BU 0800 – en
NORDAC ON (SK 300P series)
Manual with installation instructions

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NORDAC ON SK 300P Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Nord Drivesystems NORDAC ON SK 300P Series

  • Page 1 BU 0800 – en NORDAC ON (SK 300P series) Manual with installation instructions...
  • Page 2 NORDAC ON (SK 300P series) – Manual with installation instructions Read document and keep for future reference Read this document carefully prior to performing any work on the device and putting it into operation. It is essential to read and observe the instructions in this document. They serve as the prerequisite for smooth and safe operation and the fulfilment of any warranty claims.
  • Page 3: Version List

    Documentation Documentation Title: BU 0800 Order no.: 6078002 Series: SK 3xxP Device series: SK 300P, SK 301P, SK 310P, SK 311P, SK 350P Device types: SK 3xxP-360-340-A … SK 31xP-371-340-A 0.37 kW … 3.70 kW, 3 ~ 400 V Version list Title, Order number Software...
  • Page 4: Copyright Notice

    Any editing or amendment or other utilisation of the document is prohibited. Publisher Getriebebau NORD GmbH & Co. KG Getriebebau-Nord-Straße 1 • 22941 Bargteheide, Germany • http://www.nord.com Fon +49 (0) 45 32 / 289-0 • Fax +49 (0) 45 32 / 289-2253 Member of the NORD DRIVESYSTEMS Group BU 0800 en-3924...
  • Page 5 Publisher BU 0800 en-3924...
  • Page 6: Table Of Contents

    NORDAC ON (SK 300P series) – Manual with installation instructions Table of Contents General ............................... 10 Overview ............................11 Delivery ............................13 Scope of delivery..........................13 Presentation conventions ......................... 14 1.4.1 Warning information ......................14 1.4.2 Other information ........................ 14 1.4.3 Text markups ........................
  • Page 7 Table of Contents Starting up the device ........................57 Firmware update ..........................58 Selecting the operating mode for motor control ................58 4.3.1 Explanation of the operating modes (P300) ............... 58 4.3.2 Overview of controller parameter settings ................60 4.3.3 Motor control commissioning steps ..................
  • Page 8 NORDAC ON (SK 300P series) – Manual with installation instructions 8.9.6 Daisy chain hybrid cable ....................176 8.9.7 Sealing caps ........................176 8.9.8 Encoder cables ......................... 177 Maintenance and servicing information ....................178 Maintenance information ........................ 178 Service notes ..........................179 Disposal ............................
  • Page 9 1 General BU 0800 en-3924...
  • Page 10: General

    NORDAC ON (SK 300P series) – Manual with installation instructions 1 General The devices have sensorless current vector control with a wide range of settings. In combination with suitable motor models, which always provide an optimised voltage/frequency ratio, all three-phase asynchronous motors that are suitable for inverter operation and permanently excited synchronous motors can be driven.
  • Page 11: Overview

    1 General Information The device does not need to be opened at any time during its service life. All mounting, installation and commissioning works are only done on the closed device. • Assembly is done via freely accessible mounting holes. •...
  • Page 12 NORDAC ON (SK 300P series) – Manual with installation instructions Model NORDAC ON NORDAC ON NORDAC ON+ NORDAC ON PURE SK 30xP SK 30xP SK 31xP SK 350P 0.37–0.45 kW 0.37–3.7 kW 0.37–3.7 kW 0.37–1.5 kW Power 2–3 2–3 2–3 Size Integrated EMC mains filter ...
  • Page 13: Delivery

    1 General 1.2 Delivery Examine the device for transport damage or loose components immediately on delivery / unpacking. In case of damage, contact the carrier immediately and arrange for a careful survey. Important! This also applies if the packaging is undamaged. 1.3 Scope of delivery NOTICE Defect in the device...
  • Page 14: Presentation Conventions

    NORDAC ON (SK 300P series) – Manual with installation instructions 1.4 Presentation conventions 1.4.1 Warning information Warning information for the safety of users are marked as follows: DANGER This warning information warns of danger to persons that results in severe injuries or death. WARNING This warning information warns of danger to persons that could result in severe injuries or death.
  • Page 15: Text Markups

    1 General 1.4.3 Text markups The following markups are used to differentiate between various types of information: Text Type of information Example Markup Instructions Instructions whose sequence must be complied with are numbered consecutively. Enumerations • Enumerations are marked with a bullet point. P162 Parameters Parameters are indicated by a “P”...
  • Page 16 NORDAC ON (SK 300P series) – Manual with installation instructions The device is not equipped with a master mains switch and is thus always live when connected to mains voltage. Voltages may therefore be connected to a connected motor at standstill. A connected motor may also rotate if the drive is disconnected from the mains and possibly generate hazardous voltage.
  • Page 17 1 General In addition, the device and the accessories associated with it must only be installed and commissioned by a qualified electrician. A qualified electrician is a person who, because of his/her technical training and experience, has sufficient knowledge with regard to •...
  • Page 18 NORDAC ON (SK 300P series) – Manual with installation instructions The device must be protected against impermissible loads. In particular, components must not be deformed and/or insulation distances must not be changed. Touching of electronic components and contacts must be avoided. The device and its optional modules contain electrostatically sensitive components, which can be easily damaged by incorrect handling.
  • Page 19 1 General being switched off from the mains). Before starting the work, it is essential to check by measurement that all contacts of the power plug connectors or the connection terminals are voltage-free. Disposal The product and its parts and accessories must not be disposed of as domestic waste. At the end of its life, the product must be properly disposed of according to the local regulations for industrial waste.
  • Page 20: Warning And Hazard Information

    NORDAC ON (SK 300P series) – Manual with installation instructions 1.6 Warning and hazard information Under certain circumstances, hazardous situations may occur in association with the frequency inverter. In order to give explicit warning of possibly hazardous situations, clear warning and hazard information can be found on the device and in the relevant documentation.
  • Page 21: Standards And Approvals

    1 General 1.7 Standards and approvals All devices across the entire series comply with the standards and directives listed below. Applied Approval Directive Certificates Label standards Low Voltage 2014/35/EU 2014/30/EU EN 61800-5-1 EN 60529 RoHS 2011/65/EU EN 61800-3 Delegated directive C310001 (European 2015/863...
  • Page 22 NORDAC ON (SK 300P series) – Manual with installation instructions Conditions UL/CSA according to report Information • Listed as ENCLOSED POWER CONVERSION EQUIPMENT • These devices incorporate an adjustable internal solid-state motor overload protection (see P533, P535) • “Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the Manufacturer Instructions, National Electrical Code and any additional local codes”.
  • Page 23: Type Code / Nomenclature

    1 General 1.8 Type code / nomenclature The type code of the device depicts the basic features. A unique identification of the device including all customer-specific features is only possible via the device’s order or serial number. 1.8.1 Name plate All of the information which is relevant for the device, including information for the identification of the device, can be obtained from the name plate.
  • Page 24: Assembly And Installation

    NORDAC ON (SK 300P series) – Manual with installation instructions 2 Assembly and installation No options can be retrofitted. All options must be recorded by NORD when ordering and before the production process. For wall mounting, the device has lugs that are freely accessible from the outside. The electrical connection of mains, motor, daisy chain and signal cables is only possible via respective plug connectors.
  • Page 25 2 Assembly and installation Restrictions for installation positions M2 and M4 Motor mounting on Motor mounting on Wall mounting IE5+ motor IE3 motor Type S1 mode S3 mode S1 mode S3 mode S1 mode S3 mode SK 300P-360-340-A — — No derating No derating No derating...
  • Page 26: Dimensions Nordac On, Motor-Mounted

