SUPPORT INFORMATION Intrusion 2020-05-22 Seismic GM760 Issue: If the test input is activated on a GM760 and there is no GMXS1 connected, the detector will become very sensitive on the integration alarm and on the shock alarm. The was highlighted through one of our customers, who had incorrectly wired the test input on the GM760 detector which made it active and in turn causing false alarms.
Page 2
SUPPORT INFORMATION How to fix: If a detector is experiencing unwanted alarms, this could be due to the test input is active, with or without a GMXS1 fitted. Refer below for additional information. The Error Traps Error trap #1 As indicated in the above site report, the detectors can always be connected incorrectly, this is difficult for us to control but we should always ask if there is a connection into terminal 4.
Page 3
SUPPORT INFORMATION Image # 2 – Excerpt from GM760 installation manual Image # 3 – excerpt from the Seismic Application Guide TCC-2020-021_Seismic-GM760_320_01_EN...
Page 4
SUPPORT INFORMATION If you have any questions, please contact our Technical Competence Centre. Contact details can be found on our website.