the controller of processed by the indoor unit indoor unit, the controller of outdoor unit controls fan speed.
  • Page 43: Capacity Control

    Item Operation flow and applicable data, etc. Description 3. Outdoor fan motor control In cooling operation In heating operation Hz < 25.2 25.2 ≤ Hz < 66.0 RAS-16E2AVG-E RAS-16E2AVG-E 66.0 ≤ Hz 60.6 ≤ Hz Compressor speed Compressor speed Hz < 31.8 31.8 ≤...
  • Page 44: Current Release Control

    Item Operation flow and applicable data, etc. Description 5. Current release This function prevents troubles on the electronic parts of the 1) The input current of the outdoor control compressor driving inverter. unit is detected in the inverter section of the outdoor unit. This function also controls drive circuit of the compressor speed so that electric power of the compressor drive circuit 2) According to the detected...
  • Page 45: Release Protective Control By Temperature Of Indoor Heat Exchanger

    Item Operation flow and applicable data, etc. Description 1) When temperature of the indoor 6. Release protective <In cooling/dry operation> control by tempera- heat exchanger drops below 5°C, (Prevent-freezing control for indoor heat exchanger) the compressor speed is ture of indoor heat In cooling/dry operation, the sensor of indoor heat exchanger reduced.
  • Page 46: Defrost Control (Only In Heating Operation)

    Item Operation flow and applicable data, etc. Description 7. Defrost control (This function removes frost adhered to the outdoor The necessity of defrost operation is heat exchanger.) detected by the outdoor heat exchanger (Only in heating operation) temperature. The conditions to detect the The temperature sensor of the outdoor heat ex- necessity of defrost operation differ in A, changer (Te sensor) judges the frosting status of the...
  • Page 47: Louver Control

    Item Operation flow and applicable data, etc. Description 8. Louver control This function controls the air direction of the indoor unit. 1) Louver • The position is automatically controlled according to the operation position mode (COOL/HEAT). • The set louver position is stored in memory by the microcomputer, and the louver returns to the stored position when the next operation is performed.
  • Page 48: Eco Operation

    Item Operation flow and applicable data, etc. Description 9. ECO When pressing [ECO] button on the remote controller, a <Cooling operation> operation Economic operation is performed. 1) The control target temperature <Cooling operation> increase 0.5ºC per hour up to 2ºC This function operates the air conditioner with the difference starting from the set temperature between the set and the room temperature as shown in the...
  • Page 49: Temporary Operation

    Item Operation flow and applicable data, etc. Description Pressing [RESET] button starts the temporary opera- 1) When pressing [RESET] button, the 10. Temporary operation tion of [AUTO] operation. When keeping [RESET] temporary [AUTO] operation starts. button pressed for 10 seconds or more, the temporary 2) When keeping [RESET] button pressed [COOL] operation is performed.
  • Page 50: Pulse Modulating Valve (P .M.v.) Control

    Item Operation flow and applicable data, etc. Description This function controls throttle amount of the 1) When starting the operation, move the 13. Pulse Modulating refrigerant in the refrigerating cycle. valve once until it fits to the stopper. (Initialize) valve (P.M.V.) According to operating status of the air conditioner, control this function also controls the open degree of valve...
  • Page 51: Self-Cleaning Function

    Item Operation flow and applicable data, etc. Description 14. Self-Cleaning 1. Purpose function The Self-Cleaning operation is to minimize the growth of mold, bacteria etc. by running the fan and drying so as to keep the inside of the air conditioner clean. Unit now performing cooling or dry operation Self-Cleaning operation When the cooling or dry operation shuts...
  • Page 52 Item Operation flow and applicable data, etc. Description 14. Self-Cleaning function 14-1-1. Self-Cleaning diagram Operation display FCU fan rpm is depend on presetting. (500RPM) FCU louver OPEN OPEN (12.7º) CLOSE ON or OFF ON or OFF Timer display depend on presetting of timer function. depend on presetting of timer function.
  • Page 53: Remote-A Or B Selection

    Item Operation flow and applicable data, etc. Description 1. Purpose 15. Remote-A or B Setting the remote controller This operation is to operate only one selection To separate using of remote control for each indoor unit in case of 2 air conditioner are installed nearly. indoor unit using one remote controller.
  • Page 54: Sound Level

    Item Operation flow and applicable data,etc Description 17. Silent Silent button on remote controller is pressed. This function is used when the user need Operation Silent 1: to keep silent at outdoor side. It is limit Cooling/heating capacity is limited maximum for maximum compressor speed and CDU 70% of rated.
  • Page 55: Quiet Mode

    Item Operation flow and applicable data,etc Description 19. QUIET mode When the "Quiet mode" selected from [ QUIET ] button; Quiet mode is the system which, control the The fan of the indoor unit will be restricted the revolving speed of indoor fan to work revolving speed at speed UL.
  • Page 56: Comfort Sleep Mode