    NORDAC ON (SK 300P series) – Manual with installation instructions 2.2 Dimensions NORDAC ON, motor-mounted Housing dimensions Weight [mm] [kg] Device type Size (without motor) SK 30xP-360-340-A 213.5 SK 300P-450-340-A SK 30xP-370-340-A SK 30xP-750-340-A 1.85 SK 30xP-950-340-A Depending on the motor SK 30xP-111-340-A 3.28...
  • Page 27: Dimensions Nordac On+, Motor-Mounted

    2 Assembly and installation 2.3 Dimensions NORDAC ON+, motor-mounted Housing dimensions Weight [mm] [kg] Device type Size (without motor) SK 31xP-370-340-A SK 31xP-750-340-A SK 31xP-950-340-A SK 31xP-111-340-A Depending on the motor SK 31xP-151-340-A SK 31xP-221-340-A SK 31xP-301-340-A SK 31xP-371-340-A Devices with additional fan cover BU 0800 en-3924...
  • Page 28: Dimensions Nordac On Pure, Motor-Mounted

    NORDAC ON (SK 300P series) – Manual with installation instructions 2.4 Dimensions NORDAC ON PURE, motor-mounted Housing dimensions [mm] Weight [kg] Device type Size (without motor) SK 350P-370-340-A 237.5 121.5 SK 350P-750-340-A Depending on the motor SK 350P-111-340-A 306.8 SK 350P-151-340-A BU 0800 en-3924...
  • Page 29: Dimensions Nordac On And Nordac On+, Wall-Mounted

    2 Assembly and installation 2.5 Dimensions NORDAC ON and NORDAC ON+, wall-mounted Housing dimensions Weight Device type [mm] [kg] Size (x = 0 or x = 1) SK 300P-360-340-A 83.25 160.4 205.5 SK 300P-450-340-A SK 3xxP-370-340-A SK 3xxP-750-340-A 98.3 170.4 SK 3xxP-950-340-A SK 3xxP-111-340-A SK 3xxP-151-340-A...
  • Page 30: Dimensions Nordac On Pure, Wall-Mounted

    NORDAC ON (SK 300P series) – Manual with installation instructions 2.6 Dimensions NORDAC ON PURE, wall-mounted Housing dimensions Weight [mm] [kg] Device type Size SK 350P-370-340-A 171.8 110.5 234.8 SK 350P-750-340-A SK 350P-111-340-A 203.3 133.3 183.5 213.7 267.7 SK 350P-151-340-A BU 0800 en-3924...
  • Page 31: Connections

    2 Assembly and installation 2.7 Connections The device is configured according to the customer specification. Defined positions on the device apply for the selected options and features. The connections M1 to M5 described below are only available for the device versions NORDAC ON and NORDAC ON+.
  • Page 32: Nordac On, Motor-Mounted, Sizes 2 And 3

    NORDAC ON (SK 300P series) – Manual with installation instructions 2.7.2 NORDAC ON, motor-mounted, sizes 2 and 3 Function Connection SK 300P SK 301P Ethernet-In Ethernet-Out DOUT1 and DOUT2 Functional safety connection DIN1 and DIN2 DIN1 and DIN2 DIN2 and DOUT1 DIN3 and DIN4 DIN3 and DIN4 DIN4 and DOUT2...
  • Page 33: Nordac On+, Motor-Mounted, Sizes 2 And 3

    2 Assembly and installation 2.7.3 NORDAC ON+, motor-mounted, sizes 2 and 3 Function Connection SK 310P SK 311P Ethernet-In Ethernet-Out DOUT1 and DOUT2 Functional safety connection DIN1 and DIN2 DIN1 and DIN2 DIN2 and DOUT1 DIN3 and DIN4 DIN3 and DIN4 DIN4 and DOUT2 Diagnostic LED and RS485/RS232 diagnostic port When mounted on smooth IE5 motor with motor brake, or ventilated IE5 motors:...
  • Page 34: Nordac On Pure, Motor-Mounted, Sizes 2 And 3

    NORDAC ON (SK 300P series) – Manual with installation instructions 2.7.4 NORDAC ON PURE, motor-mounted, sizes 2 and 3 Connection Function Diagnostic LED and diagnostic connection RS485/RS232 Mains/24V/Ethernet-In (power connection, mains input) Mains/24V/Ethernet-Out (power connection, mains output) BU 0800 en-3924...
  • Page 35: Nordac On, Wall-Mounted, Size 1

    2 Assembly and installation 2.7.5 NORDAC ON, wall-mounted, size 1 Connection Function Ethernet-In Ethernet-Out DIN1 and DIN2 DIN2 and DOUT1 DIN3 and DIN4 DIN4 and DOUT2 Diagnostic LED and diagnostic connection RS485/RS232 Not equipped Not equipped Not equipped Mains/24V-In (power connection, mains input) Mains/24V-Out (power connection, mains output) Not equipped Motor connection...
  • Page 36: Nordac On And Nordac On+, Wall-Mounted, Sizes 2 And 3

    NORDAC ON (SK 300P series) – Manual with installation instructions 2.7.6 NORDAC ON and NORDAC ON+, wall-mounted, sizes 2 and 3 Function Connection SK 3x0P without SK CU6-STO SK 3x1P with SK CU6-STO Ethernet-In Ethernet-Out DOUT1 and DOUT2 Functional safety connection DIN1 and DIN2 DIN1 and DIN2 DIN2 and DOUT1...
  • Page 37: Nordac On Pure, Wall-Mounted, Sizes 2 And 3

    2 Assembly and installation 2.7.7 NORDAC ON PURE, wall-mounted, sizes 2 and 3 Connection Function Diagnostic LED and diagnostic connection RS485/RS232 Mains/24V/Ethernet-In (power connection, mains input) Mains/24V/Ethernet-Out (power connection, mains output) Motor connection including encoder connection 2.7.8 Hybrid cable The NORDAC ON PURE offers simpler and safer connection technology with its hybrid connections. A hybrid cable combines the connections for •...
  • Page 38: Electrical Connection

    NORDAC ON (SK 300P series) – Manual with installation instructions 2.8 Electrical Connection WARNING Electric shock Dangerous voltages may be present at the plug contacts for the power connections (e.g. mains cable, motor cable) even when the device is not in operation. •...
  • Page 39: Nordac On Pure Mains Connection

    2 Assembly and installation 2.8.2 NORDAC ON PURE mains connection Power connection Contact assignment Mains input: TE M23 hybrid plug Motor mounting NORDAC ON PURE Wall mounting NORDAC ON PURE Ethernet: a: TX+ Mains output: b: RX+ +24 V Motor mounting TE M23 hybrid c: TX- socket...
  • Page 40: Daisy Chain Connection

    NORDAC ON (SK 300P series) – Manual with installation instructions 2.8.3 Daisy chain connection Power connections provide the possibility of setting up a daisy chain. This way, the wiring effort for devices close to each other can be reduced. The current that is allowed to flow through the daisy chain cables in such an installation is limited.
  • Page 41: Motor Connection

    2 Assembly and installation 2.8.4 Motor connection The external motor connection is only available for wall-mounted devices. WARNING Hazardous voltage at the TF+, TF-, MB+, MB-, U, V and W contacts Touching the contacts may cause an electric shock. • If the TF+ and TF- or MB+ and MB- contacts are not used, the open wire ends must be insulated •...
  • Page 42: Electrical Connection Of Power Unit

    NORDAC ON (SK 300P series) – Manual with installation instructions cross-section, which is connected to the same earthing point as the device itself. Flat cables (e.g. metal clamps) are preferable, as they have a lower impedance at high frequencies. 2. The bonding cable of the motor controlled by the soft starter should be connected directly to the earthing terminal of the associated device.
  • Page 43: Mains Connection

