VESDA-E VEA-UL Installation Instructions
These installation instructions provide essential information for installing VESDA-E VEA-040-A00-UL or VEA-040-A10-UL Aspirating Smoke Detectors in accordance with the system design. Additional
installation and product documentation is listed below in the Reference Documents section. For installation instructions for the StaX module VER-A40-40-STX see document 27772.
Package Contents
The detector is shipped with the following components:
1 aspirating smoke detector
1 mounting bracket
1 mounting template for directly mounting the detector to the mounting surface
1 End of Line Resistor for the monitored GPI
1 installation instruction sheet (this sheet)
1 tube cutter (taped inside the detector door)
Prerequisites
24V DC Power Supply and backup battery, compliant with local codes and standards.
Screws and inserts that are appropriate for the installation location.
Type A to Type B USB Interface Lead, required for initial configuration of the detector.
Labels as specified in the system design, e.g. Sampling Point labels
Cable glands that are compliant with the IP 40 rating of the detector.
Conduit, as specified in the system design.
2
1.1 mm
(18 AWG) or larger wiring for power.
2
2
0.2 mm
to 2.5 mm
(24 - 14 AWG) wiring for relays.
PC or laptop installed with Xtralis VSC for initial configuration.
Standard connection instructions for where the detectors are to be added to a corporate
network.
Standards Compliance
UL/ ULC
Detector Setting
Max
Open Area
Standard
Standard
Velocity: 0 to 4000fpm
Special Application 50m (164 ft)
High
Standard
Velocity: 0 to 4000fpm
Special Application: 100m (328 ft)
High
Enhanced
Velocity: 0 to 4000fpm
DUCT Applications 50m (164 ft)
High
Standard
Velocity: 0 to 4000fpm
DUCT Applications 100m (328 ft)
High
Enhanced
Velocity: 0 to 4000fpm
Power Consumption
Supply Voltage
Max Current: Quiesent
Max Current: Alarm
Peak Current
Power Consumption @ 24VDC
Tubes
VEA-040-A00-UL
VEA-040-A10-UL
Environmental Requirements
Temperature
-
Ambient: 32°F to 100°F (0°C to 38°C)
-
Sampled Air: 32°F to 122°F (0°C to 50°C) *
Humidity: 5-95% RH, non-condensing
* The sampled air temperature shall be within the Ambient temperature specification at entry into the Detector. Refer to
Xtralis Design Guides and Application Notes for sampled air pre-conditioning.
Note:
Please consult your Xtralis representative for information on operation outside these
parameters or where sampled air is continually above 0.015% obs/ft (0.05% obs/m)
under normal operating conditions.
Transport Time
Transport time is determined by the length of the microbore tubes used on the detector. There is no
provision for the user to adjust the transport time and there is no tube modelling tool required for
VEA. The transport time is given in the table below for various tube lengths.
Maximum Tube Length
Longest Transport Time
98ft [30m]
131ft [40m]
164ft [50m]
197ft [60m]
230ft [70m]
262ft [80m]
295ft [90m]
328ft [100m]
Reference Documents
Additional installation and product information is contained in the following documents, which are
available for download in the Xtralis partner extranet at www.xtralis.com.
36402 - VESDA-E VEA-040-A00-UL Product Guide
36401 - VESDA-E VEA-040-A10-UL Product Guide
32407 - VESDA-E VEA Commissioning Guide
Tube Length
Transport
Time (s)
(m)
(ft)
Min
Max
Min
Max
Min
Max
Min
50
30
164
98
51
37
50
30
164
98
51
37
100
30
328
98
79
37
50
50
164
164
51
51
100
50
328
164
79
51
18 - 30 VDC
VEA-040-A00-UL
VEA-040-A10-UL
2.10A
2.35A
3.5A
Quiescent Current (A)
Alarm Current (A)
40
1.0
1.0
Up to 40 seconds
Up to 46 seconds
Up to 52 seconds
Up to 60 seconds
Up to 65 seconds
Up to 70 seconds
Up to 75 seconds
Up to 80 seconds
Installation Instructions
The VEA detector must be mounted in an upright position on a solid surface. Do not mount the
detector with a sideways or inverted orientation.
Installation Instructions
Remove transit screws
Important: Remove transit screws.
H
H
H H
Tube Sensitivity
Balance
Mount the detector using the mounting bracket
Max
Min
Position electrical conduit, mark pilot holes
100
81
B
C
N/A
D
D
Secure Mounting Bracket
E
40
Attach the detector to the mounting bracket
1.6
1.6
Secure the detector to the mounting bracket
G
Mount the detector directly to the mounting surface
Use the provided mounting template. Refer to the product guide for further information.
Prepare Detector:
Test Port Plugs
Ensure that the two smoke test port plugs (I) are in place and fully inserted.
Exhaust Port
Ensure that the exhaust port (J) at the bottom of the left side of the detector is open.
Remove the two transit screws (H).
Note:
The transit screws are used to hold the air
pump during transit. If the screws are not
removed excessive noise will be generated.
Position the mounting bracket (A) to allow electrical
conduit (B) to line up horizontally with the alignment
marks (C).
Mark positions for pilot holes on the mounting surface
A
through five recessed screw holes (D).
D
Remove the mouting plate and drill pilot holes.
D
D
Reposition the mounting bracket and secure to
mounting surface by screwing the five screws (E) into
E
E
their pilot holes.
E
E
Align the four mounting studs (F) on the rear of the
F
F
F
detector with the mounting stud slots on the mounting
bracket, and slide the detector down until the top
of the detector is flush with the top of the mounting
bracket.
F
Open the door by inserting an Allen key (preferred),
Philips head screwdriver or flat blade screwdriver with
the blade vertically oriented into the hole at bottom left
and press firmly.
Remove the tape covering the partially inserted
locking screw (G).
Insert and tighten the locking screw (G). This secures
the detector to the mounting bracket.
Insert the electrical conduit.
Page 1 of 2

Advertisement

loading
Need help?

Need help?

Do you have a question about the VESDA-E VEA-UL and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Xtralis VESDA-E VEA-UL

  • Page 1 Open the door by inserting an Allen key (preferred), Note: Please consult your Xtralis representative for information on operation outside these Philips head screwdriver or flat blade screwdriver with parameters or where sampled air is continually above 0.015% obs/ft (0.05% obs/m) the blade vertically oriented into the hole at bottom left under normal operating conditions.
  • Page 2 This document is subject to copyright owned by Xtralis. You agree not to copy, communicate to the public, adapt, distribute, transfer, sell, modify or publish any contents of this document without the express prior written consent of Xtralis.

This manual is also suitable for:

Vesda-e vea-040-a00-ulVesda-e vea-040-a10-ul