Advertisement
Xtralis VESDA system is a very early warning aspiration type smoke detection system.
VESDA system works on the principle of laser light scattering incorporating particle counting function with a fully integrated detection chamber. The particle counting mechanism is used to prevent false alarms due to large volumes of dust or fibers or large airborne particulates presented in the sampled air and not for the purpose of smoke density measurement and detection.
The Xtralis VESDA system installed is a proven and established technology system on International Railway systems for the protection of Rail coaches.
The Xtralis VESDA Aspiration Smoke Detection System installed consists of the following components.
The detector installed is capable of indicating an alarm in four stages viz., Alert, Action, Fire1 and Fire2. The strobe light (visual indication) is triggered when the 'Action' Stage of Alarm is trigged and the sounder (audible indication) is triggered when the ' Fire1' Stage of Alarm is triggered.
The diagram below illustrates the different parts of an Air Sampling Smoke Detection System
Each detector covers an area of up to 500 m 2 for open space protection and maximum pipe length of 50 meters.
To set up a centralised monitoring system, a VESDAnet loop (RS485) is created by networking all the Xtralis VESDA Detectors installed in each coach in peer to peer/daisy chain.
The following block diagram indicates the system setup.
This VESDAnet loop is used for PC based monitoring and control using VSM-4 software.
VESDA System Manager-4 Graphic Software Based Central Monitoring
The VESDAnet loop is interfaced using High Level Interface (HLI) with a PC installed at the monitoring location. VESDA System Manager-4 (VSM-4) software is installed on the PC for complete monitoring and control of all the VESDA detectors installed.
Key features of VSM-4 software are as follows:
The following diagram indicates the typical pipe layout in each coach.
The typical arrangement of a concealed sampling point is shown in the diagram below.
These sampling points are installed at locations with public (passengers) access – passage and seating area. Inside equipment cabinet, normal sampling holes are considered. In certain locations of the train, Heat Activated Sampling Point (HASP) is used. These areas include engine room of the Power Car, Kitchen Area of Pantry Car and in all Lavotories of all the coaches. The picture below is a sample of HASP sampling head.
The HASP head operates on thermal detectors principle in its normal operating mode. As fire starts and develops, heat (ambient temperature) increases to such point that the sampling hole is opened and it becomes a normal air sampling hole, hence the detection of the fire and alarm from Xtralis VESDA detectors. As per the Certificate of Appraisal, issued by National Building Technology Centre of Australian Government, the heat activation temperature is 68 C.
DETECTOR INSTALLATION & OPERATION
DETECTOR MOUNTING
The VESDA Laser FOCUS can be installed upright, inverted or horizontally.
Note: Ensure the smoke detector is mounted away from obstructions and below ceiling Level
An exhaust deflector must be fitted for upright mounting, unless the exhaust port is connected to a return air pipe.
Do not install this unit on its side. There is a risk of particulate and condensation collecting on critical elements of the detector chamber reducing the detectors performance.
Ensure that there is sufficient clearance to mount the detector, noting the location of air sampling pipes and cable entry points. Owing to the rigid nature of the plastic pipe, installation must provide for sufficient movement in all pipework (air inlet, air exhaust and cable pipes) to allow pipe ends to be easily fitted and removed.
Mounting location
Installing the smoke detector
In all installation cases the mounting bracket must be fitted (upright) as shown in figure.
Note: Ensure the mounting surface is flat. This will permit an air tight seal to be achieved between the sampling pipe and the tapered air ports on the detector.
Prior to drilling the attachment holes for the mounting bracket, ensure that all mounting surfaces (i.e. walls, cabinet sides, etc.). are clear of electrical wiring and plumbing.
When the pipe network and cabling are already fitted, the bracket can be used to aid alignment of the detector with the pipes. The Installation procedure below explains this process.
Installation procedure
Cut the air inlet pipe and exhaust pipe (if used) at 90 deg., and to the same length (for normal and inverted mounting). Remove all rough edges. This is critical to obtain an air tight seal with the smoke detector.
Mounting bracket orientation for upright mounting
Mounting Bracket Rear View
Air inlet pipe connections
The tapered shape of the air inlet port is designed to accept standard pipes of OD 25 mm (ID 21 mm) or IPS ¾ in (OD 1.05 in) and provide an air tight seal.
Note: Do not glue the air inlet pipe to the detector. This will void your warranty.
Detector cabling requirements
The screw type terminals located on the termination card within the VESDA Laser FOCUS will accept wire sizes from 0.2 sq. mm to 2.5 sq. mm (30 – 12 AWG).
To reach the terminal block, open the field service access door, (see Controls and indicators section), and then unscrew the front cover retaining screws. Lift off and swing down the front cover. The terminal block is located on the right hand side of the detector.
Terminal block
Terminal Block Connections:
GPI – General Purpose Input (Terminals 1 & 2)
The General Purpose Input (GPI) is a programmable input. When the GPI function parameter is set to external, the detector shall indicate an external equipment fault condition by monitoring the line impedance. An End of Line (EOL) resistor is supplied with the product and must be assembled in parallel with the device to be monitored. The EOL resistor provides a known termination to the external equipment, this allows the VLF to detect open or short circuits. The detector monitors the EOL resistor, see Figure, and reports any faults when the GPI function is set to any value, except None.
These terminal blocks come assembled and should NOT be disassembled.
If GPI will not be used we recommend that you leave the EOL resistor assembled.
Power supply (Terminals 8, 9, 10 & 11)
It is recommended that the power supply be compliant with local codes and standards required by the regional authority.
