aci XT-0-5V-0001 Installation And Operation Instruction Manual

Advertisement

PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION!
APPLICATION
The XT 0-5V 0001 provides temperature space monitoring with a backlit LCD. The unit will
display a Temperature Setpoint based on a voltage input. A setup menu provides easy output and
display configuration changes.
INSTALLATION
Precautions
• R
EMOVE POWER BEFORE WIRING
WITH POWER APPLIED
.
BOARD
• A
N ISOLATION TRANSFORMER IS RECOMMENDED WHEN POWERING THE
DEVICE WITH
• D
O NOT RUN THE
POWERED WIRING
• F
AILURE TO WIRE DEVICES WITH THE CORRECT POLARITY WHEN USING A
SHARED TRANSFORMER MAY RESULT IN DAMAGE TO ANY DEVICE POWERED
BY THE SHARED TRANSFORMER
AUTOMATION COMPONENTS, INC
2305 Pleasant View Road
Middleton, Wisconsin 53562 (888) 967-5224
www.workaci.com
Installation and Operation Instructions
. N
. D
O NOT ALLOW LIVE WIRES TO TOUCH THE CIRCUIT
24VAC.
XT 0-5V 0001
WIRING IN ANY CONDUIT WITH LINE
.
.
Page 1 of 6
EVER CONNECT OR DISCONNECT WIRING
XT-0-5V-0001
Version : 4.0
I0000650

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the XT-0-5V-0001 and is the answer not in the manual?

Questions and answers

Summary of Contents for aci XT-0-5V-0001

  • Page 1 Installation and Operation Instructions XT-0-5V-0001 PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION! APPLICATION The XT 0-5V 0001 provides temperature space monitoring with a backlit LCD. The unit will display a Temperature Setpoint based on a voltage input. A setup menu provides easy output and display configuration changes.
  • Page 2 Mounting Carefully separate the cover from the base by pulling the cover and base apart towards the bottom of the device. The hex screw may need to be turned in to release the cover. Route the wires through the access hole in the center of the base and screw them into the terminal blocks.
  • Page 3: Operation

    OPERATION Keypad The keypad comes in 2 button or 4 button versions. A 2 button keypad does not include SETUP and SELECT. SELECT SETUP Normal Mode The LCD can display temperature and temperature setpoint. The display configuration can be setup when ordered or changed through the setup menu. The top number is the temperature and the bottom number is the setpoint.
  • Page 4: Setup Mode

    Voltage Step Degrees F 0.27 0.55 0.82 1.09 1.37 1.64 1.91 2.18 2.46 2.73 3.00 Chart #1 The display will change to show the setpoint in the top numbers and the temperature will go away. The display will go back to the normal mode after 10 seconds.
  • Page 5 Setup Menu Additional Options Menu Temperature Menu RH Menu Display Menu Fan Menu System Menu Sensor Setup Sensor Sensor Setup Setup Setup Setup Setup Sensor Sensor Sensor Display Display Display Display Display Display Temperature Options Systems Options Additional Options SELECT RH Options Fan Options Display Options...
  • Page 6: Setup Lockout

    RoHS, REACH Warranty Statement The A/TUC2 Series and the A/TUCH2 Series are covered by ACI’s Five (5) Year Limited Warranty, which is located in the front of ACI’s SENSORS AND TRANSMITTERS CATALOG or can be found on ACI’s web site, which is: www.workaci.com...