F I L T E R I N G F I L T E R I N G S E - 1 0 5 GF-GC MONITOR GF-GC MONITOR Copyright 2014 by Littelfuse Startco All rights reserved. Document Number: PM-1300-EN Printed in Canada.
Page 2
Page i SE-105 Ground-Fault Ground-Check Monitor Rev. 13-B-090814 This page intentionally left blank.
2.2 Indication and Reset ..........1 Specifications are subject to change without notice. 2.3 Fusing ..............1 Littelfuse Startco is not liable for contingent or Installation ............2 consequential damages, or for expenses sustained as a 3.1 SE-105 ..............2 result of incorrect application, incorrect adjustment, or a 3.2 Ground-Fault CT ...........
Page 4
Page iii SE-105 Ground-Fault Ground-Check Monitor Rev. 13-B-090814 This page intentionally left blank.
The ground-check circuit is non-latching and does not require a reset. Terminals are provided for : The SE-105 is not a lock-out device. Follow remote indication and reset as shown in Fig. 1. lock-out procedures for maintenance. latching ground-check...
3. I NSTALLATION 3.1 SE-105 SE-105 outline and mounting details are shown in Fig. 2. Typical connections are shown in Fig. 1. Connect supply voltage to L1 and L2. For a 120-Vac supply, connect supply neutral to L2. For direct-current supply (Option D), connect supply negative to L2.
SE-105 terminals CT1 and CT2. The CT connection to current transformers are shown in Fig. 3. Pass the phase the SE-105 is not polarity sensitive. Ground one side of conductors through the CT window as shown in Fig. 1. the CT secondary.
Page 5 SE-105 Ground-Fault Ground-Check Monitor Rev. 13-B-090814 44.5 MAX (1.75) NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING SCREWS: M4 OR 8-32. BLACK WHITE SIDE FRONT (0.37) TAP M4 OR 8-32 BOTTOM MOUNTING DETAIL DIMENSIONS PART NUMBER 55.9 (2.20) 120.7 (4.75)
OMPATIBILITY For 22-mm-component applications, use the RK-102 Remote Indication and Reset Kit. Connect terminal X2 The SE-105 is a direct replacement for the SEL-100, of the green ground-check indicator to CI, terminal X2 SEL-100TD, SE-101, SE-101S, SE-102, SE-102S, SE- of the red ground-fault indicator to GI, and connect 102M, SE-103, and SE-103S.
Page 11
Page 7 SE-105 Ground-Fault Ground-Check Monitor Rev. 13-B-090814 41.5 40.0 (1.63) (1.57) 40.0 22.2 10.5 19.0 (1.57) (0.87) (0.41) (0.75) S E - T A 6 T E R M I N A T I O N A S S E M B L Y...
Page 12 SE-105 Ground-Fault Ground-Check Monitor Rev. 13-B-090814 Trip Time ......0.2 s (GC open), 5. T ECHNICAL PECIFICATIONS 0.5 s (GC to G short) Supply: Trip-Time Accuracy ... +10, -30% ac ..........10 VA, 120 or 240 Vac GC-Loop ....
Littelfuse Startco will (at Littelfuse Startco’s option) Applicable only on 240 Vac Supply (Option E in the repair, replace, or refund the original purchase price of an ordering information). SE-105 that is determined by Littelfuse Startco to be 6. O RDERING NFORMATION defective if it is returned to the factory, freight prepaid, within the warranty period.
0.5 to 9.9 A for a duration of 0.1 to 9.9 seconds. Set the test current to 0.6, 2.3, or 4.6 A for SE-105 units set at 0.5, 2.0, or 4.0 A respectively. Fig. 13b shows a test circuit using an SE-100T Ground-Fault-Relay Tester.