    2 Assembly and installation At least one four-core motor cable must be used and U-V-W and PE connected to the plug connector. • Only copper cables with temperature class 80 °C or equivalent may be used for all connections. 2.8.6.1 Mains connection No special fuses are required on the mains input side of the device.
  • Page 44 NORDAC ON (SK 300P series) – Manual with installation instructions Required parameter settings If a braking resistor is installed, the relevant peak load and continuous output limit parameters are preset. The parameter settings vary depending on the type and assembly type of the frequency inverter (see following overview).
  • Page 45: Electromechanical Brake (Optionally With Size 2 And Above)

    2 Assembly and installation 2.8.6.4 Electromechanical brake (optionally with size 2 and above) For the control of an electromechanical brake, the device generates a PWM signal from the link circuit provided at the motor plug’s contacts (MB+ and MB-). The behaviour of the electromechanical brake is determined by the parameters P280, P281 and P282. The device checks the brake during operation and generates the following messages in the event of a fault: Short circuit at the brake connection...
  • Page 46: Electrical Connection Ethernet Communication And Digital Input/Outputs

    NORDAC ON (SK 300P series) – Manual with installation instructions 2.8.7 Electrical connection Ethernet communication and digital input/outputs The control cables of the NORDAC ON and NORDAC ON+ devices are connected exclusively via M12 plug connectors. The plug connectors are permanently installed at the factory. They enable the use of straight and angled (encapsulated) cable plug connectors.
  • Page 47 2 Assembly and installation Information Cable laying All control cables must be routed separately from the mains and the motor cables to prevent interference in the device. If the cables are routed in parallel, a minimum distance of 20 cm must be maintained from cables which carry a voltage of >...
  • Page 48: Control Connection Details

    NORDAC ON (SK 300P series) – Manual with installation instructions 2.8.7.1 Control connection details Meaning, Functions Description / Technical data Contact Parameter (designation) Meaning Function of factory setting Digital outputs Signalling of the device's operating states According to EN 61131-2 Maximum load of 20 mA per output when using both digital outputs.
  • Page 49: Diagnostic Port

    2 Assembly and installation 2.9 Diagnostic port The frequency inverter is equipped with an RJ12 diagnostic interface (1). Either a PC, a Bluetooth stick or a handheld control unit can be connected here via RS232/RS485. The same diagnostic interface (1) can also be found on the NORDAC ON PURE. Communication Connection of the FI to various communication tools interface...
  • Page 50: Encoder

    NORDAC ON (SK 300P series) – Manual with installation instructions 2.10 Encoder The NORDAC ON+ is equipped with an RS485 encoder interface at the X6 (1) connection. High- resolution encoders can transmit their information to the frequency inverter in real time via this encoder interface.
  • Page 51: Encoder Connection

    2 Assembly and installation Encoder Signal Connection type Number NORDAC NORDAC NORDAC type ON PURE poles SK 30xP SK 31xP SK-35xP Motor Internal mounting Universal – – RS485 RS485A Wall mounting Via X6 RS485B Motor Internal mounting Data- Universal – –...
  • Page 52 NORDAC ON (SK 300P series) – Manual with installation instructions Information Phase sequence The counting direction of the incremental encoder must correspond to the direction of rotation of the motor. The directions of rotation are identical if a positive speed is displayed in parameter P735 when the output frequency is positive.
  • Page 53: Display

    3 Display 3 Display The display elements M1 to M5 described below are only available for the device versions NORDAC ON and NORDAC ON+. 3.1 LEDs When used for bus communication, the LEDs of the Ethernet connections M1 and M2 indicate the operating states of the respective slave.
  • Page 54: Display Of M1 And M2 When Using Ethernet/Ip

    NORDAC ON (SK 300P series) – Manual with installation instructions Labelling Display Meaning M2 – 1 ERROR = Ethernet Error EtherCAT operating normally on the bus interface Flashing (4 Hz) General EtherCAT configuration error Single flash Bus interface has changed the EtherCAT state without authorisation Double flash EtherCAT or FI time-out (P513, P151) M2 –...
  • Page 55: Display Of M1 And M2 When Using Profinet

    3 Display 3.1.3 Display of M1 and M2 when using PROFINET Labelling Display Meaning M1 – 1 No connection (Link activity) Yellow flashing Connection has been established, data is being transmitted Green on Connection has been established, no data transmission M1 –...
  • Page 56: Display Of M4 And M5

    NORDAC ON (SK 300P series) – Manual with installation instructions 3.1.5 Display of M4 and M5 Labelling Display Meaning DIN1 Yellow on Digital input 1 = high M4 – 1 Digital input 1 = low Red on Overload DIN2 Yellow on Digital input 2 = high M4 –...
  • Page 57: Commissioning

    4 Commissioning 4 Commissioning WARNING Unexpected movement Connection of the supply voltage may directly or indirectly set the drive unit into motion. This can cause unexpected movement of the drive and the attached machine, which may result in serious or fatal injuries and/or material damage.
  • Page 58: Firmware Update

    With the integrated bus interface, the frequency inverter offers the option to update both the firmware of the frequency inverter and the firmware of the integrated bus interface. A firmware update is normally not necessary. In case a FW update is required, please contact the NORD DRIVESYSTEMS service. 4.3 Selecting the operating mode for motor control The NORDAC ON frequency inverter is able to control asynchronous motors.
  • Page 59 4 Commissioning speed characteristics are recorded and included in the calculation for the motor control. The encoder also allows for the determination of the rotor position, where for the operation of a PMSM the initial value of the rotor position must be additionally determined. This allows for a more precise and faster control of the drive.
  • Page 60: Overview Of Controller Parameter Settings

    NORDAC ON (SK 300P series) – Manual with installation instructions 4.3.2 Overview of controller parameter settings The following illustration provides an overview of all parameters which are important, depending on the selected operating mode. In principle, the following applies: The more precise the setting, the more accurate the control and the higher the possible values for the dynamics and precision of drive operation.
  • Page 61: Motor Control Commissioning Steps

    4 Commissioning 4.3.3 Motor control commissioning steps The main commissioning steps are mentioned below in their ideal order. Correct assignment of the inverter/motor and the mains voltage selection are assumed. Detailed information, especially for optimisation of the current, speed and position control of asynchronous motors is described in the guide "Control optimisation"...
  • Page 62: Parameter

    NORDAC ON (SK 300P series) – Manual with installation instructions 5 Parameter WARNING Unexpected movement due to changes in the parameterisation Parameter changes become effective immediately. Under certain conditions, dangerous situations may occur, even when the drive is in standstill. Functions such as P428 “Automatic starting” can set the drive in motion and places persons at risk due to moving parts.
  • Page 63 5 Parameter Menu group Master function Operating displays (P0--) Display of parameters and operating values Basic parameters (P1--) Basic device settings such as switch-on and switch-off behaviour Motor data (P2--) Electrical settings for the motor (motor current or initial voltage (starting voltage)) Control parameters (P3--)
  • Page 64: Parameter Overview

    NORDAC ON (SK 300P series) – Manual with installation instructions 5.1 Parameter overview Operating displays P000 Operating para. disp P001 Select of disp.value P002 Display factor P003 Supervisor-Code P004 Password P005 Change password Basic parameters P100 Parameter set P101 Copy parameter set P102 Acceleration time P103 Deceleration time...
  • Page 65 5 Parameter Control terminals P410 Min. freq. a-in 1/2 P411 Max. freq. a-in 1/2 P412 Nom.val process ctrl P413 PID control P comp. P414 PID control I comp. P415 PID control D comp. P416 Ramptime PI setpoint P420 Digital inputs P425 Function PTC input P426 Quick stop time...
  • Page 66 NORDAC ON (SK 300P series) – Manual with installation instructions P000 Operating para. disp (parameter number) (parameter name) Setting range Display of the typical display format, possible setting range and number of decimal places or display range Arrays [-01] If parameters are substructured into several arrays, this is shown here. Factory setting { 0 } Typical default setting that the parameter has in the delivery state of the device, or to which it is set...
  • Page 67: Operating Displays