    Item Operation flow and applicable data, etc. Description 21. COMFORT Cooling mode The principles of comfort sleep mode are: SLEEP mode • Quietness for more comfortable. When • The preset temperature will increase as room temperature reach setting temperature show on ECO operation (Item No. 9) •...
  • Page 57: Short Timer

    Item Operation flow and applicable data, etc. Description 23. Short Timer In the normal condition, after switching one circuit Purpose breaker, 3-minute delay time for compressor and To start the unit immediately for the purpose of 1 hour for plasma air purifier are set for the testing, trial...etc, short timer can be used.
  • Page 58: Auto Restart Function

    9-3. Auto Restart Function This indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with the set operating conditions in the event of a power supply being accidentally shut down. The operation will resume without warning three minutes after power is restored. This function is set to work when shipped from the factory.
  • Page 59: How To Set The Auto Restart Function

    9-3-2. How to Set the Auto Restart Function To set the auto restart function, proceed as follows: The power supply to the unit must be on ; the function will not set if the power is off. Press the [RESET] button located in the center of the front panel continuously for three seconds. The unit receives the signal and beeps three times.
  • Page 60: Remote Controller And Its Functions

    9-4. Remote Controller and Its Functions 9-4-1. Parts Name of Remote Controller 1 Infrared signal emitter 2 Start/Stop button ( 3 Mode select button ( 4 Temperature button ( 5 Fan speed button ( 6 Swing louver button ( SWING 7 Set louver button ( 8 8°C Heating Operation ( 8°C...
  • Page 61: Wireless Lan Connection

    Android : Version 5.0 or later. About Toshiba Home AC Control 1. Toshiba Home AC Control can control AC operation by Smartphone or tablet (mobile device) via internet connection. 2. Everywhere control, control software run on Cloud system and mobile device can set and monitor AC operation via internet connection.
  • Page 62 Open application and select Log in. Enter user name and Login successful. password. Add Wireless adapter for control by Toshiba Home AC Control application. Wireless adapter Built-in Active Wireless adapter by remote controller and Auto login. Select “Add AC (Adapter)” from both display above.
  • Page 63 Add Wireless adapter for control by Toshiba Home AC Control application. AC (adapter) connect Active Wireless adapter by Remote controller Press and hold MODE button 5 seconds Wireless LED mark will blink when AP mode active MODE MENU WPS mode...
  • Page 64 Toshiba Home AC Control application Home screen Weekly schedule Setting Menu Add AC Sub menu all AC All AC On/Off  Add Group  Delete Group Group AC On/Off  Operation Setting Each AC On/Off Sub menu all AC  Select AC ...
  • Page 65 Mode and Condition setting. Enter operation mode of All AC Enter operation mode of Group AC Enter operation mode of each AC Mode select for Toshiba Home AC Control application. Provide for 5 operation modes Auto Cool Heat Fan only...
  • Page 66 Setting in operation mode. Tab for select AC Weekly schedule OFF-ON timer set 0.5-12hrs. Mode select OFF-ON Timer set Temperature set Indoor temperature Outdoor temperature ON timer set from Off mode only Fan speed set Louver set Special feature Off mode - 66 -...
  • Page 67 Group operation. Maximum 3 groups 1 Group maximum = 16 units. Add group Add AC in group Delete AC in group Please make sure Factory Reset is performed before deleting AC from mobile application. (See owner manual ʺPress and hold MODE button on remote control for 5 second and active dL functionʺ) - 67 -...
  • Page 68 Weekly schedule set. Day select Monday - Sunday Weekly schedule of all AC unit Weekly schedule of all AC unit Time select Weekly schedule set for each unit Mode select Select program for active by tick at select box Weekly schedule cancel. Weekly schedule not set Weekly schedule...
  • Page 69 Energy monitoring Select Room for Energy monitoring Select Energy monitoring Energy monitoring display Set cost calculate and currency Select Energy monitoring display Export data and send by Email ● The power consumption displayed is just an estimate as it is calculated simply. It may sometimes differ from the result measured by the power meter.
  • Page 70 In case of have some problem can check from Help menu. Note : ‘‘ The Wireless Adapter must be installed, maintained, repaired and removed by a qualified installer or qualified service person.” ‘‘Contact dealer and/or service center when equipment is malfunction.” - 70 -...
  • Page 71 5. Hi-POWER OPERATION To automatically control room temperature and airflow for faster cooling or heating operation (except in DRY and FAN ONLY mode) Press : Start and stop the operation. Hi POWER 6. ECO OPERATION To automatically control room temperature to save energy (except in DRY and FAN ONLY mode) Press : Start and stop the operation.
  • Page 72: Quiet Operation

    10. AUTO RESTART FUNCTION SETTING This product is designed so that, after a power failure, it can restart automatically in the same operating mode as before the power failure. Information The product is shipped with Auto Restart function in the ON position. Turn it OFF if this function is not required. How to turn OFF the Auto Restart Function Press and hold the [OPERATION] button on the indoor unit for 3 seconds (3 beep sounds but OPERATION lamp does not blink).
  • Page 73: Name And Functions Of Indications On Remote Controller