Check the product termination wiring label during installation and subsequent Maintenance visits.
Operating voltage: 24 VDC nominal (18 - 30 VDC) Power consumption: 5.2 W nominal, 7.0 W in alarm Current consumption: 220 mA nominal, 295 mA in alarm
Relays (Terminals 12 - 20)
The relays allow alarm and fault signals to be hard wired to external devices, such as fire alarm control panels and loop interface modules away from the detector (example, sounding a siren at Action threshold).
Note: By default, the Fault relay is normally energized when no fault is present. For example when there is no fault present, terminal 12 is held open and terminal 14 is held closed. When there is a fault present, terminal 12 is held closed and terminal 14 is held open.
Interface card
The VESDA LaserFOCUS allows for the installation of network interface card used for networking multiple detectors to form a VESDAnet.
Network Card
The VN Card is a printed circuit board with connectors on either end. It is designed to be installed inside a smoke detector such as the VLF.
Installing the VESDAnet Card into VLF
The detector must be powered down before installing or swapping an interface card otherwise damage may occur.
Detector with front cover open showing the space for interface card inside the detector
Detector with front cover open with interface card installed inside the detector
Testing the Installed VESDAnet Interface Card
The VESDAnet Interface Card uses LEDs to signify certain conditions
To test the card:
Typical Wiring to VESDAnet – Network of detectors installed in different coaches
RS232 Compatible serial port
The RS232 serial port requires a standard 9-pin DB9 PC COM serial extension cable (male to female) for configuring the detector using a PC with VESDA System Configurator (VSC) installed, for status monitoring and command input, and for event log extraction and software upgrades.
9 Pin connector and RS232 serial port
Installation Checklist
Perform the following checks listed below to ensure that all the necessary items are completed
Perform the following checks listed below to ensure that all the necessary items are completed before handing over to a commissioning engineer.
Installation Checklist
COMMISSIONING SMOKE TEST
It is recommended that a smoke test be carried out to prove the integrity of the pipe network, to demonstrate that the system is working and to measure the transport time to the detector. This test involves introducing a smoke sample at the furthest sampling hole and then measuring the time taken for the smoke to travel to the detector. Results are logged and compared to subsequent tests to note variations of the system.
PRODUCT INTERFACE
The VESDA LaserFOCUS provides the following information and control options without the need for additional configuration tools.
Instant Recognition Display
The Instant Recognition display provides you with an immediate understanding of smoke levels relative to Fire 1 alarm threshold.
Detector control buttons
Smoke level display
The smoke level is displayed on the Smoke Dial and provides incident information essential for effective response in very early warning situations. This display provides you with an instant understanding of the smoke event relative to the Fire 1 Alarm Threshold. Between 1 and 10 segments may illuminate. Each segment is equivalent to 1/10 of a Fire 1 warning.
Smoke level and fault condition display
VESDA® LaserFOCUS VLF-250 Product Guide 37 10-sector Instant Fault Finder. Reset, Disable and Test Controls. Smoke and Flow AutoLearn Controls and Indicators. Event Log Up to 18 000 events stored. Smoke trend, flow trend, faults events, configuration events and operational events.
Date and time stamp. AutoLearn Smoke & Flow Minimum 15 minutes, maximum 15 days (default 14 days). During AutoLearn, thresholds are NOT changed from pre-set values.
When a fault is registered on the detector, the fault light remains ON for Major Fault situations and flashes for Minor Fault. The Instant Fault Finluder function is operated by pressing the Reset and Disable buttons together.
Instant Fault Finder provides rapid fault diagnosis and is an additional function of the Smoke Dial display. One or more segments of the Smoke Dial will ilminate, indicating the fault by number.
The Instant Fault Finder function aids rapid diagnosis of faults.
Instant fault finder diagnosis
The VESDA LaserFOCUS smoke detector continuously monitors its own operation and conducts frequent health checks. There are two serviceable items, the air filter cartridge and the aspirator.
Electrostatic discharge precautions need to be taken prior to removing the front cover from the detector otherwise damage may occur to the detector.
Maintenance - replaceable items
Prior to any work or maintenance being carried out on the VESDA LaserFOCUS take the necessary steps to advise the monitoring authority that power may be removed and the system disabled.
Maintenance schedule
Maintenance should be conducted by a qualified service contractor.
Replace the Filter Cartridge (VLF)
The VESDA Laser FOCUS smoke detector uses a disposable dual stage air filter cartridge. This filter removes dust contamination from sampled air and provides a clean air bleed to preserve the detector chamber optics. The detector constantly monitors filter efficiency. To maintain the operational integrity of the smoke detector, it is recommended that the filter be replaced every 2 years, or when a filter fault occurs or more often for environments that experience high levels of contamination.
A fault is raised on the detector, when the filter needs to be replaced. During the replacement process the detector needs to be informed that a new filter has been installed.
Note: Ensure the area surrounding the filter is clear of dirt and debris prior to replacement.
Note: The filter is for single use only, it cannot be cleaned and re-used.
Filter replacement steps
Ensure the detector remains powered up during filter replacement and a new filter cartridge is available:
Filter replacement
Aspirator replacement
Electrostatic discharge precautions need to be taken prior to removing the front cover from the detector otherwise damage may occur to the unit.
Aspirator removal (assumes normal mounting, see Figure):
Aspirator replacement steps
Cleaning Sampling Pipes
Follow the instructions below to clean the sample pipe network.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Need help?
Do you have a question about the VESDA and is the answer not in the manual?
Questions and answers