    5 Parameter 5.1.1 Operating displays P000 Operating para. disp Display range 0.01 … 9999 Description The operating value selected in parameter P001 is displayed. Important information about the operating status of the drive can be read out as required. P001 Select of disp.value Setting range 0 ...
  • Page 68 NORDAC ON (SK 300P series) – Manual with installation instructions P002 Display factor Setting range 0.01 … 999.99 Factory setting { 1.00 } Description The selected operating value in parameter P001 “Select of disp.value” is multiplied by the scaling factor in P000 and displayed in the “Operating para. display”. It is therefore possible to display system-specific operating values such as the throughput quantity.
  • Page 69: Basic Parameters

    5 Parameter 5.1.2 Basic parameters P100 Parameter set Setting range 0 … 3 Factory setting { 0 } Description Selection of the parameters sets to be parameterised. Four parameter sets are available. The parameters to which different values can also be assigned in the four parameter sets are known as “parameter set-dependent”...
  • Page 70 NORDAC ON (SK 300P series) – Manual with installation instructions P103 Deceleration time Setting range 0.00 … 320.00 s Factory setting { 2.00 } Description The deceleration time is the time corresponding to the linear frequency reduction from the set maximum frequency P105 to 0 Hz. If a current setpoint < 100% is being used, the deceleration time reduces accordingly.
  • Page 71 5 Parameter P106 Ramp smoothing Setting range 0 … 100% Factory setting { 0 } Description This parameter enables smoothing of the acceleration and deceleration ramps. This is necessary for applications where gentle, but dynamic speed change is important. Ramp smoothing is carried out for every setpoint change. The value to be set is based on the set acceleration and deceleration time, however values <...
  • Page 72 NORDAC ON (SK 300P series) – Manual with installation instructions P107 Brake reaction time Setting range 0 … 2.50 s Factory setting { 0.00 } Description Electromagnetic brakes have a physically-dependent delayed brake reaction time when actuated. This can result in the dropping of the load in lifting gear applications. The brake takes up the load after a delay.
  • Page 73 5 Parameter P108 Switch-off mode Setting range 0 ... 14 Factory setting { 1 } Description This parameter determines the way in which the output frequency is reduced after "Blocking" (controller enable  Low). Setting values Value Meaning The output signal is switched off immediately. The FI no longer Voltage disable supplies an output frequency.
  • Page 74 NORDAC ON (SK 300P series) – Manual with installation instructions P109 DC brake current Setting range 0 … 250 % Factory setting { 100 } Description Current setting for the functions of DC current braking (P108 = 3) and combined braking (P108 = 5).
  • Page 75: Motor Data

    5 Parameter P113 Jog frequency Setting range -400.0 … 400.0 Hz Factory setting { 0.0 } Description When using a parameterisation unit to control the frequency inverter, the jog frequency represents the initial value after enabling. Alternatively, if control is via the control terminals, the jog frequency can be triggered via one of the digital inputs.
  • Page 76 NORDAC ON (SK 300P series) – Manual with installation instructions 0,09 kW 230V 56LP/4 0,50 PS/hp 230V 71LP/4 1,50 kW 400V 90LP/4 0,12 PS/hp 230V 56LP/4 0,37 kW 400V 71LP/4 2,00 PS/hp 460V 90LP/4 0,09 kW 400V 56LP/4 0,50 PS/hp 460V 71LP/4 2,20 kW 230V 100LP/4 0,12 PS/hp 460V 56LP/4 0,55 kW 230V 80SP/4...
  • Page 77 5 Parameter Information The motor default settings depend on the rated power and type of the frequency inverter (ON/ON+) and the respective assigned motor type (ASM/PMSM). This concerns the parameters P201 … P247. P201 Nominal frequency Setting range 10.0 … 399.9 Hz Factory setting The default setting depends on the nominal power of the FI.
  • Page 78 NORDAC ON (SK 300P series) – Manual with installation instructions P208 Stator resistance Setting range 0.00 … 300.00 Ω Factory setting The default setting depends on the nominal power of the FI. Description Motor stator resistance  Resistance of a phase winding with a three-phase motor. The stator resistance has a direct influence on the current control of the FI.
  • Page 79 5 Parameter P212 Slip compensation Setting range 0 ... 150% Factory setting { 100 } Description Asynchronous motor operation: Slip compensation increases the output frequency depending on the load, in order to keep the three-phase asynchronous motor speed approximately constant. The factory setting of 100 % is optimal for three-phase asynchronous motors if the correct motor data has been set.
  • Page 80 NORDAC ON (SK 300P series) – Manual with installation instructions P216 Time boost prectrl. Setting range 0.0 ... 10.0 s Factory setting { 0.0 } Description This parameter is used for 2 functionalities: 1. Time limit for the boost precontrol: Application time for the increased starting current.
  • Page 81 5 Parameter P219 Auto.magn.adjustment Setting range 25 ... 100% / 101 Factory setting { 100 } Description “Automatic flux optimisation”. With this parameter, the magnetic flux of the motor can be automatically matched to the motor load, so that the energy consumption is reduced to the amount which is actually required.
  • Page 82 NORDAC ON (SK 300P series) – Manual with installation instructions P220 Par.-identification Setting range 0 ... 2 Factory setting { 0 } Description “Parameter identification”. For devices with an output up to 7,5 kW, the motor data is determined automatically by the device via this parameter. Do not switch off the mains voltage during the parameter's identification.
  • Page 83 5 Parameter P240 EMF voltage PMSM Setting range 0 … 800 V Factory setting Depending on the FI’s nominal power Scope of application NORDAC ON+ Description The EMF voltage PMSM describes the mutual induction voltage of the motor. The value to be set can be found on the data sheet for the motor or on the name plate and is scaled to 1000 rpm.
  • Page 84 NORDAC ON (SK 300P series) – Manual with installation instructions P244 Peak current PMSM Setting range 0.1 … 1000.0 A Arrays [-01] = Peak current PMSM [-02] = Imax unsaturated Ld [-03] = Imax unsaturated Lq [-04] = Imin saturated Ld [-05] = Imin saturated Lq Factory setting...
  • Page 85 5 Parameter P281 Voltage mechan.brake Setting range 100 … 300 V Factory setting { 180 } Description The parameter describes the nominal voltage of the brake coil. P282 Mode mechan.brake Setting range 000 … 111 (bin) Factory setting { 000 } Description This parameter determines the operating mode of the spring-loaded brake.
  • Page 86: Speed Control