    15. MANUAL DEFORST OPERATION To defrosting the heat exchanger of the outdoor unit during Heating operation. Press and hold : for 5 sec. then remote control display will show [    ] as picture 1 for 2 sec. 9-4-3. Name and Functions of Indications on Remote Controller All indications, except for the clock time indicator, are displayed by pressing the button.
  • Page 74: Installation Procedure

    10. INSTALLATION PROCEDURE 10-1. Installation Diagram of Indoor and Outdoor Units RAS-B05, 07, 10S4KVG-E RAS-B13, 16, 18S4KVG-E For the rear left, bottom left and left piping Wall Hook Installation plate Cut out a piece of SPACER from indoor unit packaging box, roll it and insert between the indoor unit and wall to tilt Flat head wood screw...
  • Page 75: Optional Installation Parts

    10-2. Installation 10-2-1. Optional installation parts Part Parts name Q’ty code Refrigerant piping Liquid side : Ø6.35 mm Gas side : Ø9.52 mm (RAS-B05, 07, 10, 13S4KVG-E) each : Ø12.70 mm (RAS-B16, 18S4KVG-E) Pipe insulating material (polyethylene foam, 6 mm thick) For RAS-B05, 07, 10, 13S4KVG-E (polyethylene foam, 8 mm thick) For RAS-B16, 18S4KVG-E...
  • Page 76: Accessory And Installation Parts

    10-2-2. Accessory and installation parts Indoor Unit Part name Part name Installation plate × 1 Wireless remote controller × 1 Battery × 2 Remote controller holder × 1 Ultra Fresh filter × 1 Mounting screw × 6 Flat head wood screw × 2 Owner’s Manual ×...
  • Page 77 10-2-3. Installation/Servicing Tools Changes in the product and components In the case of an air conditioner using R32, in order to prevent any other refrigerant from being charged accidentally, the service port diameter of the outdoor unit control valve (3 way valve) has been changed. (1/2 UNF 20 threads per inch) •...
  • Page 78: Indoor Unit

    10-3-2. Cutting a hole and mounting installation Plate 10-3. Indoor Unit 10-3-1. Installation place <Cutting a hole> • A place which provides the spaces around the indoor When installing the refrigerant pipes from the rear. unit as shown in the diagram •...
  • Page 79 <When the installation plate is directly mounted on Space allows for moving range of the air inlet grille • the wall> and horizontal louver in operation above curtain rails, window cornice or other objects. 1. Securely fit the installation plate onto the wall by screwing it in the upper and lower parts to hook up (Unit : mm) the indoor unit.
  • Page 80: How To Connect Remote Controller For Wire Operation

    <For remote controller> 10-3-3. How to Connect Remote Controller for Wire Operation 1. Remove cover of remote controller by sliding down and take it out. 2. If batteries are exist, please take them out. Indoor unit The combination of using wire controller and batteries may cause of batteries explosion.
  • Page 81: Piping And Drain Hose Installation

    *Remark : 1. Recommend to use double insulation <How to remove the drain hose> lead wire for connect remote control and • The drain hose can be removed by removing air conditioner. the screw securing the drain hose and then 2.
  • Page 82: Indoor Unit Fixing

    CAUTION <In case of right or left piping> • After scribing slits inside of the front panel with a knife or • Bind the auxiliary pipes (two) and connecting a making-off pin, cut them with a pair of nippers or an cable with facing tape tightly.
  • Page 83: Outdoor Unit

    10-3-6. Drainage 10-4. Outdoor Unit 1. Run the drain hose sloped downwards. 10-4-1. Installation place • A place which provides the spaces around the NOTE outdoor unit as shown in the diagram • Hole should be made at a slight downward slant on •...
  • Page 84: Precautions About Installation In Regions With Snowfall And Cold Temperatures

    10-4-2. Precautions about installation in Regions Draining the Water with Snowfall and Cold Temperatures Install the drain nipple and a commercially available drain hose (with 16 mm inside diameter), and drain off • Do not use the supplied drain nipple for draining the water.
  • Page 85 Evacuating <Tightening connection> Align the centers of the connecting pipes and tighten After the piping has been connected to the indoor unit, the flare nut as far as possible with your fingers . Then you can perform the air purge together at once. tighten the nut with a spanner and torque wrench as shown in the figure.
  • Page 86: Vacuum Pump

    CAUTION • Securely tighten the valve cap with torque in the following table • KEEP IMPORTANT 7 POINTS FOR PIPING WORK Take away dust and moisture (inside of the Cap Size (H) Torque connecting pipes). 14~18 N.m Tighten the connections (between pipes and unit). H17 - H19 Valve Rod (1.4 to 1.8 kgf·m)
  • Page 87: Electrical Works

