2. SAFETY AND WARNINGS All persons who are responsible for mounting, installation, commissioning, maintenance, tests, and service of WESTERN CO inverter products must be suitably trained and qualified for corresponding operations. They MUST be experienced and have knowledge of operation safety and professional methods. All installation personnel must have knowledge of all applicable safety information, standards, directives, and regulations.
Align the terminal lug with the grounding conductor and the ground washer on the screw. The teeth of the ground washer must be facing the housing. Tighten it firmly into the housing (Use M5 terminal、M5 screw .screwdriver type: T25, torque: 2.5Nm). W-HPT PRO 3K/6K/8K/10K/15K USER MANUAL...
5.2.1 AC Commissioning 5.2.2 AC Switch Types Please install an individual 2-stage miniature circuit breaker according to the following specifications. Model Maximum output current(A) AC Breaker Rated current(A) W-HPT-3000P W-HPT-6000P W-HPT-8000P 12.8 W-HPT-10000P 15.9 W-HPT-15000P 23.9 W-HPT PRO 3K/6K/8K/10K/15K USER MANUAL...
This product is equipped with residual current protection device internally, in accordance with IEC 60364-7-714. An external residual current protection device is not needed. If the local regulation demands otherwise, it is recommended to install a 300mA Type B residual current protection device. W-HPT PRO 3K/6K/8K/10K/15K USER MANUAL...
For user guidance and configuration of Wi-Fi Stick, please refer to the corresponding Wi-Fi Stick Guide manual, which is available in printed form inside Documents pack, or on Western CO. website at www.western.it/en 6.1.2 RS485/Smart Meter/DRED Connection W-HPT PRO 3K/6K/8K/10K/15K USER MANUAL...
10. Grounding Resistance: Check if the grounding resistance of PV strings >1M0hm using a multimeter. After all installation and checks, close the AC circuit-breaker, then the DC switch. The inverter will start to operate when DC input voltage and grid conditions meet the requirements of inverter startup. W-HPT PRO 3K/6K/8K/10K/15K USER MANUAL...
When the inverter operates, LED symbols on display have the following meanings: 7.3 Display and Control Logics When inverter starts up and operates, there is a control button beside LCD Display of the inverter. Please follow the logics listed below: W-HPT PRO 3K/6K/8K/10K/15K USER MANUAL...
Disconnect all DC connections and resources. Unplug the DC connectors, and DO NOT pull the cables. Use multimeter to ensure the voltage on DC terminals of inverter is 0. Unscrew and remove the AC connector. W-HPT PRO 3K/6K/8K/10K/15K USER MANUAL...
Page 14
Danger to life due to high voltages. Inverter capacitors need 10 minutes to be completely de-energized. When an error occurs, DO NOT remove the cover of the inverter onsite. Improper operations and attempts may induce electric shock. W-HPT PRO 3K/6K/8K/10K/15K USER MANUAL...
Max. output current(A) Max. output overcurrent protection(A) Adjustable displacement power 0.8ind to 0.8cap factor <3% THDi at rated power EFFICIENCY 98.4% 98.4% 98.5% 98.5% 98.5% Max. Efficiency 97.4% 97.6% 97.6% 97.8% 97.8% Euro Efficiency >99.9% MPPT Efficiency W-HPT PRO 3K/6K/8K/10K/15K USER MANUAL...
Page 16
Operating ambient temperature range (°C) -30 ~ +60 0%~100% Allowable relative humidity range 2000(>2000 derating) Max. operating altitude(m) IP66 Degree of protection(IEC 60529) Climatic category (IEC 60721-3-4) 4K4H No-isolated Topology Power consuption <1(Without night monitoring), <6(With night monitoring) W-HPT PRO 3K/6K/8K/10K/15K USER MANUAL...
PV voltage than 1020V, it is the inverter. If the input voltage lies within the too high determined as permissible range while the fault occurs, please the PV voltage contact the service. is too high. W-HPT PRO 3K/6K/8K/10K/15K USER MANUAL...
Page 18
①whether the AC circuit breaker is disconnected ②whether the AC terminal or fuse is in good contact ③whether the power supply line is normal If this fault is still being shown, contact the service. W-HPT PRO 3K/6K/8K/10K/15K USER MANUAL...
Page 19
Disconnect the inverter from the utility grid and the Error, e.g. Micro CPU read PV array, and reconnect it after LED turns off. If this transition EEPROM failed fault is still being displayed, please contact the disturbance service. W-HPT PRO 3K/6K/8K/10K/15K USER MANUAL...
Page 20
AFCI error If this fault is still being displayed, please contact service. Check the connection of AFCI device. If the device is AFCI device connected normally while this fault occurs, please error contact the service. W-HPT PRO 3K/6K/8K/10K/15K USER MANUAL...
Section 6 when applicable (e.g. DC Wires need to be reassembled). Please run safety checks as described in Section 7 before closing the DC Switch and starting up again. W-HPT PRO 3K/6K/8K/10K/15K USER MANUAL...