    NORDAC ON (SK 300P series) – Manual with installation instructions 5.1.4 Speed control P300 Control method Setting range 0 … 3 Factory setting { NORDAC ON: { 0 }, NORDAC ON+: { 1 } } Description Definition of the control method for the motor Note Commissioning information: (...
  • Page 87 5 Parameter P302 Type Univers.encoder Setting range 0 … 5 Factory setting { 1 } Description The encoder type is selected via this parameter. Note Setting values Value | Meaning UART TTL Incremental BISS-C BiSS-C inverse SSI inverse P310 Speed controller P Setting range 0 …...
  • Page 88 NORDAC ON (SK 300P series) – Manual with installation instructions P314 Torq curr ctrl limit Setting range 0 … 400 V Factory setting { 400 } Description "Torque curr. Ctrl. limit". Determines the maximum voltage increase of the torque current controller. The higher the value, the greater the maximum effect that can be exercised by the torque current controller.
  • Page 89 5 Parameter P320 Weak border Setting range 0 … 110 % Factory setting { 100 } Description The field weakening limit determines the speed /current at which the controller begins to weaken the field. At a set value of 100 % the controller begins to weaken the field at approximately the synchronous speed.
  • Page 90 NORDAC ON (SK 300P series) – Manual with installation instructions P327 Speed slip error Setting range 0 … 3000 rpm Arrays [-01] = Permissible deviation during [-02] = Permissible deviation during operation standstill (to monitor a holding brake) • FI enabled •...
  • Page 91 5 Parameter P330 Ident startrotor pos Setting range 0 … 2 Factory setting { 1 } Description “Rotor starting position detection “. Selection of the method for determination of the starting position of the rotor (initial value of the rotor position) of a PMSM (Permanent Magnet Synchronous Motor).
  • Page 92 NORDAC ON (SK 300P series) – Manual with installation instructions • The switchover frequency cannot be higher than 100 Hz The frequency inverter eventually limits the setting internally. (Only valid for P300 = 3) P332 Hyst.Switchover Freq Setting range 0.1 ... 25.0% Factory setting { 5.0 } Description...
  • Page 93 5 Parameter P336 Mode Rotorpos ident Setting range 0 ... 3 Factory setting { 0 } Description “Mode of identification of the starting conditions”. This parameter has a double function. Function 1: Definition of the mode for the rotor position identification of a synchronous motor (PMSM).
  • Page 94 NORDAC ON (SK 300P series) – Manual with installation instructions Functional relation between P336 and P342 In addition to the functions described directly in the parameters, parameters P336 and P342 are also directly related to each other. Control Setting Remark P336 P342 CFC closed-loop (P300 = 1)
  • Page 95 5 Parameter P338 Voltage CFC-Inj Setting range 1 ... 1000% Factory setting { 100 } Description “Voltage CFC injection”: Adjustment of injection voltage. The higher the selected voltage, the greater the precision. In addition, the noise development increases during the identification process. Note •...
  • Page 96 NORDAC ON (SK 300P series) – Manual with installation instructions P342 Synchron Start PMSM Setting range 0 … 5 Factory setting { 0 } Description “Synchronised startup time for PMSM”: Delay of motor start after the enable signal. The delay time corresponds to the duration of the identification cycle according to P330 of the test signalling method and the identification of the starting position of the rotor with P300 = 3, multiplied by the setting parameterised in P342.
  • Page 97 5 Parameter Functional relation between P336 and P342 In addition to the functions described directly in the parameters, parameters P336 and P342 are also directly related to each other. Control Setting Remark P336 P342 CFC closed-loop (P300 = 1) No function •...
  • Page 98 NORDAC ON (SK 300P series) – Manual with installation instructions P351 PLC set val. select. Setting range 0 … 3 Factory setting { 0 } Description Selection of the source for the control word (CTW) and the main setpoint (MSW) with active PLC functionality (P350 = 1).
  • Page 99: Control Terminals

    5 Parameter 5.1.5 Control terminals P410 Min. freq. a-in 1/2 Setting range -400.0 ... 400.0 Hz Factory setting { 0.0 } Description "Minimum frequency auxiliary setpoints". The minimum frequency that can act on the setpoint via the auxiliary setpoints. Auxiliary setpoints are all frequencies that are additionally delivered for further functions in the FI: •...
  • Page 100 NORDAC ON (SK 300P series) – Manual with installation instructions P415 PID control D comp. Setting range 0 ... 400.0% ms Factory setting { 1.0 } Description This parameter is only effective when the function “PID current freq.” is selected. In case of a control deviation, the D component of the PID controller determines the frequency change depending on time.
  • Page 101 5 Parameter Fault acknowledgem. Fault acknowledgement with an external signal. If this function 01 is not programmed, a fault can also be acknowledged by setting flank enable to “low” (P506). Temperatur sensor Switching threshold approx. 2.5 V, switch-off delay = 2 s, level warning after 1 s With bus system control, a “low”...
  • Page 102 NORDAC ON (SK 300P series) – Manual with installation instructions … Evacuation mode The undervoltage detection is deactivated. high The function is not available with a PMSM in sensorless operation (P300 = 3). “Motor potentiometer function frequency +/- with automatic Motorpot.F+ and Save high saving”.
  • Page 103 5 Parameter P427 Quick stop on Error Setting range 0 ... 3 Factory setting { 0 } Description “Quick stop on error”. Activation of automatic quick stop in case of an error. A quick stop can be triggered by error E002.x, E007.0, E010.x, E012.8, E012.9 and E019.0.
  • Page 104 NORDAC ON (SK 300P series) – Manual with installation instructions P430 Fixed frequency 2 Setting range -400.0 … 400.0 Hz Factory setting { 0.0 } Description For a description of the function of the parameter, see P429 “Fixed frequency 1”. P431 Fixed frequency 3 Setting range...
  • Page 105 5 Parameter Torque current limit “Torque current limit/current limit active (warning)”. The limit value in P112 or P536 was reached. A negative value in P435 inverts the behaviour. Hysteresis = 10% Value of P541 The output can be set using parameter P541, high irrespective of the device's current operating state.
  • Page 106 NORDAC ON (SK 300P series) – Manual with installation instructions P436 Dig.out. hysteresis Setting range 1 … 100% [-01] = Digital out 1 Digital output 1 in the frequency inverter [-02] = Digital out 2 Digital output 2 in the frequency inverter Factory setting All { 10 } Description...
  • Page 107 5 Parameter P466 Min.freq. proc.ctrl. Setting range 0.0 … 400.0 Hz Factory setting { 0.0 } Description “Minimum frequency process control”. With the aid of the minimum process controller frequency the control ratio can also be kept to a minimum ratio, even with a master value of “zero”, in order to enable adjustment of the compensator.
  • Page 108 NORDAC ON (SK 300P series) – Manual with installation instructions P481 Funct-BusIO Out Bits Setting range 0 … 53 Arrays [-01] = BusIO Out Bit 0 [-02] = BusIO Out Bit 1 Out Bits 0 … 3 via bus [-03] = BusIO Out Bit 2 [-04] = BusIO Out Bit 3...
  • Page 109 5 Parameter P483 Hyst. BusIO Out Bits Setting range 1 … 100% Arrays [-01] = BusIO Out Bit 0 [-02] = BusIO Out Bit 1 Out Bit 0 … 3 via Bus [-03] = BusIO Out Bit 2 [-04] = BusIO Out Bit 3 [-05] = BusIO Out Bit 4...
  • Page 110: Additional Parameters