    10-5. Electrical works Model RAS-B05S4KVG-E RAS-B07S4KVG-E RAS-B10S4KVG-E RAS-B13S4KVG-E RAS-B16S4KVG-E RAS-B18S4KVG-E 50Hz, 220 – 240V Single phase Power source Maximum running current 5.0A 5.4A 7.2A 7.4A 9.0A 9.25A Circuit breaker rating Power supply cable H07RN-F or 60245 H07RN-F or 60245 IEC66 H07RN-F or 60245 IEC66 (1.25 mm...
  • Page 88 10-5-2. Power Supply and Connecting Cable Connection In Case of Indoor Unit Connect With 1:1 Outdoor Unit Power Supply Input at Outdoor Unit Terminal Block (Recommend) Indoor Unit Outdoor Unit Connecting cable Stripping length of the Connecting cable 1 2 3 connect to 1 2 3 connecting cable Terminal block...
  • Page 89 10-5-3. Power supply input Wiring Diagram for 1:1 Outdoor Unit Power input at Outdoor Terminal Block (Recommend) Indoor Terminal Block Outdoor Terminal Block Power input Power input at Indoor Terminal Block (Optional) Indoor Terminal Block Power input Outdoor Terminal Block CAUTION 1.
  • Page 90 10-5-4. In Case of Indoor Unit Connect With Inverter Multi System (IMS) Indoor Unit Connecting cable Stripping length of the Connecting cable connect to 1 2 3 Connecting cable Terminal block Earth line 50 mm 10 mm 10 mm Earth line 70 mm Connecting cable...
  • Page 91 10-6. Others Note : 1. Repeat previous step to reset Remote Control to be A. 10-6-1 . Gas leak test 2. Remote Control A have not “A” display. 3. Default setting of Remote Control from factory is A. Check places for the indoor unit F ig.
  • Page 92 10-6-4. Auto Restart Function Setting This product is designed so that, after a power failure, it can restart automatically in the same operating mode as before the power failure. Information The product is shipped with Auto Restart function in the ON position.
  • Page 93: How To Diagnose The Trouble

    11. HOW TO DIAGNOSE THE TROUBLE The pulse motor circuits are mounted to both indoor and outdoor units. Therefore, diagnose troubles according to the trouble diagnosis procedure as described below. (Refer to the check points in servicing written on the wiring diagrams attached to the indoor/outdoor units.) Table 11-1 Troubleshooting Procedure...
  • Page 94 RAS-16, 18E2AVG-E Compressor WP-044 IPM Module Fan motor Shared potential Driver Amplifier FET x 6 Driver Amplifier Fig. 11-2 CAUTION A high voltage (equivalent to the supply voltage) is also energized to ground through the sensors, PMV and other low-voltage circuits. The sensor leads and other wires are covered with insulated tubes for protection.
  • Page 95 K Precautions when inspecting the control section of the outdoor unit NOTE : A large-capacity electrolytic capacitor is used in the outdoor unit controller (inverter). Therefore, if the power supply is turned off, charge (charging voltage DC280 to 380V) remains and discharging takes a lot of time. After turning off the power source, if touching the charging section before discharging, an electrical shock may be caused.
  • Page 96: First Confirmation

    11-1. First Confirmation 11-1-1. Confirmation of Power Supply Confirm that the power breaker operates (ON) normally. 11-1-2. Confirmation of Power Voltage Confirm that power voltage is AC 220–230–240 ± 10%. If power voltage is not in this range, the unit may not operate normally. 11-1-3.
  • Page 97: Primary Judgment

    11-2. Primary Judgment To diagnose the troubles, use the following methods. 1) Judgment by flashing LED of indoor unit 2) Self-diagnosis by service check remote controller 3) Judgment of trouble by every symptom Firstly use the method 1) for diagnosis. Then, use the method 2) or 3) to diagnose the details of troubles. 11-3.
  • Page 98: Self-Diagnosis By Remote Controller (Check Code)

    11-4. Self-Diagnosis by Remote Controller (Check Code) 1. If the lamps are indicated as shown B to E in Table 11-3-1, execute the self-diagnosis by the remote controller. 2. When the remote controller is set to the service mode, the indoor controller diagnoses the operation condition and indicates the information of the self-diagnosis on the display of the remote controller with the check codes.
  • Page 99 11-4-2 Caution at Servicing 1. After using the service mode of remote controller finished, press the [ ] button to reset the remote controller to normal function. 2. After finished the diagnosis by the remote controller, turn OFF power supply and turn its ON again to reset the air conditioner to normal operation.
  • Page 100 Block distinction Operation of diagnosis function Action and Judgment Check Check Display flashing Block Cause of operation conditioner code code error status 1) Defective wiring of the 1) to 3) The outdoor unit never operate. Serial signal Indoor unit Flashes when and connecting operates error is detected.
  • Page 101 Block distinction Operation of diagnosis function Action and Judgment Check Check Display flashing Block Cause of operation conditioner code error code status Outdoor P.C. All OFF Flashes after 1. Remove connecting lead wire of the Current on inverter circuit is board error is detected over limit in short time.
  • Page 102 Operation of diagnosis function Block distinction Action and Judgment Check Check Display flashing Block Cause of operation conditioner code code error status Outdoor P.C. Compressor drive output error. 1. Check installation conditions such as All OFF Flashes after board error is detected (Relation of voltage, current and packed valve opening, refrigerant 8 times*.
  • Page 103 Block distinction Operation of diagnosis function Action and Judgment Display flashing Check Check Block Cause of operation conditioner code code error status The others All OFF Flashes after Compressor does not rotate. 1. Remove connecting lead wire of the (including Because of missed wiring, error is detected compressor, and operate again.
  • Page 104 Block distinction Operation of diagnosis function Action and Judgment Display flashing Check Check Block Cause of operation conditioner code code error status The others Return signal of the outdoor Indoor unit Flashes when 1. Check power supply (Rate +10%) 2. If the air conditioner repeat operate (including unit has been sent when operates...
  • Page 105: Judgment Of Trouble By Every Symptom