    NORDAC ON (SK 300P series) – Manual with installation instructions 5.1.6 Additional parameters P501 Inverter name Setting range A … Z (char) Arrays [-01] … [-20] Factory setting { 0 } Description Free input of a designation (name) for the device (max. 20 characters). With this, the frequency inverter can be uniquely identified for setting with NORDCON software or within a network.
  • Page 111 5 Parameter P505 Absolute mini. freq. Setting range 0.0 … 10.0 Hz Factory setting { 2.0 } Description “Absolute minimum frequency”. Specifies the frequency value that cannot be undershot by the FI. If the setpoint becomes smaller than the absolute minimum frequency, the FI switches off or changes to 0.0 Hz.
  • Page 112 NORDAC ON (SK 300P series) – Manual with installation instructions P510 Source Setpoints Setting range 0 ... 2 / 8 Arrays Selection of the setpoint source. [-01] = Source main setpoint [-02] = Source 2nd setpoint Factory setting all { 0 } Description Selection of the interface, from which the frequency inverter receives its setpoints.
  • Page 113 5 Parameter P516 Skip frequency 1 Setting range 0.0 … 400.0 Hz Factory setting { 0.0 } Description The output frequency around the frequency in the range between +P517 and -P517 set here is not displayed. This range is transmitted with the set deceleration and acceleration ramp; it cannot be continuously supplied to the output.
  • Page 114 NORDAC ON (SK 300P series) – Manual with installation instructions P520 Flying start Setting range 0 … 4 Factory setting { 0 } Description This function is required to actuate the FI to already rotating motors, e.g. for fan drives. Note For physical reasons, flying start only operates above 1/10 of the nominal frequency P201, however not below 10 Hz.
  • Page 115 5 Parameter P523 Factory setting Setting range 0 ... 4 Factory setting { 0 } Description With the selection and activation of the relevant value, the selected parameter range is set to the factory setting. Once this setting is made, the parameter value automatically changes back to 0.
  • Page 116 NORDAC ON (SK 300P series) – Manual with installation instructions P527 Load control freq. Setting range 0.0 ... 400.0 Hz Arrays Selection of up to 3 auxiliary values: [-01] = Auxiliary value 1 [-02] = Auxiliary value 2 [-03] = Auxiliary value 3 Factory setting All { 25.0 }...
  • Page 117 5 Parameter P535 t motor Setting range 0 … 24 Factory setting { 0 } Description The motor temperature is calculated depending on the output current, the time and the output frequency (cooling). If the temperature limit value is reached, switch-off occurs with error message E2.1.
  • Page 118 NORDAC ON (SK 300P series) – Manual with installation instructions P537 Pulse Disconnection Setting range 10 ... 250% / 251 Factory setting { 200 } Description This function prevents rapid switch-off of the FI under load. With the pulse disconnection enabled, the output current is limited to the set value. This limitation is implemented by brief switch-off of individual output stage transistors;...
  • Page 119 5 Parameter P540 Mode phase sequence Setting range 0 ... 7 Factory setting { 0 } Description For safety reasons, this parameter can be used to prevent a phase sequence reversal and therefore prevent an incorrect phase sequence. Note This function influences the function of the position control (P600 ≠ 0). Setting values Value Meaning...
  • Page 120 NORDAC ON (SK 300P series) – Manual with installation instructions P543 Bus actual value Setting range 0 … 57 Arrays Bus actual value [-01] = Bus actual value 1 [-02] = [-03] = Bus actual value 3 Bus actual value [-04] = Bus actual value 4 [-05] = Factory setting...
  • Page 121 5 Parameter P549 Function Ctrlbox Setting range 0 … 5 Factory setting { 0 } Description This parameter provides the option of adding a correction value to the current setpoint (fixed frequency, analogue value, bus) by means of the ControlBox keyboard. Explanations of the setting values can be found in the description of P400.
  • Page 122 NORDAC ON (SK 300P series) – Manual with installation instructions P554 Min. chopper Chop. Setting range 65 … 102 % Factory setting { 65 } Description "Minimum chopper threshold". Adjustment of the switching threshold of the brake chopper. Note An increase in this setting leads to a faster overvoltage FI switch off. For applications where pulsating energy is returned (crank drives) the braking resistor power dissipation can be minimised by increasing this setting.
  • Page 123 5 Parameter Instructions for parameterisation:  2.8.6.3 "Braking resistor (optionally with size 2 and above)" P558 Flux delay Setting range 0 ... 5000 ms Factory setting { 1 } Description The ISD control can only function correctly if there is a magnetic field in the motor.
  • Page 124 NORDAC ON (SK 300P series) – Manual with installation instructions P583 Motor phase sequence Setting range 0 ... 2 Factory setting { 0 } Description The motor phase control sequence (U - V - W) can be changed with this parameter. This enables the phase sequence of the motor to be changed without changing the motor connections.
  • Page 125: Information

    5 Parameter 5.1.7 Information P700 Actual Operating Status Display range 0 … 2990 Arrays [-01] = Current fault Indicates the currently active (unacknowledged) error. [-02] = Actual warning Indicates a present warning message. [-03] = Reason FI blocked Indicates the reason for active switch-on inhibit. [-04] = Extended error Displays the currently active error according to...
  • Page 126 NORDAC ON (SK 300P series) – Manual with installation instructions P706 P set last error Display range 0 ... 3 Arrays [-01] … [-10] Description “Parameter set last error 1 … 10”. This parameter stores the parameter set code that was active when the error occurred.
  • Page 127 5 Parameter P714 Operating time Display range 0.00 ... 19 999 999.99 h Description Duration of the device’s operational readiness and availability of mains voltage (cumulative value over the service life of the device). P715 Running time Display range 0.00 ... 19 999 999.99 h Description Period of time during which the device was enabled and supplied power at the output (cumulative value over the service life of the device).
  • Page 128 NORDAC ON (SK 300P series) – Manual with installation instructions P725 Present cos phi Display range 0.00 ... 1.00 Description Displays the actual calculated cos ϕ of the drive. P726 Apparent power Display range 0.00 ... 300.00 kVA Description Displays the actual calculated apparent power. Basis for calculation is the motor data P201 ...
  • Page 129 5 Parameter P735 Speed encoder Display range -9999 … 9999 rpm Arrays [-01] = Universal [-03] = Reserve (Type: TTL / UART) [-02] = [-04] = Speed monitor (The speed is determined by alternative measuring methods and by calculation) Description Displays the current speed supplied by the encoder.
  • Page 130 NORDAC ON (SK 300P series) – Manual with installation instructions P740 PZD bus in Display range 0000h … FFFFh Arrays [-01] = Control word Control word [-02] = Set value 1 Setpoint data from main setpoint P509 … [-06] = Setvalue 5 The displayed value depicts all Bus In Bit [-07] =...
  • Page 131 5 Parameter P741 PZD bus out Display range 0000h … FFFFh Arrays Status word corresponding to selection in P551 [-01] = Status word bus [-02] = Bus actual value 1 Actual values according to P543 … … [-06] = Bus actual value 5 The displayed value depicts all Bus OUT Bit [-07] = Res.stat.OutBit P481...
  • Page 132 NORDAC ON (SK 300P series) – Manual with installation instructions 0000 No extension 0001 0002 Reserved 0003 Reserved 0004 Reserved 0005 0006 Array [-03] – Addition.Interfaces Bit 0 Interface for IOE present Bit 1 TTL encoder interface Bit 2 HTL encoder functionality Bit 3 Diagnostic interface Bit 4...
  • Page 133 5 Parameter P750 Error statistics Display range 0 ... 9999 Arrays [-01] … [-25] Description Display of the error messages which have occurred during operation (P714). Note Depending on the frequency of the errors, the entries in the arrays are displayed in descending order.
  • Page 134: Operating Status Messages