    11-5. Judgment of Trouble by Every Symptom 11-5-1. Indoor Unit (Including Remote Controller) (1) Power is not turned on (Does not operate entirely) <Primary check> 1. Is the supply voltage normal? 2. Is the normal voltage provided to the outdoor unit? 3.
  • Page 106 (2) Only the indoor motor fan does not operate <Primary check> 1. Is it possible to detect the power supply voltage (AC220–240V) between on the terminal block? 2. Does the indoor fan motor operate in cooling operation? (In heating operation, the indoor fan motor does not operate for approximately 10 minutes after it is turned on, to prevent a cold air from blowing in.) Turn off power supply once, and...
  • Page 107 Is it possible to Does check display Replace change airflow level remote on remote show high? to “HIGH”? Change the new PC Replace board. Does fan speed motor change? Fan motor operates normally. Is it possible to Does check cross-flow Replace bearing rotate cross-flow fan by fan bearing normal...
  • Page 108 (3) Indoor fan motor automatically starts to rotate by turning on power supply [For DC fan motor] <Cause> The IC is built in the indoor fan motor. Therefore the P.C. board is also mounted to inside of the motor. If the P.C. board is soldered imperfectly or the IC is defective, the fan motor may automatically rotate by turning on power supply.
  • Page 109 (4) Troubleshooting for remote controller <Primary check> Check that A or B selected on the main unit is matched with A or B selected on the remote controller. There is no beep from the indoor unit Push the [ ] button. The OPERATION lamp of the air conditioner main unit does not light Does the transmission...
  • Page 110 11-5-2. Wiring Failure (Interconnecting and Serial Signal Wire) (1) Outdoor unit does not operate 1) Is the voltage between R and S of the indoor terminal block varied? Confirm that transmission from indoor unit to outdoor unit is correctly performed based upon the following diagram.
  • Page 111 11-6. How to Check Simple the Main Parts <Check procedure> Gas leakage, Discharge temp. error, disconnection of TS/TC gas leakage sensors (Check code 02, 1C) (Check code 03, 1E) Valve drive check Is coil of the pulse motor valve Set it correctly. (P.M.V.) correctly set? Set it correctly.
  • Page 112: How To Diagnose Trouble In Outdoor Unit

    11-7. How to Diagnose Trouble in Outdoor Unit 11-7-1. Summarized Inner Diagnosis of Inverter Assembly (RAS-05, 07, 10, 13E2AVG-E) Table 11-7-1 Diagnosis/Process flowchart Item Contents Summary Preparation Turn “OFF” the power supply breaker, and remove 3P Remove connector connector which connects of compressor.
  • Page 113 (RAS-16, 18E2AVG-E) Diagnosis/Process flowchart Item Contents Summary Preparation Turn “OFF” the power supply breaker, and remove 3P Remove connector connector which connects of compressor. inverter and compressor. If fuse was blown, be sure to Check • Check whether 25A fuse check the electrolytic Check 25A fuse on the control board...
  • Page 114: How To Check Simply The Main Parts

    Diagnosis/Process flowchart Item Contents Summary Check Check winding resistance between phases of compressor, and resistance between outdoor frames by using a tester. • Is not grounded. → OK if 20MΩ or more Replace control board assembly.  • Is not short-circuited →...
  • Page 115: Check Procedures

    (3) Check procedures Table 11-8-1 Procedure Check points Causes Turn off the power supply breaker Check whether or not the fuse (F01) Impulse voltage was applied or the and remove the P.C. board is blown. indoor fan motor short-circuited. assembly from electronic parts base.
  • Page 116 11-8-2. P.C. Board Layout (RAS-B05,07,10,13,16S4KVG-E) +12V [1] Sensor characteristic table : Discharge temp. sensor : Room temp. sensor TC, TCJ : Heat exchanger temp. sensor : Outdoor temp. sensor : Suction temp. sensor TA, TC, TO, TS,TCJ, TE : Outdoor heat exchanger temp sensor Temperature (˚C) - 116 -...
  • Page 117: Sensor Characteristic Table

    (RAS-B18S4KVG-E) CN21 CN36 CN32 Main Electrolyte HA1 Connector Fan Motor Stepping motor Fuse Capacitor (Wireless Adapter) Connector DB01 Diode Bridge Rectifier CN30 Power supply Input terminal (Line) Fuse CN10 Display R-03 Connector Resistor CN22 HA2 Connector L-01 (Window Switch and Line Filter RAC interface) CN31...
  • Page 118 11-8-3. Indoor Unit (Other Parts) Part name Checking procedure Room temp. (TA) sensor Disconnect the connector and measure the resistance value with tester. Heat exchanger (TC, TCJ) (Normal temp.) sensor Temperature 10°C 2 ° 0 C 2 ° 5 C 3 °...
  • Page 119: Checking Procedure

    11-8-5. Checking Method for Each Part Part name Checking procedure Electrolytic capacitor 1. Turn OFF the power supply breaker. 2. Discharge all three capacitors completely. 3. Check that safety valve at the bottom of capacitor is not broken. 4. Check that vessel is not swollen or exploded. 5.
  • Page 120: How To Simply Judge Whether Outdoor Fan Motor Is Good Or Bad

    11-9. How to Simply Judge Whether Outdoor Fan Motor is Good or Bad 1. Symptom • Outdoor fan motor does not rotate. • Outdoor fan motor stops within several tens seconds though it started rotating. • Outdoor fan motor rotates or does not rotate according to the position where the fan stopped, etc. Remote controller check code “02 : Outdoor block, 1A : Outdoor fan drive system error”...
  • Page 121: How To Replace The Main Parts

    12. HOW TO REPLACE THE MAIN PARTS WARNING • Since high voltages pass through the electrical parts, turn off the power without fail before proceeding with the repairs. Electric shocks may occur if the power plug is not disconnected. • After the repairs have been completed (after the front panel and cabinet have been installed), perform a test run, and check for smoking, unusual sounds and other abnormalities.
  • Page 122 Part name Procedures Remarks Front panel 1) Stop operation of the air conditioner and turn Front panel Type : A (For 05,07,10k) off its main power supply. 2) Securely remove two screws at the front panel. Type A: Open the air inlet grille upward. Type B: Open two screw caps.
  • Page 123: Fan Motor

    Part name Procedures Remarks Horizontal louver 1) Remove shaft of the horizontal louver Type : A (For 05,07,10k) from drain pan. Type A: Push 1 the center arm then remove the other shafts. Type B: Push 2 the center arm then remove the other shafts.
  • Page 124: Drain Pan

    Part name Procedures Remarks Drain pan 1) Follow the procedure item 3 . assembly 2) Remove screw holding the electric part cover. Connectors P.C.board Louver motor connector Screw Electric part cover 3) Disconnect the louver motor connector (5P) from P.C. board assembly. 4) Remove fixing screws of the unit display and remove unit display.
  • Page 125: Drain Pan Assembly