    NORDAC ON (SK 300P series) – Manual with installation instructions 6 Operating status messages In case of deviations from the normal operating status, a message is output. There are: • Error messages: Faults cause the device to switch off. • Warning messages: A limit value has been reached.
  • Page 135 6 Operating status messages Fault messages Coding Cause Error message • Remedy Group Number Inverter overtemp. E001 Temperature monitoring of the inverter Temperature range has been exceeded or undershot. • Reduce or increase ambient temperature • Check fan or cabinet ventilation •...
  • Page 136 NORDAC ON (SK 300P series) – Manual with installation instructions Overcurrent chopper E003 The current limit (I t) of the brake chopper has been exceeded (e.g more than 1.5 x rated current for 60 s). • Avoid overcurrent in braking resistor Check braking resistor values (P555, P556, P557 and •...
  • Page 137 6 Operating status messages Overcurrent measurem. E004 Pulse switch-off (P537) has been reached three times within 50 ms. • Reduce motor load • Check system for blockage or overload Further notes: • Error message is only possible if (P112) and (P536) are switched off Check motor data settings on the device (P201 …...
  • Page 138 NORDAC ON (SK 300P series) – Manual with installation instructions E008 Parameter loss Error in EEPROM data (maximum EEPROM value • Software version of the stored data set not compatible exceeded) with the software version of the FI Note: Faulty parameters are automatically reloaded (factory setting).
  • Page 139 6 Operating status messages E011 11.0 Control terminals Communication error to CU module • Internal customer unit (internal data bus) defective or interference due to radio radiation (EMC). • Check control connections for short circuit. • Minimise EMC interferences by separate routing of control and power cables.
  • Page 140 NORDAC ON (SK 300P series) – Manual with installation instructions E013 13.0 Encoder error Missing signals from encoder (TTL), slip error • Check connections and cables on both sides • Check the mechanical installation of the encoder (encoder shaft is at a halt when slip error monitoring is active) Further notes: •...
  • Page 141 6 Operating status messages E016 16.0 Motor phase failure A motor phase is not connected. • Check connections and cables on both sides • Check the motor Further notes: • Check (P539) E016 16.1 Magn. current watch Required exciting current not achieved at moment of switch- •...
  • Page 142 NORDAC ON (SK 300P series) – Manual with installation instructions E019 19.3 Rotor position adjustment The rotor position coupled by the zero pulse deviates considerably from the rotor position determined by the test signal method (P330). • Motor phases are not correctly connected Connect motor phase “U”...
  • Page 143 6 Operating status messages E025 25.3 Uni.encoder resol. The set universal encoder resolution does not match the one sent by the encoder. • Check P605 E025 25.4 Uni.encoder fault The universal encoder has an internal error and reports an error code to the frequency inverter. The error code received can be read in parameter P650 [-01].
  • Page 144 NORDAC ON (SK 300P series) – Manual with installation instructions Motor overtemp. PTC C002 Warning from the motor temperature sensor (trigger limit reached) • Reduce motor load • Increase motor speed • Install external motor fan or check the function Further notes: •...
  • Page 145 6 Operating status messages Overcurrent measurem. C004 The pulse disconnection (P537) has been achieved. • Reduce motor load • Check system for blockage or overload Further notes: • Error message is only possible if (P112) and (P536) are switched off •...
  • Page 146 NORDAC ON (SK 300P series) – Manual with installation instructions Messages on switch-on inhibit, “not ready” Coding Reason for switch-on inhibit, Cause “not ready” • Remedy Group Number Volt. blocked by IO I000 The input which is parameterised with the “Voltage disable” function (P420/P480) is not set (“Low”).
  • Page 147: Faq Operational Problems

    6 Operating status messages Left dir. locked Switch-on inhibit with inverter shut-off activated by: I000 • P540 or by “Block enable left” (P420 = 32, 74) The frequency inverter switches to "Ready to switch-on" status. Charging error I006 Charging relay not energised, because: •...
  • Page 148 NORDAC ON (SK 300P series) – Manual with installation instructions • Check P105 • Maximum frequency parameter setting Motor not reaching required too low speed Check P465 • Motor speed does not • Setpoint specification via BUS IO Bit is •...
  • Page 149: Technical Data

    7 Technical data 7 Technical data 7.1 General frequency inverter data Function Specification Output frequency 0.0 … 400.0 Hz Pulse frequency 3.0 … 16.0 kHz, factory setting = 6 kHz Power reduction > 6 kHz for 400 V device Typical overload capacity, typical 150% for 60 s, 200% for 5 s, 250% for 1 s overload Efficiency...
  • Page 150 NORDAC ON (SK 300P series) – Manual with installation instructions Function Specification Motor temperature monitoring t motor, PTC/bimetallic switch Regulation and control Sensorless current vector control (ISD), linear V/f characteristic curve, VFC open-loop, CFC open-loop, CFC closed-loop Waiting period between two mains 60 s for all devices in normal operating cycle switch-on cycles Interfaces...
  • Page 151: Maximum Operating / Ambient Temperature

    7 Technical data 7.2 Maximum operating / ambient temperature The maximum ambient temperature depends on the device power, assembly type, motor ventilation and pulse frequency. The following tables help to determine the maximum ambient temperature for S1 or S3 mode. Information However, it is also possible to refer to the internal temperature, see parameters P739 [-02] and P739 [- 03].
  • Page 152: Motor-Mounted Frequency Inverters

    NORDAC ON (SK 300P series) – Manual with installation instructions 7.2.2 Motor-mounted frequency inverters Frequency inverter Ventilated Pulse frequency motor Size Power 6 kHz 16 kHz 370 W & 450 W 40 °C 50 °C 70% ED 50 °C 70% ED 370 W &...
  • Page 153: Reducing The Maximum Ambient Temperature

    7 Technical data 7.2.3 Reducing the maximum ambient temperature Two important factors determine the permissible ambient temperature of a frequency inverter. This concerns the daisy chain use and the stability of the 24 V supply voltage. Under the most unfavourable conditions, the maximum permissible ambient temperature can reduce by 7 K.
  • Page 154: Technical Data For Determining The Energy Efficiency Level

    NORDAC ON (SK 300P series) – Manual with installation instructions 7.3 Technical data for determining the energy efficiency level The following tables relate to the provisions of the Ecodesign EU Regulation 2019/1781. Information Calculation basis for the energy efficiency level The energy efficiency specifications come from calculations according to DIN EN 61800 “Adjustable speed electrical power drive systems –...
  • Page 155 7 Technical data Indicative Max. Output Rated output Rated input Rated input FI type output operating power current frequency voltage range power temperature NORDAC [kVA] [kW] [°C] [Hz] SK 3xxP- 360-340 0,70 0,37 380 V – 480 V 450-340 0,84 0,45 380 V –...
  • Page 156: Electrical Data 3~ 400 V

    NORDAC ON (SK 300P series) – Manual with installation instructions 7.4 Electrical data 3~ 400 V 7.4.1 NORDAC ON, size 1 Device type SK 300P–360 SK 300P–450 400 V 0.37 kW 0.45 kW Nominal power 480 V 0.5 hp 0.6 hp 3 AC 380 V -20% …...
  • Page 157: Nordac On, Nordac On+, Nordac On Pure, Size 3

    7 Technical data 7.4.3 NORDAC ON, NORDAC ON+, NORDAC ON PURE, size 3 SK 3xxP– SK 3xxP– SK 30xP– SK 3xxP– SK 3xxP– SK 31xP– Device type 400 V 1.1 kW 1.5 kW 1.9 kW 2.2 kW 3.0 KW 3.7 kW Nominal power 480 V 1.5 hp...
  • Page 158: Electrical Data For 24 V Dc Supply

    NORDAC ON (SK 300P series) – Manual with installation instructions 7.5 Electrical data for 24 V DC supply Connected load NORDAC ON NORDAC ON+ NORDAC ON PURE 24 V control voltage DC 24 V +/- 20% Approx. 450 mA (depending on Basic input current 150 …...
  • Page 159: Additional Information

    8 Additional information 8 Additional information 8.1 Electromagnetic compatibility (EMC) 8.1.1 General Provisions As of July 2007, all electrical equipment which has an intrinsic, independent function and which is sold as an individual unit for end users, must comply with Directive 2004/108/EEC (formerly Directive EEC/89/336).
  • Page 160: Emc Evaluation

    NORDAC ON (SK 300P series) – Manual with installation instructions 8.1.2 EMC evaluation Two standards must be observed when evaluating electromagnetic compatibility. 1. EN 55011 (environmental standard) In this standard, the limit values are defined in dependence on the basic environment in which the product is operated.
  • Page 161: Emc Of Device

    8 Additional information 8.1.3 EMC of device NOTICE EMC interference to the environment This device produces high-frequency interference, which may make additional suppression measures necessary in domestic environments (see chapter 8.1 "Electromagnetic compatibility (EMC)"). The use of shielded motor cables is essential in order to maintain the specified radio interference suppression level.
  • Page 162 NORDAC ON (SK 300P series) – Manual with installation instructions EMC overview of standards that are used in accordance with EN 61800-3 as checking and measuring procedures: Interference emission Cable-related emission EN 55011 (interference voltage) Radiated emission EN 55011 (interference field strength) C3 (size 2) Interference immunity EN 61000-6-1, EN 61000-6-2...
  • Page 163: Declarations Of Conformity

    8 Additional information 8.1.4 Declarations of Conformity BU 0800 en-3924...
  • Page 164 NORDAC ON (SK 300P series) – Manual with installation instructions BU 0800 en-3924...
  • Page 165: Reduced Output Power