    Part name Procedures Remarks Drain pan Type : B (For 13,16,18k) assembly Drain pan Back body Back body Rib of drain pan Center arm Rib of drain pan Drain pan of drain pan Drain pan Back body Drain hose 1) Follow the procedure item 3 . 2) The drain hose can be removed by removing the screw securing the drain hose and then pulling out the drain hose.
  • Page 126 Part name Procedures Remarks Cross flow fan 1) Follow the procedure item 3 and 4 . Type : A (For 05,07,10k) 2) Loosen the set screw of the cross flow fan. 3) Condition for remove bearing base Heat exchanger Hins seal eva Type A: Remove 2 fixing screws from bearing base after that remove it by hold, press and Screw...
  • Page 127 Part name Procedures Remarks Heat exchanger 1) Follow the procedure in item 3 and 4 . Type : A (For 05,07,10k) (Evaporator) 2) Remove 2 fixing screws at the left side of Hins seal eva the heat exchanger. 3) Remove fixing screw at the upper right side of the heat exchanger.
  • Page 128 Part name Procedures Remarks <To re-installation> In case of evaporator is assembled with evaporator hins seal : - Put the evaporator hins seal on the body back before assembly the heat exchanger. - Please keep assembly heat exchanger follow figure as below : Heat exchanger Evaporator hins seal Cross flow fan...
  • Page 129 Microcomputer Part name Procedure Remarks Common procedure 1) Turn the power supply off to stop the Replace terminal block,  operation of air-conditioner. microcomputer ass’y and the P .C. board ass’y. 2) Remove the front panel. • Remove the 2 fixing screws. 3) Remove the electrical part base.
  • Page 130 12-2. Outdoor Unit (RAS-05, 07, 10, 13E2AVG-E) Part name Procedures Remarks Common 1. Detachment procedure 1) Stop operation of the air conditioner, and turn off the main switch and breaker of the air conditioner. 2) Remove the valve cover. (ST2T∅4 x 10L 1 pc) •...
  • Page 131 Part name Procedure Remarks Inverter module cover 1) Perform work of item 1 in  Inverter ƒ assembly 2) Remove screw (ST2TØ4×10L 2 pcs.) of the upper part of the front cabinet. • Disconnect connectors all connector on P.C. board. •...
  • Page 132 Part name Procedures Remarks „ Fan motor 1) Perform work of item 1 of 1 and 1 of 2. 2) Remove the flange nut fixing the fan motor Fan motor and the propeller fan. Propeller fan • Flange nut is loosened by turning clockwise.
  • Page 133 Part name Procedures Remarks Fan guard 1. Detachment 1) Perform work of item 1 of 1 and 1 of 2. Requirement: Perform the work on a corrugated cardboard, cloth, etc. to prevent scratches to the product. 2) Remove the front cabinet, and place it down so that the fan guard side faces downwards.
  • Page 134 Part name Procedure Remarks Control board 1. Disconnect the leads and connectors connected to assembly the other parts from the control board assembly. 1) Leads • 3 leads (black, white, orange) connected to terminal block. • Lead connected to compressor : Disconnect the connector (3P).
  • Page 135 Outdoor unit (RAS-16, 18E2AVG-E) Part name Procedures Remarks Common procedure 1. Detachment NOTE Upper cabinet Wear gloves for this job. Otherwise, you may injure your hands on the parts, etc. 1) Stop operation of the air conditioner, and turn off the main switch of the breaker for air conditioner.
  • Page 136 Part name Procedures Remarks 1. Detachment Front cabinet 1) Perform step 1 in 1. 2) Remove the fixing screws (ST2TØ4 × 10L 2 pcs.) used to secure the front cabinet and inverter cover, the screws (ST2TØ4 × 10L 4 pcs.) used to secure the front cabinet at the bottom, and the fixing screws (ST2TØ4 ×...
  • Page 137 Part name Procedures Remarks Inverter assembly 1) Perform work of item 1 in 1. 2) Remove screw (ST2TØ4 × 10L 2 pcs.) of the upper part of the front cabinet. • If removing the inverter cover in this condition, P.C. board can be checked. •...
  • Page 138 Part name Procedures Remarks Control board assembly 1. Disconnect the leads and connectors connected to the other parts from the control board CN600 CN603 CN300 CN601 CN703 assembly. 1) Leads CN700 CN602 • 3 leads (black, white, orange) connected to terminal block. •...
  • Page 139 Part name Procedures Remarks Side cabinet 1. Side cabinet (right) 1) Perform step 1 in 2 and all the steps in 3. 2) Remove the fixing screw (ST2TØ4 × 10L 4 pcs.) used for securing the side cabinet to the bottom plate and valve fixing panel 2.
  • Page 140 Procedures Part name Remarks Compressor 1) Perform work of item 1 of 1 and 2, 3, 4, 5. 2) Extract refrigerant gas. 3) Remove the partition board. (ST2TØ4 × 10L 3 pcs.) 4) Remove the sound-insulation material. 5) Remove terminal cover of the compressor, and disconnect lead wire of the compressor from the terminal.
  • Page 141 Part name Procedures Remarks 1. Detachment Electronic expansion valve coil 1) Perform step 1 in 1, all the steps in 2 and 1 in 5. 2) Turn the coil by 180 degrees then remove by pull it upward. 2. Attachment 1) Insert the coil at position which perpendicular with pipe of PMV then turn the coil by 180 degrees.
  • Page 142 Part name Procedures Remarks TE sensor (outdoor heat exchanging temperature sensor) " • Attachment Install the sensor onto the straight pipe part of the condenser output pipe. TS sensor (Suction pipe temperature sensor) • Attachment Install the senser onto the straight pipe part of the suction pipe. Be careful for the lead direction of the sensor.
  • Page 143: Exploded Views And Parts List

    13. EXPLODED VIEWS AND PARTS LIST 13-1. Indoor Unit RAS-B05,07,10S4KVG-E ELECTRICAL PARTS ASSEMBLY Location Part Location Part Description Description 43T00865 FRONT PANEL ASSY 43T44765 REFRIGERANT CYCLE ASSEMBLY 43T09612 GRILLE OF AIR INLET ASSY (FOR RAS-B10S4KVG-E) 43T80368 AIR FILTER 43T39446 EVAPORATOR HINS SEAL 43T03426 BACK BODY ASSY (FOR RAS-B05,07S4KVG-E)
  • Page 144 RAS-B13,16,18S4KVG-E ELECTRICAL PARTS ASSEMBLY Location Part Location Part Description Description 43T00863 FRONT PANEL ASSY 43T44767 REFRIGERANT CYCLE ASSEMBLY 43T09613 GRILLE OF AIR INLET ASSY (FOR RAS-B16S4KVG-E) 43T80357 AIR FILTER 43T44830 REFRIGERANT CYCLE ASSEMBLY 43T03417 BACK BODY ASSY (FOR RAS-B13S4KVG-E) 43T22343 VERTICAL LOUVER ASSY 43T19333 HOLDER, SENSOR...
  • Page 145 (FOR RAS-B18S4KVG-E) 43T62340 CORD-CLAMP 43T60502 HOUSING-WiFi 43T6W440 PC BOARD ASSY:WRS-LED 43T50603 TEMPERATURE SENSOR 43TN9500 PC BOARD (WP-048) (FOR RAS-B05,07,10,13,16S4KVG-E) (FOR RAS-B05S4KVG-E) 43T60605 TEMPERATURE SENSOR 43TN9502 PC BOARD (WP-048) (FOR RAS-B18S4KVG-E) (FOR RAS-B07S4KVG-E) 43TN9504 PC BOARD (WP-048) (FOR RAS-B10S4KVG-E) - 145 -...
  • Page 146 13-3. Outdoor Unit RAS-05, 07, 10E2AVG-E 37,41 36,40 Location Part Location Part Description Description 43T42388 BASE PLATE ASSEMBLY 43T47403 BONNET, 6.35 DIA 43T00733 UPPER CABINET ASSEMBLY 43T47404 BONNET, 9.52 DIA 43T00682 FRONT CABINET ASSEMBLY 43T46540 VALVE; PACKED 6.35 DIA 43T00448 FIXING PLATE VALVE 43T46541 VALVE;...
  • Page 147 RAS-13E2AVG-E 37,41 36,40 Location Part Location Part Description Description 43T42388 BASE PLATE ASSEMBLY 43T46540 VALVE; PACKED 6.35 DIA 43T00734 UPPER CABINET ASSEMBLY 43T46541 VALVE; PACKED 9.52 DIA 43T00683 FRONT CABINET ASSEMBLY 43T46469 BODY PMV 43T00448 FIXING PLATE VALVE 43T63360 COIL PMV 43T39334 MOTOR BASE CONNECTION PLATE 43T46470...
  • Page 148 RAS-16E2AVG-E Location Part Location Part Description Description 43T42382 BASE PLATE ASSEMBLY 43T46540 VALVE; PACKED 6.35 DIA 43T00459 LEFT CABINET 43T46461 VALVE; PACKED 12.7 DIA 43T00690 RIGHT CABINET ASSEMBLY 43T46469 BODY PMV 43T00735 UPPER CABINET ASSEMBLY 43T63360 COIL PMV 43T00688 FRONT CABINET ASSEMBLY 43T46470 4 WAY VALVE 43T00448...
  • Page 149 RAS-18E2AVG-E 37,41 Location Part Location Part Description Description 43T42382 BASE PLATE ASSEMBLY 43T46540 VALVE; PACKED 6.35 DIA 43T00459 LEFT CABINET 43T46461 VALVE; PACKED 12.7 DIA 43T00690 RIGHT CABINET ASSEMBLY 43T46469 BODY PMV 43T00735 UPPER CABINET ASSEMBLY 43T63360 COIL PMV 43T00688 FRONT CABINET ASSEMBLY 43T46470 4 WAY VALVE...
  • Page 150 13-4. Outdoor Unit (Part-E) RAS-05, 07, 10, 13E2AVG-E Location Part Location Part Description Description 43T67311 HEATSINK 43T60459 FUSE 43TN9512 PC BOARD (WP-043) 43T50412 TC-SENSOR (FOR RAS-05E2AVG-E) 43T50334 TEMPERATURE SENSOR 43TN9513 PC BOARD (WP-043) 43T50352 TEMPERATURE SENSOR (FOR RAS-07E2AVG-E) 43T50360 TC-SENSOR(TO) 43TN9514 PC BOARD (WP-043) 43T95304...
  • Page 151 RAS-16E2AVG-E Location Part Location Part Description Description 43T62351 HEATSINK 43T50360 TC-SENSOR(TO) 43TN9516 PC BOARD (WP-044) 43T62313 PC PLATE BASE 43T60392 TERMINAL-5P 43T63318 HOLDER SENSOR 43T60326 FUSE 43T63316 HOLDER,SENSOR 43T50412 TC-SENSOR 43T63317 HOLDER,SENSOR 43T50334 TEMPERATURE SENSOR 43T62401 TUBE 43T50352 TEMPERATURE SENSOR - 151 -...
  • Page 152 RAS-18E2AVG-E Location Part Location Part Description Description 43T67310 HEATSINK 43T50360 TC-SENSOR(TO) 43TN9517 PC BOARD (WP-044) 43T62313 PC PLATE BASE 43T60392 TERMINAL-5P 43T63318 HOLDER SENSOR 43T60326 FUSE 43T63316 HOLDER,SENSOR 43T50412 TC-SENSOR 43T63317 HOLDER,SENSOR 43T50334 TEMPERATURE SENSOR 43T62401 TUBE 43T50352 TEMPERATURE SENSOR - 152 -...
  • Page 153 CARRIER AIR CONDITIONING (THAILAND) CO., LTD. 144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI, AMPHUR MUANGPATHUMTHANI, PATHUMTHANI 12000, THAILAND...

Table of Contents