    8 Additional information 8.2 Reduced output power The frequency inverters are designed for special overload situations. For example, 1.5x overcurrent can be used for 60 s. For approx. 3.5 s, 2x overcurrent is possible. A reduction of the overload capacity or its duration must be considered for the following circumstances: •...
  • Page 166: Reduced Overcurrent Due To The Time

    NORDAC ON (SK 300P series) – Manual with installation instructions 8.2.2 Reduced overcurrent due to the time Depending on the duration of an overload, the possible overload capacity changes. Some values are highlighted in these tables. If one of these limit values is reached, the frequency inverter must have sufficient time (at low load or without load) to regenerate.
  • Page 167: Reduced Overcurrent Due To Output Frequency

    8 Additional information 8.2.3 Reduced overcurrent due to output frequency To protect the power unit at low output frequencies (< 4.5 Hz), monitoring is provided to determine the temperature of the IGBTs (insulated-gate bipolar transistor) due to high current. A pulse disconnection (P537) with variable limit is introduced so that no current can be accepted above the limit shown in the diagram.
  • Page 168: Reduced Output Current Due To Low Voltage

    NORDAC ON (SK 300P series) – Manual with installation instructions 8.2.4 Reduced output current due to low voltage The frequency inverters are thermally designed with regard to the rated output currents. For lower low voltages larger currents cannot be used in order to keep the output power constant. For mains voltages above 400 V the permissible output current is reduced inversely proportional to the mains voltage in order to compensate for switching losses.
  • Page 169: Motor Data - Characteristic Curves (Synchronous Motors)

    8 Additional information 8.5 Motor data – characteristic curves (synchronous motors) When operating the motor on a NORDAC frequency inverter, use the motor data listed in the corresponding motor data sheet to parameterise the motor data. The motor data sheet is available from NORD or can be requested from NORD.
  • Page 170: Scaling Of Setpoint/Actual Values

    NORDAC ON (SK 300P series) – Manual with installation instructions 8.6 Scaling of setpoint/actual values The following tables contain details for the standardisation of typical setpoints and actual values. These details relate to parameters (P543), (P546), (P740) or (P741). Indices that contain a ” ”...
  • Page 171 8 Additional information Setpoint {function} Value Reference value 100% Scaling of setpoints range Abbreviation [Unit] �((P203)²-(P209)²) * P112) 16384 * I SP No Setpoint torque process Torque current limit 16384 * p controller {46} ±100% (P112) SP No P112 Motor temperature {48} 16384 * T 100 °C ±200%...
  • Page 172: Actual Values

    NORDAC ON (SK 300P series) – Manual with installation instructions 8.6.2 Actual values Actual values {function} Reference value 100% Scaling of setpoints Abbreviation [Unit] Actual frequency {01} Maximum frequency (P105) * P105 A No 16384 [Hz] Actual speed {02} Nominal speed (P202) * P202 A No 16384...
  • Page 173: Definition Of Set And Actual Value Processing (Frequencies)

    8 Additional information 8.7 Definition of set and actual value processing (frequencies) The frequencies used in P543 are processed in various ways according to the following table. Setpoint source and Signal processing Control and motor model setpoint selection and ramp (slip determination) Output to ...
  • Page 174: Motor Temperature Monitoring

    NORDAC ON (SK 300P series) – Manual with installation instructions 8.8 Motor temperature monitoring Motors must be effectively protected against overload. The frequency inverter can take over this task by evaluating temperature sensors and by recording and evaluating various electrical operating values. The following options are available.
  • Page 175: Connection Accessories

    8 Additional information 8.9 Connection accessories The material for establishing the electrical connection is not included in the scope of delivery of the frequency inverter. However, it can be obtained from NORD. 8.9.1 Motor cable Pre-assembled cables for the motor connection are available (www.nord.com). Plug connector Designation Document...
  • Page 176: Hybrid Mains Cable

    NORDAC ON (SK 300P series) – Manual with installation instructions 8.9.4 Hybrid mains cable For the NORDAC ON PURE, pre-assembled hybrid cables are available for the mains connection (www.nord.com). Plug connector Designation Document UL FI side Low voltage side Length: 10 m SC H4S2.5 TEH51SVF OE 10 PCD Socket, 11-pole Open ends...
  • Page 177: Encoder Cables

    8 Additional information 8.9.8 Encoder cables Pre-assembled cables for the connection of incremental encoders are available (www.nord.com). Plug connector Designation Document UL FI side Encoder side SC S5Y0.25 M12-A5SMM M12- M12, Pin, M12, Socket, TI_275274874-879 A5SMF xxx A-coded, 5-pole A-coded, 5-pole BU 0800 en-3924...
  • Page 178: Maintenance And Servicing Information

    NORDAC ON (SK 300P series) – Manual with installation instructions 9 Maintenance and servicing information 9.1 Maintenance information NORD frequency inverters are maintenance-free in normal operation(see chapter 7 "Technical data"). Dusty environments If the device is operated in dusty air, the cooling surfaces must be cleaned with compressed air at regular intervals.
  • Page 179: Service Notes

    9 Maintenance and servicing information 9.2 Service notes In case of service/repair, contact your NORD Service contact person. You will find your contact person listed on your order confirmation. Additionally, you will find further possible contact persons using the following link: https://www.nord.com/de/global/locator-tool.jsp. When contacting our technical support please have the following information available: •...
  • Page 180: Disposal

    NORDAC ON (SK 300P series) – Manual with installation instructions 9.3 Disposal NORD products are made of high-quality components and valuable materials. Therefore, have faulty or defective appliances checked to see if they can be repaired and reused. If repair and reuse is not possible, observe the following disposal notes. 9.3.1 Disposal according to German law •...
  • Page 181: Abbreviations

    9 Maintenance and servicing information 9.4 Abbreviations Asynchronous machine, asynchronous Ground, common reference potential motor AOUT Analogue output In / Out (Input / Output) Current Flux Control (current-controlled, Field current (current vector control) field-oriented control) DI (DIN) Digital input Light-emitting Diode DigIn DS (LED) Status LED (device status)
  • Page 182 NORDAC ON (SK 300P series) – Manual with installation instructions Key word index Absolute mini. freq. (P505) ......111 CE mark ............159 Acceleration time (P102) ....... 69 Change Password (P005) ......68 Accessories ..........175 Charging error"..........147 Daisy chain cable ........176 Check output voltage (P539) ......
  • Page 183 Key word index Dig.out. hysteresis (P436) ......106 Field weakening limit (P320) ......89 Digit inputs (P420) ........100 Firmware update ........... 58 Digital out function (P434) ......104 Fixed freq. Array (P465)......106 Display ............53 Fixed frequency 1 (P429) ......103 Display factor (P002) ........
  • Page 184 NORDAC ON (SK 300P series) – Manual with installation instructions Mode phase sequence (P540) ....119 Mode Rotorpos ident (P336) ......93 Jog frequency (P113) ........75 Modulation depth (P218) ......80 Module version (P745) ........ 132 Last extended error (P752)......133 Motor cable ..........
  • Page 185 Key word index PID control I comp. (P414) ......99 Plug connection ........176 PID control P comp. (P413) ......99 Select of disp.value (P001) ......67 PLC display value (P360) ......98 Set digital out (P541) ........119 PLC functionality (P350) ........ 97 Setpoint processing Frequencies ....
  • Page 186 NORDAC ON (SK 300P series) – Manual with installation instructions Torq curr ctrl limit (P314) ....... 88 USS baud rate (P511)......... 112 Torque (P729) ..........128 Torque curr. ctrl. I (P313) ......87 Volt. last error (P704) ........125 Torque curr. ctrl. P (P312) ......87 Voltage CFC-Inj (P338).........
  • Page 187 Key word index BU 0800 en-3924...